IB IL TEMP 4/8 RTD ...
7079_en_05 PHOENIX CONTACT 10
11 Programming data/configuration data
INTERBUS (local bus) Other bus systems
12 Process data
The terminal has five process data words and one PCP word.
Figure 6 Order of the process data words
13 OUT process data words
Five process data output words are available.
Configure the terminal channels via the OUT process data
words OUT1 and OUT2. In this context, the output word
OUT1 contains the command and the output word OUT2
contains the parameters belonging to this command.
The following configurations are possible:
Configuration errors are indicated in the status word. The
configuration settings are stored in a volatile memory.
If you change the configuration, the message "Measured
value invalid" appears (diagnostic code 8004
hex
), until new
measured values are available.
ID code DF
hex
(223
dec
)
Length code 05
hex
Process data channel 80 bits
Input address area 5 words
Output address area 5 words
Parameter channel (PCP) 1 word
Register length (bus) 6 words
For the programming data/configuration data of
other bus systems, please refer to the corre-
sponding electronic device data sheet (e.g.,
GSD, EDS).
O U T 1
7 0 6 3 A 0 0 8
O U T 2 O U T 3 O U T 4 O U T 5
I N 2 I N 3 I N 4 I N 5
C o n t r o l w o r d
S t a t u s w o r d
I N 1
O U T
I N
Configuration Short
designa-
tion
Default
Selection of mean-value
generation (filtering)
Filter 16-sample
mean value
Type of sensor connection Connec-
tion
3-wire tech-
nology
Value of reference resistance R
0
R
0
100 Ω
Resolution setting Resolution 0.1°C
Selection of the format for repre-
senting measured values
Format IBIL format
Sensor type setting Sensor
type
Pt100 (DIN)
Please note that extended diagnostics is only
possible if the IB IL format is configured as the for-
mat for representing the measured values. As this
format is preset on the terminal, it is available as
soon as the voltage is applied.
IB IL TEMP 4/8 RTD ...
7079_en_05 PHOENIX CONTACT 11
13.1 Output word OUT1 (control word)
Bit 15 to bit 8 (command code):
CCC = channel number
13.2 Output word OUT2 (parameter word)
The parameters for the commands 4x00
hex
, 5x00
hex
, and
6000
hex
must be specified in OUT2. This parameter word is
only evaluated for these commands.
OUT1
Bit 1514131211109876543210
Assignment
Command code 00000000
Bit 15 to bit 8 OUT1 Command function
0 0 0 0 0 C C C 0x00
hex
Read measured value in IN2 channel-by-channel.
0 0 0 0 1 0 0 0 0800
hex
Read measured values of channels 1 to 4 in IN2 to IN5.
0 0 0 0 1 0 0 1 0900
hex
Read measured values of channel 5 to 8 into IN2 to IN5.
0 0 0 0 1 0 1 00A00
hex
Read measured values of channels 1 to 4 in IN2 to IN5.
Conversion of these channels only (shorter conversion time)
0 0 0 1 0 C C C 1x00
hex
Read configuration in IN2 channel-by-channel.
0 0 1 1 1 1 0 03C00
hex
Read firmware version and module ID in IN2.
0 1 0 0 0 C C C 4x00
hex
Configure channel, configuration in OUT2
0 1 0 1 0 C C C 5x00
hex
Configure channel and read measured value of the channel,
configuration in OUT2, measured value in IN2.
0 1 1 0 0 0 0 0 6000
hex
Configure entire terminal (all channels);
configuration in OUT2.
OUT2
Bit 1514131211109876543210
Assignment 0
Filter 2/3 R
0
Resolution Format Sensor type
Filter Selects mean value generation. After every
conversion, the measured value is saved in a
mean value memory via which the mean
value is generated. The memory size can be
selected with the filter option. E.g., for a 16-
sample mean value, the mean value is gen-
erated using the last 16 measured values.
2/3 Connection method, 2-wire or 3-wire
R
0
Selection of sensor resistance at 0°C.
Here, for example, you can select whether
Pt100, Pt500, Pt1000 or Pt10000 are to be
used for the platinum sensor type.
Resolution Quantization of the measured value, choice
between °Celsius or °Fahrenheit
Format Represents the measured value in the IN
process data
Sensor type Sets the selected sensor type
If invalid parameters are specified in the parame-
ter word, the command will not be executed. The
command is acknowledged in the input words
with the set error bit.
IB IL TEMP 4/8 RTD ...
7079_en_05 PHOENIX CONTACT 12
13.3 Parameters for configuration
The values displayed in bold are default settings.
Bit 14 and bit 13: Bit 12:
Bit 11 to bit 8
Bit 7 and bit 6:
Bit 5 and bit 4
Code Filter
dec bin
00016-sample mean value
101No mean value
2 10 4-sample mean value
3 11 32-sample mean value
Code Connection method (2/3)
dec bin
003-wire
112-wire
Code R
0
[Ω] Code R
0
[Ω]
dec bin hex dec bin hex
0 0000 0 100 8 1000 8 240
1 0001 1 10 9 1001 9 300
2 0010 2 20 10 1010 A 400
3 0011 3 30 11 1011 B 500
4 0100 4 50 12 1100 C 1000
5 0101 5 120 13 1101 D 1500
6 0110 6 150 14 1110 E 2000
7 0111 7 200 15 1111 F 10000
Code Resolution for sensor type
dec bin 0 to 11 13
(Potentiometer [%])
14
(Linear R: 0 to 400 Ω)
15
(Linear R: 0 to 20000 Ω)
0 00 0.1°C 1% 0.1 Ω 1 Ω
1 01 0.01°C 0.1% 0.01 Ω 0.1 Ω
2 10 0.1°F Reserved Reserved Reserved
3110.01°F
Code Format
dec bin
0 00 IB IL format (15 bits + sign bit with extended diagnostics)
1 01 IB ST format (12 bits + sign bit + 3 diagnostic bits)
2 10 S7-compatible format (15 bits + sign bit)