ELR H3-IES-PT- 24DC/500AC-...
105518_en_01 PHOENIX CONTACT 15
10 Safety functions
10.1 Safe shutdown
10.2 Motor protection
System conditions
Database for failure rates SN29500
System type (consisting of subsystems) Type B
Standard used IEC61508
Beta factor 1%
MTTF [years] (mean time to failure at
ambient temperature of40°C)
43.0
Ambient temperature 40°C
MTTFd [years] - mean time to dan-
gerous failure
518
Shutdown time [ms] 80
sd [FIT] - safe, detectable 543
su [FIT] - safe, undetectable 852
dd [FIT] - dangerous, detectable 218
du [FIT] - dangerous, undetectable 2.4
SFF [%] - safe failure fraction 99.9
DCS [%] - diagnostic coverage safe 38.9
DC [%] - diagnostic coverage 99
PFH - probability of failure per hour 2.4 x 10
-9
Safety level according to IEC/CEI 61508-1: SIL 3
ISO 13849-1: category 3 PL e
EN 954-1: category 3
Ambient temperature 40°C
MTTFd [years] - mean time to dan-
gerous failure
447
Shutdown time [ms] According to Class 10A, IEC/CEI 60947
sd [FIT] - safe, detectable 517
su [FIT] - safe, undetectable 809
dd [FIT] - dangerous, detectable 239
du [FIT] - dangerous, undetectable 17
SFF [%] - safe failure fraction 99
DCS [%] - diagnostic coverage safe 39.0
DC [%] - diagnostic coverage 93.3
Safety level according to IEC/CEI 61508-1: SIL 2
Additional safety data is available on request.