IB IL AI 4/EF ...
7252_en_02 PHOENIX CONTACT 7
Error Messages to the Higher-Level Control or Computer System
Failure of the internal I/O voltage supply Yes, I/O error message sent to the bus coupler
Failure of or insufficient communications power U
L
Yes, I/O error message sent to the bus coupler
Peripheral fault/user error Yes, error message via the IN process data (see page 17)
Approvals
For the latest approvals, please visit www.download.phoenixcontact.com.
IB IL AI 4/EF ...
7252_en_02 PHOENIX CONTACT 8
4 Local Diagnostic and Status Indicators and Terminal Point Assignment
Figure 1 IB IL AI 4/EF terminal
with an appropriate connector
4.1 Function Identification
Green
2 Mbps: White stripe in the vicinity of the D LED
4.2 Local Diagnostic and Status Indicators
4.3 Terminal Point Assignment for Each Connector
5 Installation Instructions
High current flowing through potential jumpers U
M
and U
S
leads to a temperature rise in the potential jumpers and inside
the terminal. Observe the following instructions to keep the current flowing through the potential jumpers of the analog
terminals as low as possible:
UiS
D
A
I
4
E
F
UiS
D
AI4EF
12
1
2
3
4
1
2
3
4
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
TR
TR
72520005
Des. Color Meaning
D Green Diagnostics
TR Green PCP communication active
UiS Green/red Sensor supply
Green ON Sensor supply present
Red ON Overload/short circuit of sensor
supply U
iS
or supply voltage U
M
not present
If the UiS LED is red, please also check the
UM LED on the previous power terminal.
UiS red ON/UM ON: Overload/short circuit of
the sensor supply U
iS
;
UiS red ON/UM OFF: Supply voltage U
M
not
present
Terminal
Points
Signal Assignment
1.1 U
iSx
(24 V) Initiator supply for channel x
2.1 GND Ground for UiSx
1.2 Ux+ Positive voltage input for
channel x
2.2 Ux- Minus input for channel x
(voltage)
1.3 Ix+ Positive current input for
channel x
2.3 Ix- Minus input for channel x
(current)
1.4, 2.4 Shield Shield connection
x = 1 to 4
Create a separate main circuit for each analog terminal.
If this is not possible in your application and you are using analog terminals in a main circuit together with other
terminals, place the analog terminals after all the other terminals at the end of the main circuit.
IB IL AI 4/EF ...
7252_en_02 PHOENIX CONTACT 9
6 Internal Circuit Diagram
Figure 2 Internal wiring of the terminal points
Key:
Local Bus
+24V(U )
M
+24V(U )
S
U
L+
U
ANA
U
L-
EEPROM
OPC
µP
GND GND GND GND
U1- U2- U3- U4-
24 V
15 V
+
-
5V
+
-
SUPER-
VISOR
U
is1
U
is2
U
is3
U
is4
ELF
ELF
ELF
ELF
I1- I2- I3- I4-
I1+ I2+ I3+ I4+
U1+
U2+
U3+ U4+
REF
MUX
72520111
Protocol chip Reference voltage
Power supply unit with electrical isolation Analog/digital converter
Optocoupler Amplifier
Microprocessor Multiplexer
Electrically erasable programmable read-
only memory
Electronic fuse
Microprocessor monitoring Resistor
OPC
R E F
x x x
X X X
µ P
M U X
E E P R O M
E L F
S U P E R -
V I S O R
Other symbols used are explained in the
IB IL SYS PRO UM E user manual or in the
Inline system manual for your bus system.