7252_en_02 PHOENIX CONTACT 22
16.5 Supported Error Codes for the "IB IL" and "Standardized Display" Formats
After an error message, the following errors/messages for "IB IL" and "standardized representation" format are displayed
in words IN2 to IN5 in the status word (error bit):
Supported Error Codes in "IB IL" Format
17 PCP Communication
By default upon delivery, the device is configured according to the default settings listed on page 16. The device can be
configured to suit your application using process data or PCP.
In PCP mode, the device is configured with the "Config Table" object.
17.1 Object Dictionary
Input Data Word (hex) Error
8001 Overrange
8002 Open circuit
8004 Measured value invalid
8020 Sensor and/or analog supply not present
8040 Device faulty
8080 Underrange
For information on PCP communication, please refer to the IBS SYS PCP G4 UM E
(Order No. 2745169) and IBS PCP COMPACT UM E (Order No. 9015349) user manuals.
The IBS CMD (for standard controller boards) and PC WorX (for Field Controllers (FC) and Remote Field
Controllers (RFC)) programs are available for the configuration and parameterization of your INTERBUS
system.
For additional information, please refer to the "IBS CMD SWT G4 UM E" (Order No. 2722250) user manual and
the documention for your applied PC WorX version.
Index Data Type N L Meaning Object Name Rights
0080
hex
Array of Unsigned 16 5 2 Config Table rd/wr
0081
hex
Array of Unsigned 16 4 2 Analog Values rd
N: Number of elements rd: Read access permitted
L: Length of an element in bytes wr: Write access permitted
IB IL AI 4/EF ...
7252_en_02 PHOENIX CONTACT 23
17.2 Object Description
Config Table Object
Configure the device using this object.
Object description:
Element Value Range
The "Configuration channel x" elements have the following structure:
For the value ranges for the individual parameters, please refer to "Parameters for Configuration" on page 16.
The "System bits" element has the following structure:
"PF"
If bit 2 = 1, a peripheral fault is generated in the event of a sensor problem (overrange, underrange, open circuit).
"Conf"
If bit 0 = 1, configuration via process data is permitted (command code 400x
hex
or 500x
hex
).
If an invalid configuration is specified, a negative confirmation is generated with error message 08
hex
, 00
hex
or xx30
hex
. The
low byte of the additional error code is 30
hex
(value is out of range), the high byte contains the number of the affected
element.
Example: Config Table is completely written with data (subindex 00) and the entry for channel 2 is invalid. In this case, the
additional error code is equal to 0230
hex
.
Object Config Table
Access Read, write
Data type Array of Unsigned 16 5 x 2 bytes
Index 0080
hex
Subindex 00
hex
01
hex
02
hex
03
hex
04
hex
05
hex
Write all elements
Configuration channel 1
Configuration channel 2
Configuration channel 3
Configuration channel 4
System bits
Length (bytes) 0A
hex
02
hex
Subindex 00
hex
Subindex 01
hex
to 05
hex
Data Device configuration
Bit 1514131211109876543210
Assignment 000000
Filter 0 0 Format Output range
Bit 1514131211109876543210
Assignment 0000000000000PF 0 Conf
IB IL AI 4/EF ...
7252_en_02 PHOENIX CONTACT 24
Analog Values Object
The elements of this object contain the analog values of the channels in the format that was selected for this channel.
Object description:
DiagState Object
The elements of this object contain the current diagnostic status of the device.
Object description:
Object Analog Values
Access Read
Data type Array of Unsigned 16 4 x 2 bytes
Index 0081
hex
Subindex 00
hex
01
hex
02
hex
03
hex
04
hex
Read all elements
Analog value channel 1
Analog value channel 2
Analog value channel 3
Analog value channel 4
Length (bytes) 08
hex
02
hex
Subindex 00
hex
Subindex 01
hex
to 04
hex
Data Analog values of the channels
Object DiagState
Access Read
Data type Record
Index 0018
hex
Subindex 00
hex
Read all elements
01
hex
Consecutive no. Unsigned 16 (2 bytes)
02
hex
Priority Unsigned 8 (1 byte)
03
hex
Channel Unsigned 8 (1 byte)
04
hex
Code Unsigned 16 (2 bytes)
05
hex
MoreFollows Unsigned 8 (1 byte)
06
hex
Text OctetString (10 bytes)
Length (bytes) 11
hex
01
hex
02
hex
0A
hex
Subindex 00
hex
Subindex 02
hex
, 03
hex
, 05
hex
Subindex 01
hex
, 04
hex
Subindex 06
hex
Data Diagnostic status of the device