AXL E ETH DIO16 M12 6M
8547_en_03 PHOENIX CONTACT 4
Dimensions (nominal sizes in mm)
Width 60 mm
Height 185 mm
Depth 38 mm
Note on dimensions The height is 194.5 mm including the mounting plate. With fixing clips pulled out,
the height is 212 mm. The depth is 38 mm including the mounting plate (30.5 mm
without the mounting plate).
4 Technical data
194,5
185
38
60
General data
Housing material Zinc die-cast
Weight 750 g
Ambient temperature (operation) -25 °C ... 60 °C
CAUTION: Risk of burns
If the device is used at an ambient temperature above50°C, the contact temperature of metal surfaces may exceed70°C.
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 %
Permissible humidity (storage/transport) 5 % ... 95 %
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP65/IP67
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Connection data
Connection method M12 connector
Interface Ethernet
Number 2
Connection method M12 connectors, D-coded
Designation connection point Copper cable
Number of positions 4
Transmission speed 10/100 MBit/s (with auto negotiation)
Cycle Time min. 1 ms
AXL E ETH DIO16 M12 6M
8547_en_03 PHOENIX CONTACT 5
Modbus/TCP
Equipment type Modbus slave (server)
Modbus protocols Modbus/TCP
Additional protocols SNMP v1, HTTP, TFTP, FTP, BootP, DHCP
Specification Modbus application protocol V1.1b
Supply: Module electronics, sensors and actuators (U
S
)
Connection method M12 connector (T-coded)
Number of positions 4
Supply voltage 24 V DC
Nominal supply voltage range 18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Typical current consumption 190 mA ±15 % (at 24 V DC)
Current consumption max. 12 A
Supply: Actuators (U
A
) for additional devices
Connection method M12 connector (T-coded)
Number of positions 4
Supply voltage 24 V DC
Nominal supply voltage range 18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Typical current consumption 3 mA ±15 % (at 24 V DC)
Current consumption max. 12 A
Digital inputs
Number of inputs 16 (EN 61131-2 types 1 and 3)
Connection method M12 connector, double occupancy
Connection method 2, 3, 4-wire
Nominal input voltage 24 V DC
Nominal input current typ. 3 mA
Sensor current per channel typ. 0.75 mA (from Us)
Total sensor current max. 1.2 A (per device)
Input voltage range "0" signal -30 V DC ... 5 V DC
Input voltage range "1" signal 11 V DC ... 30 V DC
Input filter time < 1000 µs
Permissible conductor length to the sensor 30 m
Overload protection, short-circuit protection of sensor supply Yes
Digital outputs
Number of outputs 16
Connection method M12 connector, double occupancy
Connection method 2, 3-wire
Nominal output voltage 24 V DC (from voltage U
S
)
Output voltage range 18 V DC ... 31.2 V DC
Maximum output current per channel 0.5 A
Nominal load, ohmic 12 W (48 ; with nominal voltage)
Nominal load, inductive 12 VA (1.2 H; 48 ; with nominal voltage)
Signal delay max. 150 µs (when switched on)
max. 200 µs (when switched off)
Switching frequency max. 5500 per second (with at least 50mA load current)
Switching frequency max. 1 per second (with inductive load)
AXL E ETH DIO16 M12 6M
8547_en_03 PHOENIX CONTACT 6
Limitation of the voltage induced on circuit interruption -28 V ... -17 V
Output voltage when switched off max. 1 V
Output current when switched off max. 20 µA
Behavior with overload Auto restart
Reverse voltage resistance to short pulses Reverse voltage proof
Overcurrent shut-down min. 0.7 A
Overload protection, short-circuit protection of outputs Electronic
Electrical isolation/isolation of the voltage areas
Test section Te s t vo l t a g e
24 V supply (communications power/sensor supply, digital inputs/outputs)/
bus connection (Ethernet1)
500 V AC, 50 Hz, 1 min
24 V supply (communications power/sensor supply, digital inputs/outputs)/
bus connection (Ethernet2)
500 V AC, 50 Hz, 1 min
24 V supply (communications power/sensor supply, digital inputs/outputs)/
FE
500 V AC, 50 Hz, 1 min
Bus connection (Ethernet1)/FE 500 V AC, 50 Hz, 1 min
Bus connection (Ethernet2)/FE 500 V AC, 50 Hz, 1 min
Bus connection (Ethernet1)/bus connection (Ethernet2) 500 V AC, 50 Hz, 1 min
24 V supply (actuator supply)/24 V supply (communications power and
sensor supply, digital inputs/outputs)
500 V AC, 50 Hz, 1 min
24 V supply (actuator supply)/bus connection (Ethernet1) 500 V AC, 50 Hz, 1 min
24 V supply (actuator supply)/bus connection (Ethernet2) 500 V AC, 50 Hz, 1 min
24 V supply (actuator supply)/FE 500 V AC, 50 Hz, 1 min
Mechanical tests
Vibration resistance in acc. with EN60068-2-6/IEC60068-2-6 5g
Shock in acc. with EN60068-2-27/IEC60068-2-27 30g, 11 ms period, half-sine shock pulse
Continuous shock according to EN60068-2-27/IEC60068-2-27 10g
Conformance with EMC Directive 2004/108/EC
Noise immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD) EN61000-4-2/IEC61000-4-2 Criterion B; 6 kV contact discharge, 8 kV air discharge
Electromagnetic fields EN61000-4-3/IEC61000-4-3 Criterion A; Field intensity: 10 V/m
Fast transients (burst) EN61000-4-4/IEC61000-4-4 Criterion B, 2kV
Transient surge voltage (surge) EN61000-4-5/IEC61000-4-5 Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
Conducted interference EN61000-4-6/IEC61000-4-6 Criterion A; Test voltage 10 V
Noise emission test as per EN 61000-6-4
Radio interference properties EN 55022 Class A
Approvals
For the latest approvals, please visit phoenixcontact.net/products.
Digital outputs

2701539

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
AXL E ETH DIO16 M12 6M
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet