QUINT-PS/24DC/24DC/10/CO
105538_en_01 PHOENIX CONTACT 4
4 Technical data
Input data
Nominal input voltage 24 V DC
Input voltage range 18 V DC ... 32 V DC
Extended input voltage range in operation 14 V DC ... 18 V DC (Derating)
Current consumption 14 A (24 V, I
BOOST
)
Inrush current limitation < 15 A (typical)
I
2
t < 2.7 A
2
s
Power failure bypass > 12 ms (24 V DC)
Protective circuit Transient surge protection Varistor
Protection against polarity reversal Yes , 30 V DC
Input fuse, integrated 25 A (internal (device protection))
Output data
Nominal output voltage 24 V DC ±1%
Setting range of the output voltage 18 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current 10 A (-25 °C ... 60 °C)
12.5 A (with POWER BOOST, -25°C ... 40°C permanently, U
OUT
= 24 V DC)
60 A (SFB technology, 12 ms)
Magnetic fuse tripping B2 / B4 / B6 / C2 / C4
Current limitation Approx. 18 A
Max. capacitive load Unlimited
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Efficiency > 92 %
Ascent time < 2 ms (U
OUT
(10 % ... 90 %))
Residual ripple < 20 mV
PP
Peak switching voltages < 10 mV
PP
(20 MHz)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series Yes
Protection against surge voltage on the output < 35 V DC
Resistance to reverse feed 35 V DC
Power consumption
Maximum power dissipation NO-Load 1.6 W
Power loss nominal load max. 24 W
Status and diagnostic indicator DC OK active
Active switching output U
OUT
> 0.9 x U
N
: High signal
Voltage 18 V DC ... 24 V DC
Current < 20 mA (short-circuit resistant)
Status display "DC OK" LED green
Status and diagnostic indicator POWER BOOST, active
Active switching output I
OUT
< I
N
: High signal
Voltage 18 V DC ... 24 V DC
Current < 20 mA (short-circuit resistant)
Status display "BOOST" LED yellow/I
OUT
> I
N
:LED on
QUINT-PS/24DC/24DC/10/CO
105538_en_01 PHOENIX CONTACT 5
Status and diagnostic indicator U
IN
OK, active
Active switching output U
IN
> 19.2 V: High signal
Voltage 18 V DC ... 24 V DC
Current 20 mA (short-circuit resistant)
Status display LED "U
IN
< 19.2 V" yellow/U
IN
< 19.2 V DC: LED on
Status and diagnostic indicator DC OK floating
Active switching output Relay
Voltage 30 V AC/DC
Current 100 mA
Status display U
OUT
> 0.9 x U
N
: Contact closed
General data
Insulation voltage input/output 1.5 kV (type test)
1 kV (routine test)
MTBF > 763000 h (According to EN 29500)
Normal mounting position horizontal DIN rail NS 35, EN 60715
Dimensions W/H/D (normal mounting position/delivered condition) 48 mm / 130 mm / 125 mm
Dimensions W / H / D (X-axis rotated 270°) 122 mm / 130 mm / 51 mm
Weight 0.9 kg
Housing
Degree of protection IP20
Type of housing Aluminum (AlMg3)
Hood version Galvanized sheet steel, free from chrome (VI)
Input connection data
Connection method Pluggable screw connection
Conductor cross section, solid 0.2 mm² ... 2.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil 24 ... 12
Stripping length 8 mm
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm
Connection data, output/signals
Connection method Pluggable screw connection
Conductor cross section, solid 0.2 mm² ... 2.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil 24 ... 12
Stripping length 7 mm
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm
QUINT-PS/24DC/24DC/10/CO
105538_en_01 PHOENIX CONTACT 6
Ambient conditions
Protection class III
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C derating)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 100 % (at 25 °C, non-condensing)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Shock 30 g in each direction, according to IEC 60068-2-27
Pollution degree in acc. with EN 50178 2
Climatic class 3K3 (in acc. with EN 60721)
Standards
Electrical Equipment for Machinery EN 60204
Electrical safety (of information technology equipment - Safety - Part 1) EN 60950-1/VDE 0805 (SELV)
Electronic equipment for use in electrical power installations EN 50178/VDE 0160 (PELV)
SELV EN 60950-1 (SELV)
EN 60204 (PELV)
Safe isolation / protection against electric shock DIN VDE 0100-410
Approvals
ATEX II 3 G Ex nA nC IIC T4 Gc
IECEx Ex nA nC IIC T4 Gc
UL approvals UL applied for

2320555

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
DIN Rail Power Supplies QUINT-PS/24DC 24DC/10/CO
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet