11.4 Acknowledge error message
To reset the error, it must be acknowledged.
The following options are available:
–Auto (default)
–Manual
This confirmation mode can be configured in the WBM only.
Auto (default)
The error is acknowledged “automatically” with the next
valid write access to the output process data.
(Net Fail in register 7996 is deleted and the NET LED
changes to green).
Manual
In “manual” mode the error must be acknowledged via reg-
ister 2006 or the web-based management.
12 Substitute value behavior
If Ethernet communication fails, all device outputs are set to
the previous parameterized substitute values.
Set the desired substitute value behavior
To set the desired substitute value behavior, the following
options are available:
Web-based management
Modbus register 2002
For further information, please refer to the “Fault response
mode” section.
13 Modbus protocols and registers
The device supports a Modbus/TCP server.
As such, the Modbus protocol can be used in a connection-
related (TCP) manner.
13.1 Modbus connections
The device supports up to eight Modbus/TCP connections
at the same time.
The connection can access different addresses simultane-
ously.
Since eight connections are supported, a connection can
quickly be restored. This means that the client can success-
fully restore an interrupted Modbus connection.
13.2 Modbus conformity classes
The device supports Modbus conformity classes
0 and 1 as well as parts of class 2.
13.3 Modbus function codes
The following function codes are supported:
Function
code
Function Description
FC1 Read coils Read output and input bits
FC2 Read input dis-
cretes
Read multiple input bits
FC3 Read holding
registers
Read words from outputs
and inputs
FC4 Read input reg-
isters
Read words from inputs
FC5 Write coil Write an output bit
FC6 Write single reg-
isters
Write word for output data
FC15 Write multiple
coils
Write multiple output bits
FC16 Write multiple
registers
Write several output words
FC23 Read/write mul-
tiple registers
Read and write several pro-
cess data for inputs and out-
puts
AXL E ETH DIO16 M12 6M
8547_en_03 PHOENIX CONTACT 17
13.4 Modbus register
Modbus register table
(16-bit word)
Access Function Access with function code
Special register
1280 R/W Modbus timeout monitoring FC3, FC4, FC6, FC16, FC23
2000 R/W Timeout for process data watchdog FC3, FC4, FC6, FC16, FC23
2002 R/W Substitute value behavior (fault response mode) FC3, FC4, FC6, FC16, FC23
2004 R Net Fail reason FC3, FC4, FC23
2006 W Command register FC6, FC16, FC23
Diagnostics
7996 R Status register FC3, FC4, FC23
7997 R Diagnostic status register FC3, FC4, FC23
7998 R Diagnostic parameter register FC3, FC4, FC23
Process data
8000 R Input process data FC1, FC2, FC3, FC4, FC23
9000 R/W Output process data FC1, FC2, FC3, FC4, FC5, FC6,
FC15, FC16, FC23
RRead
WWrite
In write access to the Modbus/TCP clients on the “Read only” register, the data is not transferred and is an-
swered with exception code 02.
AXL E ETH DIO16 M12 6M
8547_en_03 PHOENIX CONTACT 18
13.5 Modbus timeout monitoring (1280)
Modbus monitoring means setting or reading the timeout
value for the Modbus connection monitoring.
A timeout value of 0 ms deactivates monitoring.
Enter the time in milliseconds in the range from 200ms to
65000ms, converted to hexadecimal.
13.6 Timeout OUT process data monitoring (pro-
cess data watchdog) (2000)
Timeout OUT process data monitoring means setting or
reading the timeout value for the process data watchdog.
Enter the time in milliseconds in the range from 200ms to
65000ms, converted to hexadecimal.
A timeout value of 0 ms deactivates the watchdog.
13.7 Fault response mode (2002)
The required fault response mode can be set via web-based
management or by writing to Modbus register 2002.
13.8 Net Fail reason (2002)
The reasons for a Fault Response and a set Net Fail signal
can be accessed via web-based management or via the
Modbus register2004.
13.9 Command register (2006)
Only set one bit for the command register, otherwise an error
message is output. Only write access is enabled for the reg-
ister.
Connection monitoring with the new timeout
values is only activated after a Modbus/TCP
function has been executed on the relevant
TCP connection.
Code
(bin)
Code
(hex)
Meaning
00 0000 All outputs are set to “0”.
01 0001 All outputs are set to “1”.
10 0002 All outputs keep their last value.
Code (hex) Meaning
0001 ... 0006 Reserved
0007 DTI timeout occurred
0008 Host timeout occurred
0009 Set by user.
000A Connection aborted
000B Initialization error
000C Process data watchdog triggered
000D Modbus timeout occurred
Bit Code
(hex)
Meaning
0 0001 Reserved
1 0002 Reserved
2 0004 Reserved
3 0008 Reserved
40010Set Net Fail
50020Acknowledge Net Fail
6 0040 Reserved
7 0080 Delete a detected I/O warning/malfunction
8 0100 Reserved
9 0200 Reserved
10 0400 Reserved
11 0800 Reserved
12 1000 Reserved
13 2000 Reserved
14 4000 Reserved
15 8000 Reserved