QUINT-PS/ 1AC/24DC/ 5
103127_en_04 PHOENIX CONTACT 5
Standards
Electrical Equipment for Machinery EN 60204
Safety transformers for power supply units IEC 61558-2-17
Electrical safety (of information technology equipment) IEC 60950/VDE 0805 (SELV)
Electronic equipment for use in electrical power installations EN 50178/VDE 0160 (PELV)
SELV IEC 60950 (SELV) and EN 60204 (PELV)
Safe isolation DIN VDE 0100-410
DIN VDE 0106-1010
Protection against electric shock DIN 57100-410
Protection against electric shock, basic requirements for safe isolation in
electrical equipment
DIN VDE 0106-101
Limitation of mains harmonic currents EN 61000-3-2
Device safety GS (tested safety)
Network variants (undervoltage) Semi F47-0706
Certificate CB Scheme
Approvals
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950
UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D
Conformance with EMC guideline 2004/108/EC and for low-voltage guideline 2006/95/EC
Noise immunity according to EN 61000-6-2
Electrostatic discharge EN 61000-4-2
Housing Level 4
Contact discharge 8 kV
Discharge in air 15 kV
Comments Criterion B
Electromagnetic HF field EN 61000-4-3
Housing Level 4
Frequency range 80 MHz ... 1000 MHz (20 V/m)
1 GHz ... 3 GHz (10 V/m)
Field intensity
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 4 kV (level 4 - asymmetrical)
Output 2 kV (level 1 - asymmetrical)
Signal 1 kV (level 1 - asymmetrical)
Comments Criterion B
Surge current loads (surge) EN 61000-4-5
Input 4 kV (inst. class 4 - asymmetrical: conductor to ground)
2 kV (inst. class 4 -symmetrical: conductor to conductor)
Output 2 kV (level 3 - asymmetrical: conductor to ground)
1 kV (level 1 - symmetrical: conductor to conductor)
Signal 1 kV (level 3 - asymmetrical: conductor to ground)
Comments Criterion B