IB IL TEMP 4/8 RTD ...
7079_en_05 PHOENIX CONTACT 16
This sensor type (potentiometer) does not have defined upper limits of the measuring range. Depending on the
gain, however, an open circuit is detected at approximately 400 Ω or at approximately 20000 Ω.
Please note for the potentiometer (No. 13) and linear resistor (No. 14 and 15) sensor types that below 0.8% of the
nominal range (e.g., 0 Ω to 3 Ω for the "linear R: 0 to 400 Ω" type) the diagnostic messages "Overrange" and "Un-
derrange" can be generated.
Sensor type All temperature sensors Potentiometer Linear
0 to 400 Ω
Linear
0 to 20 kΩ
Sensor/code 0 to 11 13 14 15
Resolution (bits 7 and 6) 01
bin
/11
bin
01
bin
01
bin
01
bin
Process data item (= analog value) 0.01°C/0.01°F
[°C]/[°F]
0.1%
[%]
0.01 Ω
[Ω]
0.1 Ω
[Ω]
hex dec
8002 Open circuit
8001 > 325.12
Overrange
(see page 22)
3251.2
325.12 3251.2
2710 10000 100.00 1000.0 (10 x R0)
100.00 1000.0
0FA0 4000 40.00 400.0 (4 x R
0
) 40.00 400.0
000A 10 0.1 1 (0.01 x R
0
)0.1 1
0001 1 0.01 0.1 (0.001 x R
0
) 0.01 0.1
0000 0 0 0 0 0
FFFF -1 -0.01
FC18 (-1000) -10 -10
D8F0 -10000 -100.00
8080 Underrange
(see page 22)
––
If the measured value is outside the representation area of the process data, the "Overrange" or "Underrange" er-
ror message is displayed.
Please note for the potentiometer (No. 13) and linear resistor (No. 14 and 15) sensor types that below 0.8% of the
nominal range (e.g., 0 Ω to 3 Ω for the "linear R: 0 to 400 Ω" type) the diagnostic messages "Overrange" and "Un-
derrange" can be generated.
IB IL TEMP 4/8 RTD ...
7079_en_05 PHOENIX CONTACT 17
15.2 IB ST format
The measured value is represented in bits 14 through 3. The
remaining 4 bits are available as sign and error bits.
Measured value representation in IB ST format; 12 bits
Typical analog values depending on the resolution
MSB LSB
1514131211109876543210
SB Analog value 0 OC OR
SB Sign bit
0Reserved
OC Open circuit/short circuit
OR Overrange
Sensor type RTD sensor
Sensor code (0 to 11)
Resolution (bits 7 and 6) 00
bin
/10
bin
01
bin
/11
bin
Process data item (= analog value) 0.1°C/0.1°F
[°C]/[°F]
0.01°C/0.01°F
[°C]/[°F]
hex dec
xxxx xxxx xxxx xxx1
bin
Overrange
(AV = positive final value from the table on page 22)
2710 10000 1000.0 100.00
03E8 1000 100.0 10.00
0008 8 0.8 0.08
0000 0 0 0
FFF8 -8 -0.8 -0.08
FC18 -1000 -100.0 -10.00
xxxx xxxx xxxx xxx1
bin
Underrange
(AV = negative final value from the table on page 22)
xxxx xxxx xxxx xx1x
bin
Open circuit/short circuit
(AV = negative final value from the table on page 22)
AV Analog value
x Can have the value 0 or 1
If the measured value is outside the representa-
tion area of the process data, bit 0 is set to 1.
In the event of an open/short circuit, bit 1 is set
to 1.
IB IL TEMP 4/8 RTD ...
7079_en_05 PHOENIX CONTACT 18
15.3 S7-compatible format
The measured value is represented in bits 14 to 0. An addi-
tional bit (bit 15) is available as a sign bit.
Measured value representation in S7-compatible format; 15 bits
16 PCP communication
By default upon delivery, the terminal is configured accord-
ing to the default settings on page 10. The terminal can be
configured using process data or PCP to suit your applica-
tion.
In PCP mode, the terminal is configured with the "Config Ta-
ble" object.
16.1 Object dictionary
MSB LSB
1514131211109876543210
SB Analog value
SB Sign bit
AV Analog value
IB input data word
(Two's complement)
(hex)
All temperature sensors
Resolution 0.1°C or 0.1°F
(°C) or (°F)
All temperature sensors
Resolution 0.01°C or 0.01°F
(°C) or (°F)
7FFF Overrange Overrange
2710 (10000) 1000.0 100.0
03E8 (1000) 100.0 10.00
0008 (8) 0.8 0.08
0000 0 0
FFF8 (-8) -0.8 -0.08
FC18 (-1000) -100.0 -10
8000 Underrange Underrange
For information on PCP communication, please
refer to the IBS SYS PCP G4 UM E and
IBS PCP COMPACT UM E user manuals.
The IBS CMD (for standard controller boards)
and IBS PC WORX (for Field Controllers (FC) and
Remote Field Controllers (RFC)) programs are
available for the configuration and parameteriza-
tion of your INTERBUS system.
For additional information, please refer to the
"IBS CMD SWT G4 UM E" user manual and the
documentation for the version of PC WORX
used.
Index Data type A L Meaning Object name Rights
0080
hex
Array of Unsigned 16 12 2 Config table rd/wr
0081
hex
Array of Unsigned 16 8 2 Analog Values rd
A: Number of elements rd: Read access permitted
L: Length of an element in bytes wr: Write access permitted

2878612

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Controllers IB IL TEMP 4/8 RTD- 2MBD-PAC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet