FL-PP-RJ45... / FL CAT5...
104622_en_04 PHOENIX CONTACT 12
11 Patch panel FL CAT5 TERMINAL BOX with screw connection terminal blocks
11.1 Design
1 RJ45 socket (TP port)
2 Screw connection terminal blocks
3 Strain relief with shield connection
4 DIN rail
5 Universal snap-on foot for DIN rails
11.2 Dimensions
Figure 12 Dimensions of FL CAT5 TERMINAL BOX
11.3 Connecting the Ethernet network
Twisted pair interface (TP port)
• Take the Ethernet patch cable which leads to the termi-
nation device and has a RJ45 connector, and push this
into the RJ45 socket (TP port) until the connector audi-
bly snaps in.
Pin assignment and color coding
Figure 13 Ethernet (IEC 80.3u: TIA 568 A, TIA 568 B)
and PROFINET
– YE = yellow
–OG = orange
–WH = white
–BU = blue
– GN = green
Screw connection terminal blocks
Figure 14 Required stripping lengths
– a = 10 mm
–b = 10 mm
–c = 5 mm
• Remove cable sheath in accordance with length B.
• Fold back 10 mm of the braided shield over the outer
sheath.
• Remove the aluminum foil.
• Strip 5 mm off each single wire.
• Lay the shielding under the clip bracket of the strain re-
lief and screw tight.
• Connect the single wires to the screw terminal blocks. If
possible, make sure the single wires remain twisted up
to the connection terminal blocks.
Only use shielded twisted pair cables and corre-
sponding shielded RJ45 connectors.
PROFINET
BU6
WH3
OG2
YE1
1236
GN6
WH/GN3
OG2
WH/OG1
1236
OG6
WH/OG3
GN2
WH/GN1
1236
TIA 568 A
Ethernet