10
FN8111.0
March 28, 2005
Read Operation
Prior to issuing the Slave Address Byte with the R/W
bit
set to one, the master must first perform a “dummy” write
operation. The master issues the start condition and the
Slave Address Byte, receives an acknowledge, then
issues the Word Address Bytes. After acknowledging
receipts of the Word Address Bytes, the master immedi-
ately issues another start condition and the Slave
Address Byte with the R/W
bit set to one. This is followed
by an acknowledge from the device and then by the eight
bit word. The master terminates the read operation by
not responding with an acknowledge and then issuing a
stop condition. See Figure 12 for the address, acknowl-
edge, and data transfer sequence.
Figure 9. Read Sequence
Stops and Write Modes
Stop conditions that terminate write operations must
be sent by the master after sending at least 1 full data
byte plus the subsequent ACK signal. If a stop is
issued in the middle of a data byte, or before 1 full
data byte plus its associated ACK is sent, then the
device will reset itself without performing the write. The
contents of the array will not be effected.
Acknowledge Polling
The disabling of the inputs during high voltage cycles
can be used to take advantage of the typical 5ms write
cycle time. Once the stop condition is issued to indi-
cate the end of the master’s byte load operation, the
device initiates the internal high voltage cycle.
Acknowledge polling can be initiated immediately. To
do this, the master issues a start condition followed by
the Slave Address Byte for a write or read operation. If
the device is still busy with the high voltage cycle then
no ACK will be returned. If the device has completed
the write operation, an ACK will be returned and the
host can then proceed with the read or write operation.
See Figure 12.
Serial Read Operations
Read operations are initiated in the same manner as
write operations with the exception that the R/W
bit of
the Slave Address Byte is set to one. There are three
basic read operations: Current Address Reads, Ran-
dom Reads, and Sequential Reads.
Current Address Read
Internally the device contains an address counter that
maintains the address of the last word read incre-
mented by one. Therefore, if the last read was to
address n, the next read operation would access data
from address n+1. On power up, the address of the
address counter is undefined, requiring a read or write
operation for initialization.
Upon receipt of the Slave Address Byte with the R/W
bit set to one, the device issues an acknowledge and
then transmits the eight bits of the Data Byte. The
master terminates the read operation when it does not
respond with an acknowledge during the ninth clock
and then issues a stop condition. See Figure 13 for the
address, acknowledge, and data transfer sequence.
0
Slave
Address
Byte
Address
A
C
K
A
C
K
S
t
a
r
t
S
t
o
p
Slave
Address
Data
A
C
K
1
S
t
a
r
t
SDA Bus
Signals from
the Slave
Signals from
the Master
101
0
01
11111111
X40010, X40011, X40014, X40015
11
FN8111.0
March 28, 2005
Figure 10. Acknowledge Polling Sequence
It should be noted that the ninth clock cycle of the read
operation is not a “don’t care.” To terminate a read
operation, the master must either issue a stop condi-
tion during the ninth cycle or hold SDA HIGH during
the ninth clock cycle and then issue a stop condition.
Random Read
Random read operation allows the master to access any
memory location in the array. Prior to issuing the Slave
Address Byte with the R/W
bit set to one, the master
must first perform a “dummy” write operation. The master
issues the start condition and the Slave Address Byte,
receives an acknowledge, then issues the Word Address
Bytes. After acknowledging receipts of the Word Address
Bytes, the master immediately issues another start con-
dition and the Slave Address Byte with the R/W
bit set to
one. This is followed by an acknowledge from the device
and then by the eight bit word. The master terminates the
read operation by not responding with an acknowledge
and then issuing a stop condition. See Figure 14 for the
address, acknowledge, and data transfer sequence.
A similar operation called “Set Current Address” where
the device will perform this operation if a stop is issued
instead of the second start shown in Figure 13. The
device will go into standby mode after the stop and all
bus activity will be ignored until a start is detected.
This operation loads the new address into the address
counter. The next Current Address Read operation will
read from the newly loaded address. This operation
could be useful if the master knows the next address it
needs to read, but is not ready for the data.
Sequential Read
Sequential reads can be initiated as either a current
address read or random address read. The first Data
Byte is transmitted as with the other modes; however,
the master now responds with an acknowledge, indicat-
ing it requires additional data. The device continues to
output data for each acknowledge received. The master
terminates the read operation by not responding with an
acknowledge and then issuing a stop condition.
The data output is sequential, with the data from
address n followed by the data from address n + 1. The
address counter for read operations increments through
all page and column addresses, allowing the entire
memory contents to be serially read during one opera-
tion. At the end of the address space the counter “rolls
over” to address 0000
H
and the device continues to out-
put data for each acknowledge received. See Figure 15
for the acknowledge and data transfer sequence.
ACK
Returned?
Issue Slave Address
Byte (Read or Write)
Byte Load Completed
by Issuing STOP.
Enter ACK Polling
Issue STOP
Issue START
NO
YES
High Voltage Cycle
Complete. Continue
Command Sequence?
Issue STOP
NO
Continue Normal
Read or Write
Command Sequence
PROCEED
YES
X40010, X40011, X40014, X40015
12
FN8111.0
March 28, 2005
SERIAL DEVICE ADDRESSING
Memory Address Map
CR, Control Register, CR7: CR0
Address: 1FF
hex
FDR, Fault DetectionRegister, FDR7: FDR0
Address: 0FF
hex
Slave Address Byte
Following a start condition, the master must output a
Slave Address Byte. This byte consists of several parts:
a device type identifier that is always ‘101x’. Where
x=0 is for Array, x=1 is for Control Register or Fault
Detection Register.
next two bits are ‘0’.
next bit that becomes the MSB of the address.
One bit of the slave command byte is a R/W
bit. The
R/W
bit of the Slave Address Byte defines the oper-
ation to be performed. When the R/W
bit is a one,
then a read operation is selected. A zero selects a
write operation.
Figure 11. X40010/11/14/15 Addressing
Figure 12. Current Address Read Sequence
Figure 13. Random Address Read Sequence
Control Register
Fault Detection Register
1011
Word Address
Slave Byte
1
0
1011
0
0
0
0
R/W
R/W
Control Register
Fault Detection Register
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
S
t
a
r
t
S
t
o
p
Slave
Address
Data
SDA Bus
Signals from
the Slave
Signals from
the Master
1
1010 00
0
Slave
Address
Byte
Address
A
C
K
A
C
K
S
t
a
r
t
S
t
o
p
Slave
Address
Data
A
C
K
1
S
t
a
r
t
SDA Bus
Signals from
the Slave
Signals from
the Master
101 00
X40010, X40011, X40014, X40015

X40015S8I-A

Mfr. #:
Manufacturer:
Renesas / Intersil
Description:
IC VOLTAGE MONITOR DUAL 8-SOIC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union