ADF4116/ADF4117/ADF4118
Rev. D | Page 19 of 28
FUNCTION LATCH
With C2 and C1 set to 1 and 0, respectively, the on-chip
function latch is programmed.
Figure 33 shows the input data
format for programming the function latch.
COUNTER RESET
DB2 (F1) is the counter reset bit. When this bit is set to 1, the R
counter, A counter, and B counter are reset. For normal operation,
this bit should be set to 0. On power-up, the F1 bit needs to be
disabled, for the N counter to resume counting in “close
alignment with the R counter. (The maximum error is one
prescaler cycle.)
POWER-DOWN
DB3 (PD1) and DB19 (PD2) on the ADF411x family provide
programmable power-down modes. They are enabled by the
CE pin.
When the CE pin is low, the device is immediately disabled
regardless of the states of PD2 and PD1.
In programmed asynchronous power-down, the device powers
down immediately after latching a 1 into the PD1 bit, with the
condition that PD2 is loaded with a 0.
In programmed synchronous power-down, the device power-
down is gated by the charge pump to prevent unwanted
frequency jumps. Once power-down is enabled by writing a 1
into the PD1 bit (on condition that a 1 is also loaded to PD2),
the device goes into power-down after the first successive
charge pump event.
When a power-down is activated (either synchronous or
asynchronous mode including CE pin-activated power-down),
the following events occur:
All active dc current paths are removed.
The R counter, N counter, and timeout counter are forced
to their load state conditions.
The charge pump is forced into three-state mode.
The digital clock detect circuitry is reset.
The RF
IN
input is debiased.
The oscillator input buffer circuitry is disabled.
The input register remains active and capable of loading
and latching data.
MUXOUT CONTROL
The on-chip multiplexer is controlled by DB6 (M3), DB5 (M2),
and DB4 (M1) on the ADF411x family.
Figure 33 shows the
truth table.
PHASE DETECTOR POLARITY
DB7 (F2) of the function latch sets the phase detector polarity.
When the VCO characteristics are positive, DB7 should be set
to 1. When they are negative, it should be set to 0.
CHARGE PUMP THREE-STATE
The DB8 (F3) bit puts the charge pump into three-state mode
when programmed to 1. It should be set to 0 for normal operation.
FASTLOCK ENABLE BIT
DB9 (F4) of the function latch is the fastlock enable bit. Fastlock
is enabled only when DB9 is set to 1.
FASTLOCK MODE BIT
DB11 (F6) of the function latch is the fastlock mode bit. When
fastlock is enabled, this bit determines which fastlock mode is
used. If the fastlock mode bit is 0, Fastlock Mode 1 is selected; if
the fastlock mode bit is 1, Fastlock Mode 2 is selected.
If fastlock is not enabled (DB9 = 0), DB11 (ADF4116)
determines the state of the FL
O
output. FL
O
state is the same as
that programmed to DB11.
Fastlock Mode 1
In the ADF411x family, the output level of FL
O
is programmed
to a low state, and the charge pump current is switched to the
high value (1 mA). FL
O
is used to switch a resistor in the loop
filter and to ensure stability while in fastlock by altering the
loop bandwidth.
The device enters fastlock by having a 1 written to the CP Gain
bit in the N register. The device exits fastlock by having a 0
written to the CP Gain bit in the N register.
Fastlock Mode 2
In the ADF411x family, the output level of FL
O
is programmed
to a low state, and the charge pump current is switched to the
high value (1 mA). FL
O
is used to switch a resistor in the loop
filter and to ensure stability while in fastlock by altering the
loop bandwidth.
The device enters fastlock by having a 1 written to the CP gain
bit in the N register. The device exits fastlock under the control
of the timer counter. After the timeout period determined by
the value in TC4 to TC1, the CP Gain bit in the N register is
automatically reset to 0, and the device reverts to normal mode
instead of fastlock.
TIMER COUNTER CONTROL
In the ADF411x family, the user has the option of switching
between two charge pump current values to speed up locking to
a new frequency.
When using the fastlock feature with the ADF411x family, the
following should be noted:
The user must make sure that fastlock is enabled. Set DB9
to 1. The user must also choose which fastlock mode to use.
ADF4116/ADF4117/ADF4118
Rev. D | Page 20 of 28
Fastlock Mode 2 uses the values in the timer counter to
determine the timeout period before reverting to normal
mode operation after fastlock. Fastlock Mode 2 is chosen
by setting DB11 to 1.
The user must also decide how long to keep the high
current (1 mA) active before reverting to low current
(250 μA). This is controlled by the timer counter control
bits, DB14 to DB11 (TC4 to TC1), in the function latch.
The truth table is given in
Figure 33.
To program a new output frequency, program the A counter
and B counter latch with new values for A and B. At the
same time, set the CP Gain bit to a 1, which sets the charge
pump to 1 mA for a period of time determined by TC4 to
TC1. When this time is up, the charge pump current
reverts to 250 μA. At the same time, the CP Gain bit in the
A counter and B counter latch is reset to 0 and is ready for
the next time that the user wants to change the frequency.
INITIALIZATION LATCH
When C2 and C1 are both set to 1, the initialization latch is
programmed. This is essentially the same as the function latch
that is programmed when C2, C1 = 1, 0.
However, when the initialization latch is programmed, an
additional internal reset pulse is applied to the R counter and
N counter. This pulse ensures that the N counter is at a load
point when the N counter data is latched and that the device
begins counting in close phase alignment.
If the latch is programmed for synchronous power-down (CE
pin is high; PD1 bit is high; PD2 bit is low), the internal pulse
also triggers this power-down. The prescaler reference and the
oscillator input buffer are unaffected by the internal reset pulse,
so close phase alignment is maintained when counting resumes.
When the first N counter data is latched after initialization, the
internal reset pulse is again activated. However, successive
N counter loads do not trigger the internal reset pulse.
DEVICE PROGRAMMING AFTER
INITIAL POWER-UP
After initial power-up, the device can be programmed by the
initialization latch method, the CE pin method, or the counter
reset method.
Initialization Latch Method
1. Apply V
DD
.
2. Program the initialization latch (11 in 2 LSBs of input
word). Make sure that F1 bit is programmed to 0.
3. Do an R load (00 in 2 LSBs).
4. Do an N load (01 in 2 LSBs).
When the initialization latch is loaded, the following occurs:
The function latch contents are loaded.
An internal pulse resets the R, N, and timeout counters to
load state conditions and also three-states the charge pump.
Note that the prescaler band gap reference and the oscillator
input buffer are unaffected by the internal reset pulse, allowing
close phase alignment when counting resumes.
Latching the first N counter data after the initialization
word activates the same internal reset pulse. Successive
N loads do not trigger the internal reset pulse unless there
is another initialization.
CE Pin Method
1. Apply V
DD
.
2. Bring CE low to put the device into power-down. This is an
asynchronous power-down in that it happens immediately.
3. Program the function latch (10).
4. Program the R counter latch (00).
5. Program the N counter latch (01).
6. Bring CE high to take the device out of power-down.
The R counter and N counter resume counting in close alignment.
Note that after CE goes high, a duration of 1 μs may be required
for the prescaler band gap voltage and oscillator input buffer
bias to reach a steady state.
CE can be used to power up and power down the device to check
for channel activity. The input register does not need to be repro-
grammed each time the device is disabled and enabled, as long
as it is programmed at least once after V
CC
is initially applied.
Counter Reset Method
1. Apply V
DD
.
2. Do a function latch load (10 in 2 LSBs). As part of this,
load 1 to the F1 bit. This enables the counter reset.
3. Do an R counter load (00 in 2 LSBs).
4. Do an N counter load (01 in 2 LSBs).
5. Do a function latch load (10 in 2 LSBs). As part of this,
load 0 to the F1 bit. This disables the counter reset.
