IB IL TEMP 4/8 RTD ...
7079_en_05 PHOENIX CONTACT 13
Bit 3 to bit 0:
Example of a parameterization
Sensor Pt1000 DIN
14 IN process data words
14.1 Input word IN1 (status word)
The input word IN1 serves as status word.
EB: Error bit
The following error bits set the error bit during configuration:
An invalid parameter word was sent.
Remedy: Check the parameters (see "Parameters for
configuration" on page 12)
Parameterization via process data was disabled during
parameterization via PCP
Remedy: Permit parameterization via process data
("System bit" element, "Conf" bit = 1, see "Config Table
object" on page 19)
Mirroring of the command code:
A command code mirrored from the control word. Here, the
MSB is suppressed.
Code Sensor type Code Sensor type
dec bin dec bin
0 0000 Pt DIN 8 1000 Ni500 (Viessmann)
1 0001 Pt SAMA 9 1001 KTY 81-110
2 0010 Ni DIN 10 1010 KTY 84
3 0011 Ni SAMA 11 1011 KTY 81-210
4 0100 Cu10 12 1100 Reserved
5 0101 Cu50 13 1101 Potentiometer [%]
6 0110 Cu53 14 1110 Linear R: 0 to 400 Ω
7 0111 Ni1000 (Landis & Gyr) 15 1111 Linear R: 0 to 20000 Ω
OUT2
Bit 1514131211109876543210
Assignment 0
Filter 2/3 R
0
Resolution Format Sensor type
Assignment 0
1 1 1 1 1 0 0 0 0 0 0 0 0 0 0
IN1
Bit 1514131211109876543210
Assignment
EB Mirrored command code 00000000
EB = 0 No error has occurred.
EB = 1 An error has occurred.
IB IL TEMP 4/8 RTD ...
7079_en_05 PHOENIX CONTACT 14
14.2 Input words IN2 to IN5
The measured values, the configuration or the firmware ver-
sion are transmitted to the controller board or the PC using
the process data input words IN2 through IN5 in accordance
with the configuration.
For the control word 3C00
hex
, IN2 supplies the firmware
version and the module ID.
Example: firmware version 1.23
Basically three formats are available for the representation
of the measured values. For more detailed information
about the formats, please refer to "Formats for representing
measured values" on page 15.
Open-circuit detection:
An open circuit is detected according to the following table:
IN2
Bit 1514131211109876543210
Assignment
(hex)
123E
hex
Meaning Firmware version 1.23 Module ID
MSB LSB
1514131211109876543210
SB Analog value
IB IL format,
S7-compatible format
1514131211109876543210
SB Analog value 0 OC OR IB ST format
MSB Most significant bit
LSB Least significant bit
SB Sign bit
AV Analog value
0Reserved
OC Open circuit/short circuit
OR Overrange
Faulty sensor
cable
2-wire 3-wire
I+/U+ Yes Yes
I- Yes Yes
U- No
Yes Open circuit is detected.
The cable is not connected when using this
connection method.
No Open circuit is not detected.
IB IL TEMP 4/8 RTD ...
7079_en_05 PHOENIX CONTACT 15
15 Formats for representing measured values
15.1 IB IL format (default setting)
The measured value is represented in bits 14 to 0. An addi-
tional bit (bit 15) is available as a sign bit. This format sup-
ports extended diagnostics. Values > 8000hex and
< 8100hex indicate an error.
The following diagnostic codes are possible:
Measured value representation in IB IL format, 15 bits
Typical analog values depending on the resolution
Code
(hex)
Error
8001 Measuring range exceeded (overrange)
8002 Open circuit
8004 Measured value invalid/no valid measured value
available (e.g., because channel was not config-
ured)
8010 Configuration invalid
8020 I/O supply voltage faulty
8040 Terminal faulty
8080 Below measuring range (underrange)
MSB LSB
1514131211109876543210
SB Analog value
SB Sign bit
Sensor type All temperature sensors Potentiometer Linear
0 to 400 Ω
Linear
0 to 20 kΩ
Sensor/code 0 to 11 13 14 15
Resolution (bits 7 and 6) 00
bin
/10
bin
00
bin
00
bin
00
bin
Process data item (= analog value) 0.1°C/0.1°F
[°C]/[°F]
1%
[%]
0.1 Ω
[Ω]
1 Ω
[Ω]
hex dec
8002 Open circuit
8001 Overrange
(see table on page 22)
See note below
>400.0 >20000
2710 10000 1000.0 10000 (100 x R
0
)–10000
0FA0 4000 400.0 4000 (40 x R
0
) 400.0 4000
000A 10 1.0 10 (0.10 x R
0
)1.0 10
0001 1 0.1 1 (0.01 x R
0
)0.1 1
0000 0 0 0 0 0
FFFF -1 -0.1
FC18 -1000 -100.0
8080 Underrange
(cf. Table page 22)
––