1Description
Hybrid motor starter
ELR H3-IES-PT- 24DC/500AC-...
© PHOENIX CONTACT
Data sheet
The 3-phase hybrid motor starter with current monitoring
provides the following functions.
Right contactor
Motor overload protection relay
EMERGENCY STOP to performance level PLe
The amount of cabling required is reduced to a minimum by
the internal locking circuit and the load wiring.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products
.
This data sheet is valid for all products listed on the following page:
105518_en_01
2013-12-17
ELR H3-IES-PT- 24DC/500AC-...
105518_en_01 PHOENIX CONTACT 2
2Table of contents
1 Description .............................................................................................................................. 1
2 Table of contents..................................................................................................................... 2
3 Ordering data .......................................................................................................................... 3
4 Technical data ......................................................................................................................... 3
5 Safety regulations and installation notes.................................................................................. 6
6 Operating and indication elements .......................................................................................... 7
7 Connection notes .................................................................................................................... 7
7.1 Mains connection and line protection........................................................................................ 7
7.2 Connecting cables ............................................................................................................... 8
7.3 Block diagram..................................................................................................................... 8
8 Function................................................................................................................................... 9
8.1 Status and diagnostics indicators............................................................................................. 9
8.2 Diagnostic function............................................................................................................... 9
8.3 Parameterization - Nominal current setting ............................................................................... 11
9 Application examples ............................................................................................................ 12
9.1 Emergency stop ................................................................................................................ 12
9.2 Safety door (emergency stop)............................................................................................... 13
9.3 Motor protection ................................................................................................................ 14
9.4 Motor with brake................................................................................................................ 14
9.5 Auxiliary relay connection .................................................................................................... 14
10 Safety functions..................................................................................................................... 15
10.1 Safe shutdown .................................................................................................................. 15
10.2 Motor protection ................................................................................................................ 15
11 Trigger characteristic for20°C............................................................................................... 16
12 Derating curves for 100%operating time............................................................................... 17
ELR H3-IES-PT- 24DC/500AC-...
105518_en_01 PHOENIX CONTACT 3
Description Type Order No. Pcs. / Pkt.
“3 in 1” hybrid motor starter for starting 3~ AC motors up to 550 V AC, with
24 V DC input, 0.6 A output current, emergency stop function, adjustable
overload shutdown, and push-in connection.
ELR H3-IES-PT- 24DC/500AC-0,6 2903914 1
“3 in 1” hybrid motor starter for starting 3~ AC motors up to 550 V AC, with
24 V DC input, 2.4 A output current, emergency stop function, adjustable
overload shutdown, and push-in connection.
ELR H3-IES-PT- 24DC/500AC-2 2903916 1
“3 in 1” hybrid motor starter for starting 3~ AC motors up to 550 V AC, with
24 V DC input, 9 A output current, emergency stop function, adjustable
overload shutdown, and push-in connection.
ELR H3-IES-PT- 24DC/500AC-9 2903918 1
3Ordering data
4 Technical data
Device supply
Rated control supply voltage U
S
24 V DC (According to IEC 60947-1)
Rated control supply voltage range 19.2 V DC ... 30 V DC (32 V DC, max. 1 min. )
Voltage range with reference to U
S
0.8 ... 1.25
Rated control supply current I
S
40 mA
Protective circuit Protection against polarity reversal
Surge protection
Control input
Typical input current at U
N
5 mA
Rated control supply current I
S
40 mA (According to IEC 60947-1)
Rated actuating voltage U
C
24 V DC
Voltage range with reference to U
C
0.8 ... 1.25
Rated actuating current I
C
5 mA
Triggering voltage range "High" 19.2 V DC ... 30 V DC
Triggering voltage range "Low" -3 V DC ... 9.6 V DC
Switching level "safe off" < 5 V DC
Protective circuit Protection against polarity reversal
Typical response time < 35 ms
Typical turn-off time < 40 ms
AC output
Nominal output voltage 500 V AC ( 50 Hz , 60 Hz )
Nominal output voltage range 42 V AC ... 550 V AC
Load current see derating curve 75 mA ... max. 600 mA / 180 mA ... max. 2.4 A / 1.5 A ... max. 9 A
Rated operating current at AC-51 0.6 A / 2.4 A / 9 A
Rated operating current at AC-53a 0.6 A / 2.4 A / 6.5 A
Leakage current 0 mA / 0 mA / 0 mA
Residual voltage at I
e
< 0.2 V / < 0.3 V / < 0.5 V
Surge current 100 A (t = 10 ms)
Protective circuit Surge protection Varistor

2903914

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules ELR H3-IES-PT- 24DC/ 500AC-0.6
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union