IB IL TEMP 4/8 RTD ...
7079_en_05 PHOENIX CONTACT 4
3 Technical data
General data
Housing dimensions (width x height x depth) 48.8 mm x 136.8 mm x 71.5 mm (with connectors)
Weight 125 g (without connectors), 190 g (with connectors)
Operating mode Process data mode with 5 words/1 word PCP
Connection method for sensors 2 and 3-wire technology
Ambient temperature (operation) -25°C ... +55°C
Ambient temperature (storage/transport) -25°C ... +85°C
Permissible humidity (operation/storage/transport) 10% ... 95%, according to DIN EN 61131-2
Permissible air pressure (operation/storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Class of protection Class III, EN 61131-2, IEC 61131-2
Connection data for Inline connectors
Connection method Spring-cage terminal blocks
Conductor cross section 0.08 mm
2
... 1.5 mm
2
(solid or stranded), 28 - 16 AWG
Interface
Inline local bus Inline data routing
Transmission speed
IB IL TEMP 4/8 RTD,
IB IL TEMP 4/8 RTD-PAC,
IB IL TEMP 4/8 RTD-PAC/CN
500 kbps
IB IL TEMP 4/8 RTD-2MBD,
IB IL TEMP 4/8 RTD-2MBD-PAC
2 Mbps
Power consumption 500 kbps 2 Mbps
Communications power U
L
7.5 V 7.5 V
Current consumption from U
L
75 mA (typical) 100 mA (typical)
I/O supply voltage U
ANA
24 V DC 24 V DC
Current consumption at U
ANA
28 mA (typical) 41 mA (typical)
Total power consumption 1.24 W (typical) 1.75 W (typical)
Supply of the module electronics and I/O through bus coupler/power terminal
Connection method Potential routing
Analog inputs
Number 8 analog RTD inputs
Description of the input Input for resistive temperature sensors
Connection method Spring-cage connection
Connection method 2, 3-wire (shielded)
Linear resistance range 0 Ω ... 400 Ω, 0 Ω ... 20 kΩ
Sensor types that can be used Pt, Ni, KTY, Cu, linear resistors
Standards for characteristic curves According to DIN EN 60751: 07/1996/
according to SAMA RC 21-4-1966
Measuring principle Successive approximation
Measured value representation 16 bits (15 bits + sign bit)
Conversion time of the A/D converter 5 µs, typical; 10 µs, maximum
Process data update 6 ms (up to 230 ms possible depending on the connection method)
Data formats IB IL, IB ST, S7-compatible
Accuracy 0.06% (typical), 0.25% (maximum)
Accuracy ±0.5°C (typical)