LTC4267-1
19
42671fa
For more information www.linear.com/4267-1
applicaTions inForMaTion
can be disabled by floating the R
CLASS
pin. The R
CLASS
pin should not be shorted to V
PORTN
as this would force
the LTC4267-1 classification circuit to attempt to source
very large currents and quickly go into thermal shutdown.
Power Good Interface
The PWRGD signal is controlled by a high voltage, open-
drain transistor. The designer has the option of using this
signal to enable the onboard switching regulator through
the I
TH
/RUN or the P
VCC
pins. Examples of active-high
interface circuits for controlling the switching regulator
are shown in Figure 7.
In some applications, it is desirable to ignore intermittent
power bad conditions. This can be accomplished by includ-
ing capacitor C15 in Figure 7 to form a lowpass filter. With
the components shown, power bad conditions less than
about 200µs will be ignored. Conversely, in other applica-
tions it may be desirable to delay assertion of PWRGD to
the switching regulator using C
PVCC
as shown in Figure 7.
It is recommended that the designer use the power good
signal to enable the switching regulator. Using PWRGD
ensures the capacitor C1 has reached within 1.5V of the
final value and is ready to accept a load.
The LTC4267-1
is
designed with wide power good hysteresis to handle
sudden fluctuations in the load voltage and current without
prematurely shutting off the switching regulator. Please
refer to the Power-Up Sequencing of the Application
Information section.
Signature Disable Interface
To disable the 25k signature resistor, connect SIGDISA pin
to the V
PORTP
pin. Alternately, SIGDISA pin can be driven
high with respect to V
PORTN
. An example of a signature
disable interface is shown in Figure 16, option 2. Note that
the SIGDISA input resistance is relatively large and the
threshold voltage is fairly low. Because of high voltages
present on the printed circuit board, leakage currents from
the V
PORTP
pin could inadvertently pull SIGDISA high. To
ensure trouble-free operation, use high voltage layout
techniques in the vicinity of SIGDISA. If unused, connect
SIGDISA to V
PORTN
.
Load Capacitor
The IEEE 802.3af specification requires that the PD main-
tain a minimum load capacitance ofF (provided by C1
in Figure 11). It is permissible to have a much larger load
capacitor and the LTC4267-1 can charge very large load
capacitors before thermal issues become a problem. The
load capacitor must be large enough to provide sufficient
energy for proper operation of
the switching
regulator.
However, the capacitor must not be too large or the PD
design may violate IEEE 802.3af requirements.
If the load capacitor is too large, there can be a problem
with inadvertent power shutdown by the PSE. Consider
the following scenario. If the PSE is running at 57V
(maximum allowed) and the PD has detected and powered
up, the load capacitor will be charged to nearly 57V. If
for some reason the PSE voltage is suddenly reduced to
44V (minimum allowed), the input bridge will reverse bias
and the PD power will be supplied by the load capacitor.
Depending on the size of the load capacitor and the DC load
of the PD, the PD will not draw any power for a period of
time. If this period of time exceeds the IEEE 802.3af 300ms
disconnect delay, the PSE will remove power from the PD.
For this reason, it is necessary to ensure that inadvertent
shutdown cannot occur.
Very small output capacitors (≤10µF) will charge very
quickly in current limit. The rapidly changing voltage at
the output may reduce the current limit temporarily, caus-
ing the capacitor to charge at a somewhat reduced rate.
Conversely
, charging a very large capacitor may cause the
current limit to increase slightly. In either case, once the
output voltage reaches its final value, the input current
limit will be restored to its nominal value.
The load capacitor can store significant energy when fully
charged. The design of a PD must ensure that this energy
is not inadvertently dissipated in the LTC4267-1. The
polarity-protection diode(s) prevent an accidental short on
the cable from causing damage. However, if the V
PORTN
pin is shorted to V
PORTP
inside the PD while the capacitor
is charged, current will flow through the parasitic body
diode of the internal MOSFET and may cause permanent
damage to the LTC4267-1.
LTC4267-1
20
42671fa
For more information www.linear.com/4267-1
applicaTions inForMaTion
Maintain Power Signature
In an IEEE 802.3af system, the PSE uses the maintain
power signature (MPS) to determine if a PD continues to
require power. The MPS requires the PD to periodically
draw at least 10mA and also have an AC impedance less
than 26.25 in parallel with 0.05µF. If either the DC
current is less than 10mA or the AC impedance is above
26.25kΩ, the PSE may disconnect power. The DC current
must be less than 5mA and the AC impedance must be
above 2MΩ to guarantee power will be removed.
Selecting Feedback Resistor Values
The regulated output voltage of the switching regulator is
determined by the resistor divider across V
OUT
(R1 and
R2 in Figure 11) and the error amplifier reference voltage
V
REF
. The ratio of R2 to R1 needed to produce the desired
voltage can be calculated as:
R2 = R1 • (V
OUT
– V
REF
)/V
REF
In an isolated power supply application, V
REF
is determined
by the designer’s choice of an external error amplifier.
Commercially available error amplifiers or programmable
shunt regulators may include an internal reference of
1.25V or 2.5V. Since the LTC4267-1 internal reference
and error amplifier are not used
in an isolated design, tie
the V
FB
pin to PGND.
In a nonisolated power supply application, the LTC4267-1
onboard internal reference and error amplifier can be
used. The resistor divider output can be tied directly to
the V
FB
pin. The internal reference of the LTC4267-1 is
0.8V nominal.
Choose resistance values for R1 and R2 to be as large as
possible to minimize any efficiency loss due to the static
current drawn from V
OUT
, but just small enough so that
when V
OUT
is in regulation, the error caused by the nonzero
input current from the output of the resistor divider to the
error amplifier pin is less than 1%.
Error Amplifier and Opto-Isolator Considerations
In an isolated topology, the selection of the external error
amplifier depends on the output voltage of the switching
regulator. Typical error amplifiers include a voltage refer-
ence of either 1.25V or 2.5V. The output of the amplifier
and the amplifier upper supply rail are often tied together
internally. The supply rail is usually specified with a wide
upper voltage range, but it is not allowed to fall below the
reference voltage. This can be a problem in an isolated
switcher design if
the amplifier supply voltage is not prop-
erly
managed. When the switcher load current decreases
and the output voltage rises, the error amplifier responds
by pulling more current through the LED. The LED voltage
can be as large as 1.5V, and along with R
LIM
, reduces the
supply voltage to the error amplifier. If the error amp does
not have enough headroom, the voltage drop across the
LED and R
LIM
may shut the amplifier off momentarily,
causing a lock-up condition in the main loop. The switcher
will undershoot and not recover until the error amplifier
releases its sink current. Care must be taken to select the
reference voltage and R
LIM
value so that the error amplifier
always has enough headroom. An alternate solution that
avoids these problems is to utilize the LT1431 or LT4430
where the output of the error amplifier and amplifier supply
rail are brought out to separate pins.
The PD designer must also select an opto-isolator such
that its bandwidth is sufficiently wider than the bandwidth
of the main control loop. If this step is overlooked, the
main control loop may be difficult to stabilize. The output
collector resistor of the opto-isolator
can be selected for
an increase in bandwidth at the cost of a reduction in gain
of this stage.
Output Transformer Design Considerations
Since the external feedback resistor divider sets the
output voltage, the PD designer has relative freedom in
selecting the transformer turns ratio. The PD designer
can use simple ratios of small integers (i.e. 1:1, 2:1, 3:2)
which yields more freedom in setting the total turns and
mutual inductance and may allow the use of an off the
shelf transformer.
Transformer leakage inductance on either the primary or
secondary causes a voltage spike to occur after the output
switch (Q1 in Figure 11) turns off. The input supply volt-
age plus the secondary-to-primary referred voltage of the
LTC4267-1
21
42671fa
For more information www.linear.com/4267-1
applicaTions inForMaTion
flyback pulse (including leakage spike) must not exceed
the allowed external MOSFET breakdown rating. This spike
is increasingly prominent at higher load currents, where
more stored energy must be dissipated. In some cases,
asnubber” circuit will be required to avoid overvoltage
breakdown at the MOSFET’s drain node. Application
Note 19 is a good reference for snubber design.
Current Sense Resistor Consideration
The external current sense resistor (R
SENSE
in Figure 11)
allows the designer to optimize the current limit behavior
for a particular application. As the current sense resistor
is varied from several ohms down to tens of milliohms,
peak swing current goes from a fraction of an ampere to
several amperes. Care must be taken to ensure proper
circuit operation, especially for small current sense resis-
tor values.
Choose R
SENSE
such that the switching current exercises
the entire range of the I
TH
/RUN voltage. The nominal voltage
range is 0.7V to 1.9V and R
SENSE
can be determined by
experiment. The main loop can be temporarily stabilized by
connecting a large capacitor on the power supply. Apply
the maximum load current allowable at the power sup-
ply output based on the class of the PD. Choose
R
SENSE
such that I
TH
/RUN approaches 1.9V. Finally, exercise the
output load current over the entire operating range and
ensure that I
TH
/RUN voltage remains within the 0.7V to
1.9V range. Layout is critical around the R
SENSE
resistor.
For example, a 0.020Ω sense resistor, with one milliohm
(0.001Ω) of parasitic resistance will cause a 5% reduction
in peak switch current. The resistance of printed circuit
copper traces cannot necessarily be ignored and good
layout techniques are mandatory.
Programmable Slope Compensation
The LTC4267-1 switching regulator injects a ramping
current through its SENSE pin into an external slope
compensation resistor (R
SL
in Figure 11). This current
ramp starts at zero after the NGATE pin has been high for
the LTC4267-1’s minimum duty cycle of 6%. The current
rises linearly towards a peak ofA at the maximum duty
cycle of 80%, shutting off once the NGATE pin goes low.
A series resistor (R
SL
) connecting the SENSE pin to the
current sense resistor (R
SENSE
) develops a ramping volt-
age drop. From the perspective of the LTC4267-1 SENSE
pin, this ramping voltage adds to the voltage across the
sense resistor, effectively reducing the current comparator
threshold in proportion to duty cycle. This
stabilizes the
control
loop against subharmonic oscillation. The amount
of reduction in the current comparator thresholdV
SENSE
)
can be calculated using the following equation:
V
SENSE
= 5µAR
SL
• [(Duty Cycle – 6%)/74%]
Note: The LTC4267-1 enforces 6% < Duty Cycle < 80%.
Designs not needing slope compensation may replace R
SL
with a short-circuit.
Applications Employing a Third Transformer Winding
A standard operating topology may employ a third wind-
ing on the transformer’s primary side that provides power
to the LTC4267-1 switching regulator via its P
VCC
pin
(Figure 11). However, this arrangement is not inherently
self-starting. Start-up is usually implemented by the use of
an externaltrickle-charge” resistor (R
START
) in conjunc-
tion with the internal wide hysteresis undervoltage lockout
circuit that monitors the P
VCC
pin voltage.
R
START
is connected to V
PORTP
and supplies a current,
typically 100µA, to charge C
PVCC
. After some time, the
voltage on C
PVCC
reaches the P
VCC
turn-on threshold. The
LTC4267-1 switching regulator then turns on abruptly and
draws its normal supply current. The NGATE pin begins
switching and the external MOSFET (Q1) begins to deliver
power. The voltage on C
PVCC
begins to decline as the
switching regulator draws its normal supply current,
which
exceeds the delivery from R
START
. After some time, typically
tens of milliseconds, the output voltage approaches the
desired value. By this time, the third transformer winding
is providing virtually all the supply current required by the
LTC4267-1 switching regulator.
One potential design pitfall is under-sizing the value of
capacitor C
PVCC
. In this case, the normal supply current
drawn through P
VCC
will discharge C
PVCC
rapidly before the
third winding drive becomes effective. Depending on the
particular situation, this may result in either several off-on
cycles before proper operation is reached or permanent
relaxation oscillation at the P
VCC
node.

LTC4267CGN-1#TRPBF

Mfr. #:
Manufacturer:
Analog Devices Inc.
Description:
Power Switch ICs - POE / LAN IEEE802.3af PD w/Switching Reg.
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union