IB IL AI 4/EF ...
7252_en_02 25
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3-4 12 00
www.phoenixcontact.com
18 Diagnostics
The following events are monitored and indicated:
© PHOENIX CONTACT 10/2006
Meaning Possible Values
Consecutive no. Unique, consecutive error number since the last
power up reset or history reset
0 to 65535
Priority Priority of the message If Code = 0000
hex
, Priority = 00
hex
otherwise Priority = 02
hex
Channel If Code = 0000
hex
, Channel = 00
hex
otherwise Channel = 01
hex
to 04
hex
Code Error code 0000
hex
: No error
8910
hex
: Overrange
8920
hex
: Underrange
7710
hex
: Cable break
5160
hex
: Power supply error
5010
hex
: Hardware fault
MoreFollows 00
hex
= No additional information is available for
this error.
00
hex
Text The first 10 characters of the status message.
Default: "Status OK"
If Code = 0000
hex
,
Text = "Status OK"
otherwise text contains error-specific
information
Event Response
Open circuit,
overrange and underrange of the
measuring range
– Error bit set
– Indication of an error code in the measured value
(only for "IB IL" and "standardized representation" format)
– Generation of a peripheral fault, if this was permitted during configuration
Voltage failure of the sensor supply – Error bit set
– Device error
– Indication of an error code in the measured value
(only for "IB IL" and "standardized representation" format)
– Generation of a peripheral fault, if this was permitted during configuration
Voltage failure of the internal analog
device supply (5 V and 15 V)
– Error bit set
– Indication of an error code in the measured value
(only for "IB IL" and "standardized representation" format)
– Generation of a peripheral fault, if this was permitted during configuration
Faulty configuration – Error bit set