MAX6884/MAX6885
Configuration Lock
Lock the configuration register bank and configuration
EEPROM contents after initial programming by setting
the lock bit high (see Table 10). Locking the configura-
tion prevents write operations to configuration EEPROM
and configuration registers except the configuration
lock bit. Set the lock bit to 0 to reconfigure the device.
Write Disable
A unique write disable feature protects the
MAX6884/MAX6885 from inadvertent user EEPROM
writes. As input voltages that power the serial interface,
a µP, or any other writing devices fall, unintentional
data may be written onto the data bus. The user
EEPROM write-disable function (see Table 11) ensures
that unintentional data does not corrupt the MAX6884/
MAX6885 user EEPROM data.
EEPROM-Programmable, Hex
Power-Supply Supervisory Circuits
22 ______________________________________________________________________________________
REGISTER
ADDRESS
BIT RANGE
DESCRIPTION
[0] 1 = IN1 Voltage Falls Below Primary Undervoltage Threshold
[1] 1 = IN2 Voltage Falls Below Primary Undervoltage Threshold
[2] 1 = IN3 Voltage Falls Below Primary Undervoltage Threshold
[3] 1 = IN4 Voltage Falls Below Primary Undervoltage Threshold
[4] 1 = IN5 Voltage Falls Below Primary Undervoltage Threshold
[5] 1 = IN6 Voltage Falls Below Primary Undervoltage Threshold
28h
[7:6] Unused
[0] 1 = IN1* Voltage Falls Below Secondary Threshold
[1] 1 = IN2* Voltage Falls Below Secondary Threshold
[2] 1 = IN3* Voltage Falls Below Secondary Threshold
[3] 1 = IN4* Voltage Falls Below Secondary Threshold
[4] 1 = IN5* Voltage Falls Below Secondary Threshold
[5] 1 = IN6* Voltage Falls Below Secondary Threshold
29h
[7:6] Unused
[0] 1 = UV/OV Has Been Asserted
[1] 1 = RESET Has Been Asserted
[6:2] Unused
2Ah
[7] 1 = WDO Has Been Asserted
Table 9. Fault Registers (28h–2Ah)
REGISTER
ADDRESS
EEPROM
MEMORY
ADDRESS
BIT RANGE DESCRIPTION
16h 96h [3]
1 = Configuration Locked
0 = Configuration Unlocked
Table 10. Configuration Lock Bit
*Does not matter if set as undervoltage or overvoltage.
Configuration Register Bank
and EEPROM
The configuration registers can be directly modified by
the serial interface without modifying the EEPROM
after the power-up procedure terminates and the con-
figuration EEPROM data has been loaded into the con-
figuration register bank. Use the write byte or block
write protocols to write directly to the configuration reg-
isters. Changes to the configuration registers take
effect immediately and are lost upon power removal.
At device power-up, the register bank loads configura-
tion data from the EEPROM. Configuration data may
be directly altered in the register bank during applica-
tion development, allowing maximum flexibility.
Transfer the new configuration data, byte by byte, to
the configuration EEPROM with the write byte protocol.
The next device power-up or software reboot automati-
cally loads the new configuration. See Table 12 for a
complete register map.
Configuration EEPROM
The configuration EEPROM addresses range from 80h to
97h. Write data to the configuration EEPROM to set up
the MAX6884/MAX6885 automatically upon power-up.
Data transfers from the configuration EEPROM to the
configuration registers when V
CC
exceeds UVLO during
power-up or after a software reboot. After V
CC
exceeds
UVLO, an internal 1MHz clock starts after a 5µs delay,
and data transfer begins. Data transfer disables access
to the configuration registers and EEPROM. The data
transfer from EEPROM to configuration registers takes
2.5ms maximum. Read configuration EEPROM and con-
figuration register data any time after power-up or soft-
ware reboot. Write commands to the configuration
EEPROM and configuration registers are allowed at any
time after power-up or software reboot unless the config-
uration lock bit is set (see Table 10). When the configura-
tion lock bit is set, all write access to EEPROM and
registers is disabled with the exception of the configura-
tion lock bit itself. The maximum cycle time to write a sin-
gle byte in EEPROM is 11ms (max).
User EEPROM
The 512-bit user EEPROM addresses range from 40h to
7Fh (see Figure 11). Store revision data, board revision
data, or other data in these registers. The maximum
cycle time to write a single byte is 11ms (max). Disable
writes to the user EEPROM during RESET or UV/OV
assertion by programming bit R16h[1] or R16h[0],
respectively (see Table 11).
