ADE7769
Rev. A | Page 15 of 20
Table 5. F
1–4
Frequency Selection
S1 S0 OSC Relation
1
F
1–4
at Nominal OSC (Hz)
2
0 0 OSC/2
19
0.86
0 1 OSC/2
18
1.72
1 0 OSC/2
17
3.43
1 1 OSC/2
16
6.86
1
F
1–4
is a binary fraction of the internal oscillator frequency.
2
Values are generated using the nominal frequency of 450 kHz.
Example
In this example, with ac voltages of ±30 mV peak applied to
V1 and ±165 mV peak applied to V2, the expected output
frequency is calculated as
F
1–4
= OSC/2
19
Hz, S0 = S1 = 0
V1
rms
= 0.03/√2 V
V2
rms
= 0.165/√2 V
V
REF
= 2.45 V (nominal reference value)
If the on-chip reference is used, actual output frequencies
may vary from device to device due to the reference tolerance
of ±200 mV.
175.0204.0
45.222
165.003.075.494
2
=×=
××
×××
=
1
1
F
F
Freq
(11)
Table 6. Maximum Output Frequency on F1 and F2
S1 S0 OSC Relation Max Frequency
1
or AC Inputs (Hz)
0 0 0.204 × F
1
0.175
0 1 0.204 × F
2
0.35
1 0 0.204 × F
3
0.70
1 1 0.204 × F
4
1.40
1
Values are generated using the nominal frequency of 450 kHz.
Frequency Output CF
The pulse output CF (calibration frequency) is intended for
calibration purposes. The output pulse rate on CF can be up to
2048 times the pulse rate on F1 and F2. The lower the F
1–4
frequency selected, the higher the CF scaling (except for the
high frequency mode SCF = 0, S1 = S0 = 1).
Table 7 shows how
the two frequencies are related, depending on the states of the
logic inputs S0, S1, and SCF. Due to its relatively high pulse
rate, the frequency at the CF logic output is proportional to the
instantaneous real power. As with F1 and F2, CF is derived
from the output of the low-pass filter after multiplication.
However, because the output frequency is high, this real
power information is accumulated over a much shorter time.
Therefore, less averaging is carried out in the digital-to-
frequency conversion. With much less averaging of the real
power signal, the CF output is much more responsive to power
fluctuations (see the signal processing block diagram shown in
Figure 15).
Table 7. Maximum Output Frequency on CF
SCF S1 S0 CF Max for AC Signals (Hz)
1
1 0 0 128 × F1, F2 = 22.4
0 0 0 64 × F1, F2 = 11.2
1 0 1 64 × F1, F2 = 22.4
0 0 1 32 × F1, F2 = 11.2
1 1 0 32 × F1, F2 = 22.4
0 1 0 16 × F1, F2 = 11.2
1 1 1 16 × F1, F2 = 22.4
0 1 1 2048 × F1, F2 = 2.867 kHz
1
Values are generated using the nominal frequency of 450 kHz.
SELECTING A FREQUENCY FOR AN ENERGY
METER APPLICATION
As shown in Table 5, the user can select one of four frequencies.
This frequency selection determines the maximum frequency
on F1 and F2. These outputs are intended for driving an energy
register (electromechanical or other). Because only four
different output frequencies can be selected, the available
frequency selection has been optimized for a meter constant
of 100 imp/kWh with a maximum current of between 10 A
and 120 A.
Table 8 shows the output frequency for several
maximum currents (I
MAX
) with a line voltage of 220 V. In all
cases, the meter constant is 100 imp/kWh.
Table 8. F1 and F2 Frequency at 100 imp/kWh
I
MAX
(A) F1 and F2 (Hz)
12.5 0.076
25.0 0.153
40.0 0.244
60.0 0.367
80.0 0.489
120.0 0.733
The F
1–4
frequencies allow complete coverage of this range of
output frequencies (F1, F2). When designing an energy meter,
the nominal design voltage on Channel V2 (voltage) should be
set to half-scale to allow for calibration of the meter constant.
The current channel should also be no more than half scale
when the meter sees maximum load. This allows overcurrent
signals and signals with high crest factors to be accommodated.
Table 9 shows the output frequency on F1 and F2 when both
analog inputs are half scale. The frequencies in
Table 9 align
very well with those in
Table 8 for maximum load.
Table 9. F1 and F2 Frequency with Half-Scale AC Inputs
S1 S0 F
1–4
(Hz)
Frequency on F1 and F2—
CH1 and CH2 Half-Scale AC Input
1
0 0 0.86
0.051 × F
1
0.044 Hz
0 1 1.72 0.051 × F
2
0.088 Hz
1 0 3.43 0.051 × F
3
0.176 Hz
1 1 6.86 0.051 × F
4
0.352 Hz
1
Values are generated using the nominal frequency of 450 kHz.
ADE7769
Rev. A | Page 16 of 20
When selecting a suitable F
1–4
frequency for a meter design, the
frequency output at I
MAX
(maximum load) with a meter constant
of 100 imp/kWh should be compared with Column 4 of
Table 9.
The closest frequency in
Table 9 determines the best choice of
frequency (F
1–4
). For example, if a meter with a maximum
current of 25 A is being designed, the output frequency on F1
and F2 with a meter constant of 100 imp/kWh is 0.153 Hz at 25
A and 220 V (from
Table 8). In Table 9 the closest frequency to
0.153 Hz in Column 4 is 0.176 Hz. Therefore, as shown in
Tab le
5
, F3 (3.43 Hz) is selected for this design.
Frequency Outputs
Figure 2 shows a timing diagram for the various frequency
outputs. The F1 and F2 outputs are the low frequency
outputs that can be used to directly drive a stepper motor or
electromechanical impulse counter. The F1 and F2 outputs
provide two alternating low frequency pulses. The F1 and F2
pulse widths (t
1
) are set such that if they fall below 240 ms
(0.24 Hz), they are set to half of their period. The maximum
output frequencies for F1 and F2 are shown in
Table 6.
The high frequency CF output is intended to be used for
communications and calibration purposes. CF produces a
90-ms-wide active high pulse (t
4
) at a frequency proportional to
active power. The CF output frequencies are given in
Table 7.
As with F1 and F2, if the period of CF (t
5
) falls below 180 ms,
the CF pulse width is set to half the period. For example, if the
CF frequency is 20 Hz, the CF pulse width is 25 ms.
When high frequency mode is selected (that is, SCF = 0,
S1 = S0 = 1), the CF pulse width is fixed at 35 μs. Therefore,
t
4
is always 35 μs, regardless of output frequency on CF.
NO-LOAD THRESHOLD
The ADE7769 includes a no-load threshold and start-up
current feature, which eliminates any creep effects in the meter.
The ADE7769 is designed to issue a minimum output
frequency. Any load generating a frequency lower than this
minimum frequency does not cause a pulse to be issued on F1
or F2. The minimum output frequency is given as 0.00244% for
each of the F
1–4
frequency selections (see Table 5).
For example, for an energy meter with a meter constant of
100 imp/kWh on F1, F2 using F
3
(3.43 Hz), the minimum
output frequency at F1 or F2 would be 0.00244% of 3.43 Hz or
8.38 × 10
–5
Hz. This would be 2.68 × 10
–3
Hz at CF (32 × F1 Hz)
when SCF = S0 = 1, S1 = 0. In this example, the no-load
threshold would be equivalent to 3 W of load or a start-up
current of 13.72 mA at 220 V. Compare this value to the
IEC62053-21 specification which states that the meter must
start up with a load equal to or less than 0.4% Ib. For a 5 A (Ib)
meter, 0.4% of Ib is equivalent to 20 mA.
The no-load condition is indicated with CF output pulse
remaining logic high, as shown in
Figure 28.
CF
0W
NO-LOAD
THRESHOLD
MAGNITUDE
TIME
ACTIVE POWER
CF FREQUENCY PROPORTIONAL TO POWER
05332-028
Figure 28. No-Load Indication Using ADE7769
NEGATIVE POWER INFORMATION
The ADE7769 detects when the current and voltage channels
have a phase shift greater than 90°. This mechanism can detect
an incorrect meter connection or the generation of negative
power. The REVP pin output goes active high when negative
power is detected and active low if positive power is detected.
The REVP pin output changes state as a pulse is issued on CF.
EVALUATION BOARD AND REFERENCE DESIGN
BOARD
An evaluation board can be used to verify the functionality and
the performance of the ADE7769. Download the documenta-
tion for the board from http://www.analog.com/ADE7769.
In addition, the reference design board ADE7769ARN-REF
and Application Note AN-679 can be used in the design
of a low cost watt-hour meter that surpasses IEC62053-21
accuracy specifications. The application note can be
downloaded from http://www.analog.com/ADE7769.
ADE7769
Rev. A | Page 17 of 20
OUTLINE DIMENSIONS
CONTROLLING DIMENSIONS ARE IN MILLIMETERS; INCH DIMENSIONS
(IN PARENTHESES) ARE ROUNDED-OFF MILLIMETER EQUIVALENTS FOR
REFERENCE ONLY AND ARE NOT APPROPRIATE FOR USE IN DESIGN
COMPLIANT TO JEDEC STANDARDS MS-012-AC
16
9
8
1
4.00 (0.1575)
3.80 (0.1496)
10.00 (0.3937)
9.80 (0.3858)
1.27 (0.0500)
BSC
6.20 (0.2441)
5.80 (0.2283)
SEATING
PLANE
0.25 (0.0098)
0.10 (0.0039)
0.51 (0.0201)
0.31 (0.0122)
1.75 (0.0689)
1.35 (0.0531)
0.50 (0.0197)
0.25 (0.0098)
1.27 (0.0500)
0.40 (0.0157)
0.25 (0.0098)
0.17 (0.0067)
COPLANARITY
0.10
× 45°
Figure 29. 16-Lead Standard Small Outline Package [SOIC_N]
Narrow Body (R-16)
Dimensions shown in millimeters and (inches)
ORDERING GUIDE
Model Temperature Range Package Description Package Option
ADE7769AR −40°C to +85°C 16-Lead Standard Small Outline Package [SOIC_N] R-16
ADE7769AR-RL −40°C to +85°C 16-Lead Standard Small Outline Package [SOIC_N] REEL R-16
ADE7769ARZ
1
−40°C to +85°C 16-Lead Standard Small Outline Package [SOIC_N] R-16
ADE7769ARZ-RL
1
−40°C to +85°C 16-Lead Standard Small Outline Package [SOIC_N] REEL R-16
EVAL-ADE7769EB Evaluation Board
ADE7769AR-REF Reference Design Board
1
Z = Pb-free part.

ADE7769ARZ-RL

Mfr. #:
Manufacturer:
Analog Devices Inc.
Description:
Data Acquisition ADCs/DACs - Specialized Energy Meter IC w/ Intg Oscillator
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet