ELR H3-IES-PT- 24DC/500AC-...
105518_en_01 PHOENIX CONTACT 10
Explanation: A = LED switched off / E = LED lights continuously / B = LED flashes ca. 2 Hz (50:50) / Aut = Automatic / Man =
Manual / Nm = Not possible / Ne = Not required
Status Description PWR ERR I
adj.
ON Error
acknow-
ledgment
Green Red Yellow
OFF Supply voltage not present A A A A -
Ready to operate Supply voltage present E A A A -
Drive switched on EAAE
Internal error Internal device error - device replacement
required
EEAANm
External error in the con-
troller or the I/O devices
(maintenance require-
ment, NE44)
Motor protection function: The motor
current is higher than the motor nominal
current specification: Cooling time elapsing
(20 minutes)
EBAEAut
After 2min, “ON” flashes: a manual reset is
possible
EBABMan
Error restoring the system state: Check-
sum error. The thermal memory of the
motor protection function is set to the maxi-
mum value. The error must be manually ac-
knowledged.
EBBBMan
Symmetry: The two motor currents deviate
from each other by more than 33%.
EBAAMan
Blocking: The max. measurable motor cur-
rent is exceeded for more than 2s.
EBABMan
Message (power path re-
mains switched on)
Message with pending control signal:
- 2 or more phases are missing
- No motor connected
- Motor current in at least two phases >2s
below the minimum current value that can
be set
BBAENe
ELR H3-IES-PT- 24DC/500AC-...
105518_en_01 PHOENIX CONTACT 11
Error acknowledgment
Three different options are available for error acknowledg-
ment.
Manual (reset button)
Press the reset button on the front of the device.
When pressing the reset button for more than 2 s (approxi-
mately), the device returns to the error state.
Pressing the reset button for more than 6s changes the de-
vice to the "Parameterization" mode.
Manual (remote acknowledgment point)
Connect a button (N/O contact) between the MAN and RES
terminals.
An acknowledgement is triggered as soon as a positive
edge is detected at the MAN input. If no negative edge is de-
tected after approx. 2s, the device adopts an error state
since manipulation or an error in the acknowledgment circuit
may have occurred.
Automatic
Establish an electrical connection between the RES and
AUT terminals.
Following triggering of motor protection monitoring and sub-
sequent cooling, the device performs an automatic acknowl-
edgment.
Feedback
As soon as the device detects an error or indicates a mes-
sage, the reply relay is switched, i.e. the N/O contact is
closed or the N/C contact is opened. This behavior matches
that of a motor protection switch or motor protection relay.
8.3 Parameterization - Nominal current setting
Press the reset button for more than 6 s to change to the
"Parameterization" mode. The green PWR flashes
once.
In the Parameterization mode, the LEDs are switched off
every 2s for 0.3s to distinguish this mode from other oper-
ating modes.
Set the nominal drive current with the 240° potentiome-
ter. The nominal current is specified in 16 stages. The
four LEDs show the set current.
Store this value by pressing the reset button again (non-
volatile area of the mass storage).
Press the reset button for more than 2s (and less than
6s) to display the set current for 3s. This function is
only possible if 1) the device is not activated, and 2)
there is no error at the device.
The RES terminal provides the voltage for the
reset.
In variants with a rated control supply voltage
of 24VDC, this is 24VDC.
The feedback is for signaling purposes only
and is not part of the safety chain. It is there-
fore not included in the safety considerations.
Code Nominal current [mA]
PWR ERR I
adj.
ON 0.6A 2 A 9 A
0 0 0 0 75 180 1500
0 0 0 1 110 250 2000
0 0 1 0 145 410 2500
0 0 1 1 180 560 3000
0 1 0 0 215 710 3500
0 1 0 1 250 870 4000
0 1 1 0 285 1020 4500
0 1 1 1 320 1170 5000
1 0 0 0 355 1330 5500
1 0 0 1 390 1480 6000
1 0 1 0 425 1630 6500
1 0 1 1 460 1790 7000
1 1 0 0 495 1940 7500
1 1 0 1 530 2090 8000
1 1 1 0 565 2250 8500
1 1 1 1 600 2400 9000
NOTE
Lock monitoring is activated from a motor cur-
rent of 45A.
ELR H3-IES-PT- 24DC/500AC-...
105518_en_01 PHOENIX CONTACT 12
9 Application examples
9.1 Emergency stop
The hybrid motor starter can be integrated into an emer-
gency stop chain.
Figure 4 Emergency stop
1 Supply 1
2 Emergency stop
3 Reset button
4 Supply 2
The control supply voltage is switched off via a safety relay
as soon as the emergency stop button is actuated.
If shutdown is performed, e.g.,from a “safe controller” with
semiconductor outputs, the residual voltage must be <
5VDC.
Interruptions 1ms are filtered.
NOTE
Switching off the control voltage supply with a
controlled motor always results in wear in the
hybrid motor starter.
This type of switching off should only be used
if no more than 10,000 shutdowns can be ex-
pected over the entire lifetime of the system.
U1
V1
W1
PE
M
3
S11
S12
S21
S22
13
23
31
14
24
32
S2
S2
S3
F1
L1
L2
L3
N
PE
A2
A1
PSR-SCP-24UC/ESA4/2X1/1X2
S33
S34
24 V DC
GND
97
2/
T1
4/
T2
6/
T3
ON
1/
L1
3/
L2
5/
L3
ELR H3-.../500AC-...
24 V DC
GND
96/98
95
RES
MAN
AUT
U
S
E
1
2
3
4

2903914

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules ELR H3-IES-PT- 24DC/ 500AC-0.6
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet