ELR H3-IES-PT- 24DC/500AC-...
105518_en_01 PHOENIX CONTACT 16
11 Trigger characteristic for20°C
Figure 6 Trigger characteristic
12345678910
0,5
2
5
10
3
1
20
50
100
30
200
I/I
N
t [s]
= Class 10 A
= Min
=
= Max
I>45A=>t<2s
t [s] Release time in seconds
I/I
N
Overcurrent factor: the ratio between the actual current and the parameterized nominal current
ELR H3-IES-PT- 24DC/500AC-...
105518_en_01 17
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
12 Derating curves for 100%operating time
Additional data is available on request.
Figure 7 Derating curve
The adjustment factors described here refer to hybrid motor
starters with a maximum load current of 9A. You can deter-
mine the maximum permissible rated current of the motor
using the load current, the overcurrent factor (see data sheet
of the relevant motor), and the 9A derating curve.
0 10203040506070
0
1
2
3
4
5
6
7
8
9
I=9A
t
A
[°C]
I [A]
L
I = 2,4 A
I=9A
I = 0,6 A
I
L
= Load current [A]
t
A
= Ambient temperature [°C]
I
A
= Starting current [A]
= Aligned with 20mm spacing
= Aligned without spacing
9A derating curve
Overcurrent factor I
A
/I
N
12345678910
Adjustment factor K111110.960.830.720.640.58
Overcurrent factor 1 Utilization category AC-51
Overcurrent factor 8 Utilization category AC-53a
Example 1
Motor with overcurrent factor I
A
/I
N
(from motor
data sheet)
8
Adjustment factor K 0.72
Max. permissible load current I
L
at30°C, not
aligned (from derating curve)
9 A
Max. permissible rated current I
N
of the motor 6.5A
Example 2
Motor with overcurrent factor I
A
/I
N
(from motor
data sheet)
5
Adjustment factor K 1
Max. permissible load current I
L
at60°C, aligned
(from derating curve)
3.2 A
Max. permissible rated current I
N
of the motor 3.2 A

2903914

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules ELR H3-IES-PT- 24DC/ 500AC-0.6
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet