IB IL TEMP 4/8 RTD ...
7079_en_05 PHOENIX CONTACT 11
13.1 Output word OUT1 (control word)
Bit 15 to bit 8 (command code):
CCC = channel number
13.2 Output word OUT2 (parameter word)
The parameters for the commands 4x00
hex
, 5x00
hex
, and
6000
hex
must be specified in OUT2. This parameter word is
only evaluated for these commands.
OUT1
Bit 1514131211109876543210
Assignment
Command code 00000000
Bit 15 to bit 8 OUT1 Command function
0 0 0 0 0 C C C 0x00
hex
Read measured value in IN2 channel-by-channel.
0 0 0 0 1 0 0 0 0800
hex
Read measured values of channels 1 to 4 in IN2 to IN5.
0 0 0 0 1 0 0 1 0900
hex
Read measured values of channel 5 to 8 into IN2 to IN5.
0 0 0 0 1 0 1 00A00
hex
Read measured values of channels 1 to 4 in IN2 to IN5.
Conversion of these channels only (shorter conversion time)
0 0 0 1 0 C C C 1x00
hex
Read configuration in IN2 channel-by-channel.
0 0 1 1 1 1 0 03C00
hex
Read firmware version and module ID in IN2.
0 1 0 0 0 C C C 4x00
hex
Configure channel, configuration in OUT2
0 1 0 1 0 C C C 5x00
hex
Configure channel and read measured value of the channel,
configuration in OUT2, measured value in IN2.
0 1 1 0 0 0 0 0 6000
hex
Configure entire terminal (all channels);
configuration in OUT2.
OUT2
Bit 1514131211109876543210
Assignment 0
Filter 2/3 R
0
Resolution Format Sensor type
Filter Selects mean value generation. After every
conversion, the measured value is saved in a
mean value memory via which the mean
value is generated. The memory size can be
selected with the filter option. E.g., for a 16-
sample mean value, the mean value is gen-
erated using the last 16 measured values.
2/3 Connection method, 2-wire or 3-wire
R
0
Selection of sensor resistance at 0°C.
Here, for example, you can select whether
Pt100, Pt500, Pt1000 or Pt10000 are to be
used for the platinum sensor type.
Resolution Quantization of the measured value, choice
between °Celsius or °Fahrenheit
Format Represents the measured value in the IN
process data
Sensor type Sets the selected sensor type
If invalid parameters are specified in the parame-
ter word, the command will not be executed. The
command is acknowledged in the input words
with the set error bit.