IB IL AI 4/EF ...
7252_en_02 PHOENIX CONTACT 16
14.2 Output Words OUT2 to OUT5 (Configuration)
Each channel can be configured independently of the other channels. The first channel is configured via the second output
word, the second channel via the third output word, etc.
If the configuration changes, the corresponding channel is re-initialized. If the format "IB IL" is set, the error code "Measured
value invalid" is output.
If the configuration is invalid, a corresponding error message is output in the status word. The configuration is stored in a
volatile memory.
For commands 400x
hex
and 500x
hex
, specify the parameters for the appropriate channels 1 to 4 in OUT2 to OUT5. The
parameter words are only evaluated by this command.
14.3 Parameters for Configuration
The values displayed in bold are default settings.
Bit 9 and bit 8
Bit 5 and bit 4
Bit 3 to bit 0
OUTx (x = 2 to 5)
Bit 1514131211109876543210
Assignment 000000
Filter 0 0 Format Measuring range
Code (bin) Filter
00 Mean value via 16 measured values
01 No mean value
10 Mean value via 4 measured values
11 Mean value via 32 measured values
Code (bin) Format
00 IB IL (15 bits)
01 IB ST (12 bits)
10 S7-compatible
11 Standardized representation
Code (bin) Code (hex) Measuring Range
0000 0 0 V to 10 V
0001 1 ±10 V
0010 2 0 V to 5 V
0011 3 ±5 V
1000 8 0 mA to 20 mA
1001 9 ±20 mA
1010 A 4 mA to 20 mA
4 to 7
B to F
Reserved
IB IL AI 4/EF ...
7252_en_02 PHOENIX CONTACT 17
15 IN Process Data Words
15.1 Input Word IN1 (Status Word)
Error bit:
The error bit is available as a group error message. Possible errors and their effects are listed in "Diagnostics" on page 25.
* Mirrored command codes:
A command code mirrored from the control word. Here, the MSB is suppressed.
15.2 Input Words IN2 to IN5
The measured values, firmware version or configuration are transmitted to the controller board or the computer via IN
process data words IN2 to IN5 according to the configuration.
For control words 0000
hex
and 5000
hex
(error-free standard operation) the measured values are transmitted in IN2 to IN5.
For control word 1x00
hex
, the configuration of the selected channel is indicated in IN2. For control word 3C00
hex
, IN2
supplies the firmware version and the device ID.
Example:
For control word 4000
hex
(configuration mode),
the configuration data is mirrored in the input words after transfer.
OUT1
Byte 0 Byte 1
Bit 1514131211109876543210
Assignment
EB Mirrored command code* 0 0 0 0 0 0 0 0
EB = 0 No error has occurred.
EB = 1 An error has occurred.
IN2
Bit 1514131211109876543210
Assignment (hex) 1 2 3 6
Meaning Firmware Version 1.23 Device ID
IB IL AI 4/EF ...
7252_en_02 PHOENIX CONTACT 18
16 Formats for the Representation of Measured Values (IN2 to IN5)
16.1 Format: "IB IL" (Default Setting)
The measured value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit.
This format supports extended diagnostics. Values > 8000
hex
and < 8100
hex
indicate an error. The error codes are listed
on page 22.
Measured value representation in "IB IL" format (15 bits)
Significant Measured Values
Measuring range 0 mA to 20 mA/4 mA to 20 mA/0 V to 5 V/0 V to 10 V
Measuring range -20 mA to +20 mA/-5 V to +5 V/-10 V to +10 V
MSB LSB
1514131211109876543210
SB Analog value
SB Sign bit
Input Data Word
(Two's Complement)
0mA to 20 mA
I
Input
4mA to 20 mA
I
Input
0V to 5V
U
Input
0 V to 10 V
U
Input
hex dec mA mA V V
8001 Overrange > +21.6746 > +21.339733 > +5.419 > +10.837
7F00 32512 +21.6746 +21.339733 +5.419 +10.837
7530 30000 +20.0 +20.0 +5.0 +10.0
0001 1 +0.66667 µA +4.00053333 +166.67 µV +333.33 µV
0000 0 0 +3.2 to +4.0 0 0
8002 Open circuit < +3.2
Input Data Word
(Two's Complement)
-20 mA to +20 mA
I
Input
-5 V to +5 V
U
Input
-10 V to +10 V
U
Input
hex dec mA V V
8001 Overrange > +21.6746 > +5.419 > +10.837
7F00 32512 +21.6746 +5.419 +10.837
7530 30000 +20.0 +5.0 +10.0
0001 1 +0.66667 µA +166.67 µV +333.33 µV
0000 0 0 0 0
FFFF -1 -0.66667 µA -166.67 µV -333.33 µV
8AD0 -30000 -20.0 -5.0 -10.0
8100 -32512 -21.6746 -5.419 -10.837
8080 Underrange < -21.6746 < -5.419 < -10.837