This sequence provides the same close alignment as the initiali-
zation method. It offers direct control over the internal reset.
Note that counter reset holds the counters at load point and
three-states the charge pump, but it does not trigger synchro-
nous power-down. The counter reset method requires an extra
function latch load compared to the initialization latch method.
ADF4116/ADF4117/ADF4118
Rev. D | Page 21 of 28
APPLICATIONS INFORMATION
LOCAL OSCILLATOR FOR THE
GSM BASE STATION TRANSMITTER
Figure 35 shows the ADF4117/ADF4118 being used with a
VCO to produce the LO for a GSM base station transmitter.
The reference input signal is applied to the circuit at F
REFIN
and,
in this case, is terminated in 50 Ω. A typical GSM system has a
13 MHz TCXO driving the reference input without a 50 Ω
termination. To have a channel spacing of 200 kHz (the GSM
standard), the reference input must be divided by 65, using the
on-chip reference divider of the ADF4117/ADF1118.
The charge pump output of the ADF4117/ADF1118 (Pin 2)
drives the loop filter. In calculating the loop filter component
values, a number of items need to be considered. In this example,
the loop filter was designed so that the overall phase margin for
the system is 45°. Other PLL system specifications include:
K
D
= 1 mA
K
V
= 12 MHz/V
Loop bandwidth = 20 kHz
F
REF
= 200 kHz
N = 4500
Extra reference spur attenuation = 10 dB
All of these specifications are needed and are used to produce
the loop filter component values shown in
Figure 36.
The loop filter output drives the VCO, which, in turn, is fed back
to the RF input of the PLL synthesizer; it also drives the RF
output terminal. A T-circuit configuration provides 50 Ω
matching between the VCO output, the RF output, and the
RF
IN
terminal of the synthesizer.
In a PLL system, it is important to know when the system is in
locked mode. In
Figure 35, this is accomplished by using the
MUXOUT signal from the synthesizer. The MUXOUT pin can
be programmed to monitor various internal signals in the
synthesizer. One of these is the LD or lock-detect signal.
SHUTDOWN CIRCUIT
The attached circuit in Figure 36 shows how to shut down both
the ADF411x family and the accompanying VCO. The ADG702
switch goes open-circuit when a Logic 1 is applied to the IN
input. The low cost switch is available in both SOT-23 and
MSOP packages.
DIRECT CONVERSION MODULATOR
In some applications, a direct conversion architecture can be
used in base station transmitters.
Figure 37 shows the
combination available from Analog Devices, Inc. to implement
this solution.
The circuit diagram shows the AD9761 being used with the
AD8346. The use of dual integrated DACs, such as the AD9761
with specified ±0.02 dB and ±0.004 dB gain and offset matching
characteristics, ensures minimum error contribution (over
temperature) from this portion of the signal chain.
The local oscillator is implemented by using the ADF4117/
ADF4118. In this case, the FOX801BH-130 provides the stable
13 MHz reference frequency. The system is designed for
200 kHz channel spacing and an output center frequency of
1960 MHz. The target application is a WCDMA base station
transmitter. Typical phase noise performance from this LO is
−85 dBc/Hz at a 1 kHz offset. The LO port of the AD8346 is
driven in single-ended fashion. LOIN is ac-coupled to ground
with the 100 pF capacitor, and LOIP is driven through the ac-
coupling capacitor from a 50 Ω source. An LO drive level between
−6 dBm and −12 dBm is required. The circuit in
Figure 37 gives a
typical level of −8 dBm.
The RF output is designed to drive a 50 Ω load, but it must be
ac-coupled as shown in
Figure 37. If the I and Q inputs are
driven in quadrature by 2 V p-p signals, the resulting output
power is approximately −10 dBm.

ADF4117BRUZ-RL

Mfr. #:
Manufacturer:
Analog Devices Inc.
Description:
Phase Locked Loops - PLL SGL Integer-N 1.2 GHz
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union