MAX6884/MAX6885
EEPROM-Programmable, Hex
Power-Supply Supervisory Circuits
______________________________________________________________________________________ 23
REGISTER
ADDRESS
EEPROM
MEMORY
ADDRESS
BIT RANGE DESCRIPTION
[1]
1 = User EEPROM Writes Disabled on RESET Assertion
0 = User EEPROM Writes Enabled on RESET Assertion
16h 96h
[0]
1 = User EEPROM Writes Disabled on UV/OV Assertion
0 = User EEPROM Writes Enabled on UV/OV Assertion
Table 11. User EEPROM Write Disable Bits
MAX6884/MAX6885
EEPROM-Programmable, Hex
Power-Supply Supervisory Circuits
24 ______________________________________________________________________________________
Table 12. Register Map
REGISTER
ADDRESS
EEPROM
MEMORY
ADDRESS
READ/
WRITE
DESCRIPTION
00h 80h R/W IN1 Primary Undervoltage Detector Threshold (Table 4)
01h 81h R/W IN2 Primary Undervoltage Detector Threshold (Table 4)
02h 82h R/W IN3 Primary Undervoltage Detector Threshold (Table 4)
03h 83h R/W IN4 Primary Undervoltage Detector Threshold (Table 4)
04h 84h R/W IN5 Primary Undervoltage Detector Threshold (Table 4)
05h 85h R/W IN6 Primary Undervoltage Detector Threshold (Table 4)
06h 86h R/W IN1 Secondary Undervoltage/Overvoltage Detector Threshold (Table 4)
07h 87h R/W IN2 Secondary Undervoltage/Overvoltage Detector Threshold (Table 4)
08h 88h R/W IN3 Secondary Undervoltage/Overvoltage Detector Threshold (Table 4)
09h 89h R/W IN4 Secondary Undervoltage/Overvoltage Detector Threshold (Table 4)
0Ah 8Ah R/W IN5 Secondary Undervoltage/Overvoltage Detector Threshold (Table 4)
0Bh 8Bh R/W IN6 Secondary Undervoltage/Overvoltage Detector Threshold (Table 4)
0Ch 8Ch R Unused. Returns 0h when read.
0Dh 8Dh R Unused. Returns 0h when read.
0Eh 8Eh R/W Secondary Threshold Undervoltage/Overvoltage Selection (Table 4)
0Fh 8Fh R/W Threshold Range Selection (Table 4)
10h 90h R/W High-Z Mode Selection (Table 4)
11h 91h R/W RESET Dependency Selection (Table 6)
12h 92h R/W
RESET Output Type, Timeout Period, and WDO Dependency Selection
(Table 6)
13h 93h R/W UV/OV Dependency Selection (Table 7)
14h 94h R/W UV/OV Output Type and Timeout Period (Table 7)
15h 95h R/W Watchdog Initial and Normal Timeout Selection (Table 8)
16h 96h R/W
Internal/External V
CC
(Table 2), Internal/External Reference (Table 5),
Configuration Lock Bit (Table 10), User EEPROM Write Disable (Table 11)
17h 97h R Unused (Table 5)
18h R ADC Conversion Data for IN1 (8 MSBs) (Table 3)
19h R ADC Conversion Data for IN1 (2 LSBs) (Table 3)
1Ah R ADC Conversion Data for IN2 (8 MSBs) (Table 3)
1Bh R ADC Conversion Data for IN2 (2 LSBs) (Table 3)
1Ch R ADC Conversion Data for IN3 (8 MSBs) (Table 3)
1Dh R ADC Conversion Data for IN3 (2 LSBs) (Table 3)
1Eh R ADC Conversion Data for IN4 (8 MSBs) (Table 3)
1Fh R ADC Conversion Data for IN4 (2 LSBs) (Table 3)
20h R ADC Conversion Data for IN5 (8 MSBs) (Table 3)
21h R ADC Conversion Data for IN5 (2 LSBs) (Table 3)
22h R ADC Conversion Data for IN6 (8 MSBs) (Table 3)
23h R ADC Conversion Data for IN6 (2 LSBs) (Table 3)
24h R ADC Conversion Data for AUXIN (8 MSBs) (Table 3)

MAX6884ETP+T

Mfr. #:
Manufacturer:
Maxim Integrated
Description:
Supervisory Circuits EEPROM-Prog Hex Power-Sup Sequencer
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet