QUINT-PS/ 1AC/24DC/ 5
103127_en_04 PHOENIX CONTACT 7
5Structure
LN
PE
Input AC 100-240V
Output DC 24V 5 A
13
14
-
-
-
+++
D
C
O
K
Ι
<
Ι
N
DC OK
Boost
18-29,5V
QUINT POWER
1
9
6
7
8
2
3
4
5
1 AC input
2 DC output
3 POWER BOOST switching output, active
4 DC OK switching output active
5 DC OK output, floating
6 Potentiometer 18 V DC ... 29.5 V DC
7 "DC OK" LED
8 "BOOST" LED
9 Universal DIN rail adapter UTA 107/30
[mm
2
] AWG [Nm]
solid stranded Torque
Input 0.2 - 2.5 0.2 - 2.5 20 - 12 0.5 - 0.6
Output 0.2 - 2.5 0.2 - 2.5 20 - 12 0.5 - 0.6
Signal 0.2 - 2.5 0.2 - 2.5 20 - 12 0.5 - 0.6
Input data
Input nominal voltage range 100 V AC ... 240 V AC
AC input voltage range 85 V AC ... 264 V AC
Short-term input voltage 300 V AC
DC input voltage range 90 V DC ... 350 V DC
AC frequency range 45 Hz ... 65 Hz
DC frequency range 0 Hz
Input fuse, integrated 5 A (slow-blow, internal)
Recommended backup fuse for mains protection 6 A (characteristic B)
10 A (characteristic B)
16 A (characteristic B)
Type of connection Pluggable screw connection
Stripping length 7 mm
Output data
Nominal output voltage 24 V DC ±1%
Setting range of the output voltage 18 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current 5 A (-25°C ... 70°C, U
OUT
= 24 V DC)
7.5 A (with POWER BOOST, -25°C ... 40°C permanently, U
OUT
= 24 V DC)
30 A (with SFB technology, 12 ms)
Type of connection Pluggable screw connection
Stripping length 7 mm
QUINT-PS/ 1AC/24DC/ 5
103127_en_04 PHOENIX CONTACT 8
6Block diagram
13
I<I
N
DC OK
14
L (+)
N (-)
PE
active
PFC
7Safety and warning notes
DANGER OF EXPLOSION!
Only remove equipment when it is disconnected and not in the potentially explosive area.
DANGER
The device contains dangerous live elements and high levels of stored energy.
Never carry out work when the power is turned on.
WARNING
Before startup please ensure:
The mains connection has been carried out by a competent person and protection against electric shock is
guaranteed!
The device can be disconnected outside the power supply unit in accordance with the regulations as in EN
60950 (e.g. through primary side line protection)!
The ground conductor is connected!
All feed lines are sufficiently protected and dimensioned!
All output lines are dimensioned according to the maximum output current of the device or separately
protected!
Sufficient convection is guaranteed!
CAUTION
The power supply units are built-in devices. The device may only be installed and put into operation by qualified
personnel. The corresponding national regulations must be observed.
QUINT-PS/ 1AC/24DC/ 5
103127_en_04 PHOENIX CONTACT 9
8 Installation
LN
PE
Input AC 100-240V
Output DC 24V 5 A
13
14
-
-
-
+++
D
C
O
K
Ι
<
Ι
N
DC OK
Boost
18-29,5V
QUINT POWER
ATTENTION
In order to ensure sufficient convection, we
recommend a minimum vertical distance of 5
cm to the other modules.
A lateral distance of 5 mm, and in the case of
active components, that of 15 mm is necessary
for proper functioning of the module.
Depending on the ambient temperature and
the load of the module, the housing can
become very hot!
The power supply unit can be snapped onto all
DIN rails in acc. with EN 60715. They must be
mounted horizontally (connecting terminal
blocks top and bottom).
9 Installation position
QUINT POWER
LNPE
Input AC 100-240 V
Output DC 24V 5 A
13 14
---
+++
DC
OK
Ι
<
ΙN
DC OK
Boost
18-29,5V
40 55 122
130
50
115
230
Slim-style installation: Installation depth 125 mm (+ DIN rail)
(state at delivery)
Low-profile installation: Installation depth 43 mm (+ DIN rail)