AXL F DO8/2 2A 1H
8238_en_04 PHOENIX CONTACT 9 / 14
9 Local diagnostic and status indicators
Figure 6 Local diagnostic and status indicators
D
UO
E1
30 3231 33
20 2221 23
10 1211 13
00 0201 03
Designati
on
Color Meaning State Description
DRed/
yellow/
green
Diagnostics of local bus communication
Run Green ON The device is ready for operation, communication within the station is
OK.
All data is valid. An error has not occurred.
Active Green
flashing
The device is ready for operation, communication within the station is
OK.
The data is not valid. Valid data from the controller/higher-level
network not available.
There is no fault in the module.
Device
application not
active
Flashing
green/yellow
The device is ready for operation, communication within the station is
OK.
Output data cannot be outputted and/or input data cannot be read.
There is a fault on the periphery side of the module..
Ready Yellow ON The device is ready for operation but did not detect a valid cycle after
power-up.
Connected Yellow
flashing
The device is not (yet) part of the active configuration.
Reset Red ON The device is ready for operation but has lost the connection to the
bus head.
Not connected Flashing red The device is ready for operation but there is no connection to the
previously existing device.
Power down OFF Device is in (power) reset.
U
O
Green U
Output
ON Supply for digital output modules present.
OFF Supply for digital output modules is not present.
E1 Red Peripheral fault ON Breakdown or overload/short-circuit of an output.
OFF No I/O error.
00 ... 03,
20 ... 23
Yellow Output status ON Output is set.
OFF Output is not set.
10 ... 13,
30 ... 33
Red Diagnostics of
the output
ON Short-circuit/overload of the output.
OFF No short-circuit/overload of the output.