QUINT-PS/24DC/24DC/10/CO
105538_en_01 PHOENIX CONTACT 7
Conformance with EMC Directive 2004/108/EC
Noise immunity according to EN 61000-6-2
EN 61000-6-2 requirement Tested
Electrostatic discharge EN 61000-4-2
Housing contact discharge 4 kV (Test intensity 2) 8 kV (Test intensity 4)
Housing air discharge 8 kV (Test intensity 3) 15 kV (Test intensity 4)
Comments Criterion B Criterion A
Electromagnetic HF field EN 61000-4-3
Frequency range 80 MHz ... 1 GHz 80 MHz ... 1 GHz
Test field strength 10 V/m 10 V/m
Frequency range 1.4 GHz ... 2 GHz 1 GHz ... 2 GHz
Test field strength 3 V/m 10 V/m
Frequency range 2 GHz ... 2.7 GHz 2 GHz ... 3 GHz
Test field strength 1 V/m 10 V/m
Comments Criterion A Criterion A
Fast transients (burst) EN 61000-4-4
Input 2 kV (Test intensity 3 - asymmetrical) 2 kV (Test intensity 3 - asymmetrical)
Output 2 kV (Test intensity 3 - asymmetrical) 2 kV (Test intensity 3 - asymmetrical)
Signal 1 kV (Test intensity 3 - asymmetrical) 2 kV (Test intensity 4 - asymmetrical)
Comments Criterion B Criterion A
Surge current loads (surge) EN 61000-4-5
Input 0.5 kV (Test intensity 1 - symmetrical)
0.5 kV (Test intensity 1 - asymmetrical)
1 kV (Test intensity 2 - symmetrical)
2 kV (Test intensity 3 - asymmetrical)
Output 0.5 kV (Test intensity 1 - symmetrical)
0.5 kV (Test intensity 1 - asymmetrical)
1 kV (Test intensity 2 - symmetrical)
2 kV (Test intensity 3 - asymmetrical)
Signal 1 kV (Test intensity 2 - asymmetrical) 1 kV (Test intensity 2 - asymmetrical)
Comments Criterion B Criterion A
Conducted interference EN 61000-4-6
Input/Output/Signal asymmetrical asymmetrical
Frequency range 0.15 MHz ... 80 MHz 0.15 MHz ... 80 MHz
Voltage 10 V (Test intensity 3) 10 V (Test intensity 3)
Comments Criterion A Criterion A
Emitted interference in acc. with EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
All technical specifications are nominal and refer to a room temperature of 25°C and 70% relative humidity at
100m above sea level.
Current approvals/permissions for the product can be found in the download area under phoenixcontact.net/
products.
QUINT-PS/24DC/24DC/10/CO
105538_en_01 PHOENIX CONTACT 8
5 Safety regulations and installation
notes
Before startup please ensure:
Only qualified specialist personnel may
install, start up, and operate the device.
Observe the national safety and accident
prevention regulations.
NOTE: Danger if used improperly
The device is a built-in device.
The IP20 degree of protection
(IEC60529/EN60529) of the device is in-
tended for use in a clean and dry environ-
ment. Do not subject the device to any
load that exceeds the described limits.
Do not subject the device to mechanical
and/or thermal loads that exceed the
specified limits.
Installation and startup may only be car-
ried out by qualified personnel. The rele-
vant country-specific regulations must be
observed.
It is not permissible to open or modify the
device. Do not repair the device yourself
but replace it with an equivalent device.
Repairs may only be carried out by the
manufacturer. The manufacturer is not li-
able for damage resulting from violation.
CAUTION:
Before startup please ensure:
Connection must be performed by spe-
cialist personnel and protection against
electric shock ensured.
It must be possible to switch off the de-
vice outside the power supply according
to the regulations in EN 60950-1 (e.g., by
line protection on the primary side).
All feed lines are sufficiently protected
and dimensioned!
All output lines are dimensioned accord-
ing to the maximum output current of the
device or separately protected!
Sufficient convection is guaranteed!
EXPLOSION HAZARD!
Only remove equipment when it is discon-
nected and not in the potentially explosive ar-
ea.
DANGER
Never carry out work on live parts!
The housing can become very hot, depending
on the ambient temperature and load!
QUINT-PS/24DC/24DC/10/CO
105538_en_01 PHOENIX CONTACT 9
6 Basic circuit diagram
Figure 1 Basic circuit diagram
7 Structure
Figure 2 Function elements
1 DC input
2 DC output
3 Potentiometer 18 ... 29.5VDC
4 LED "U
IN
< 19.2 V", yellow
5 "DC OK" LED, green
6 LED "BOOST", yellow
7 U
IN
> 19.2 V, active switching output
8 I < I
IN
, active switching output
9 DC OK, active switching output
10 DC OK relay contact 13/14
11 SFB switch (left: SFB activated, right: SFB deactivated)
12 Strain relief for connecting cables
13 DIN rail adapter
8 Installation
Figure 3 Convection
DC OK
U >19,2 V
IN
I<I
N
13
14
+
+
+
-
-
-
-
13
14
_
_
_
O
K
D
C
I
<
I
N
19.2V
U
IN>
Output DC 24V 10A
Boost
DC OK
18-29.5V
U <19.2 V
IN
Input DC 24V
QUINT POWER
13
14
1
9
.2
V
>
I
N
U
7
8
9
5
6
3
4
1
2
13
10
12
ON OFF
11
SFB
!
To enable sufficient convection, we rec-
ommend a minimum vertical spacing of
50mm from other devices. Lateral spac-
ing of 5mm, or 15mm for active compo-
nents, must be observed in order to
ensure correct device function of the DC/
DC converter.
The housing can become very hot de-
pending on the ambient temperature and
load of the DC/DC converter.
The DC/DC converter can be snapped onto
all DIN rails according to EN60715 and
should be mounted in the normal mounting
position (connection terminal blocks on top
and bottom).
13
14
_
_
_
OK
DC
I
<
I
N
19.2V
U
I
N
>
Output DC 24V 10A
Boost
DC OK
18-
29
.5V
U <19
.2 V
IN
Input DC 24V
QUINT POWER
13
14
19
.2V
>
I
N
U
!

2320555