4 Local Diagnostic and Status Indicators and Terminal Point Assignment
Figure 1 IB IL AI 4/EF terminal
with an appropriate connector
4.1 Function Identification
Green
2 Mbps: White stripe in the vicinity of the D LED
4.2 Local Diagnostic and Status Indicators
4.3 Terminal Point Assignment for Each Connector
5 Installation Instructions
High current flowing through potential jumpers U
M
and U
S
leads to a temperature rise in the potential jumpers and inside
the terminal. Observe the following instructions to keep the current flowing through the potential jumpers of the analog
terminals as low as possible:
UiS
D
A
I
4
E
F
UiS
D
AI4EF
12
1
2
3
4
1
2
3
4
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
TR
TR
72520005
Des. Color Meaning
D Green Diagnostics
TR Green PCP communication active
UiS Green/red Sensor supply
Green ON Sensor supply present
Red ON Overload/short circuit of sensor
supply U
iS
or supply voltage U
M
not present
If the UiS LED is red, please also check the
UM LED on the previous power terminal.
UiS red ON/UM ON: Overload/short circuit of
the sensor supply U
iS
;
UiS red ON/UM OFF: Supply voltage U
M
not
present
Terminal
Points
Signal Assignment
1.1 U
iSx
(24 V) Initiator supply for channel x
2.1 GND Ground for UiSx
1.2 Ux+ Positive voltage input for
channel x
2.2 Ux- Minus input for channel x
(voltage)
1.3 Ix+ Positive current input for
channel x
2.3 Ix- Minus input for channel x
(current)
1.4, 2.4 Shield Shield connection
x = 1 to 4
Create a separate main circuit for each analog terminal.
If this is not possible in your application and you are using analog terminals in a main circuit together with other
terminals, place the analog terminals after all the other terminals at the end of the main circuit.