1Description
IEC 62061
SILCL
Safety relay for emergency stop, safety door and
light grid monitoring
PSR-MC40
© PHOENIX CONTACT
Data sheet
Intended Use
The PSR-MC40 safety relay can be used to monitor two-
channel signal generators, e.g.,emergency stop buttons,
safety door locking mechanisms, and light grids, as well as
to control actuators.
The safety relay is equipped with three enabling current
paths that drop out without delay corresponding to stop cat-
egory0 according to EN60204-1.
The enabling current paths are controlled automatically
once the sensor circuit has been closed.
With the manual, monitored reset device, a machine start
may not be triggered in accordance with ENISO13849-1.
Features
Safety relay for emergency stop, safety door, and light
grid monitoring
Suitable up to category4, PLe (ENISO13849-1),
SILCL3 (EN62061)
1 two-channel sensor circuit
3 undelayed enabling current paths
1 digital signal output
Option of screw or spring-cage terminal blocks for plug-
in
12.5mm housing width
WARNING: Risk of electric shock
Observe the safety instructions in the corresponding section!
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
This document meets the same requirements as the original operating instructions in terms of contents and is
valid for all products listed in the “Ordering data” section.
106175_en_02
2015-08-21
PSR-MC40
106175_en_02 PHOENIX CONTACT 2
2Table of contents
1 Description .............................................................................................................................. 1
2 Table of contents ..................................................................................................................... 2
3 Ordering data .......................................................................................................................... 3
4 Technical data ......................................................................................................................... 3
5 Safety notes............................................................................................................................. 6
6 Basic circuit diagram ............................................................................................................... 7
7 Derating................................................................................................................................... 7
8 Load curve............................................................................................................................... 7
9 Function/time diagrams ........................................................................................................... 8
9.1 Time diagram for automatic start ............................................................................................. 8
9.2 Time diagram for manual, monitored start .................................................................................. 8
10 Operating and indication elements .......................................................................................... 9
10.1 Connection versions............................................................................................................. 9
10.2 Connection assignment......................................................................................................... 9
11 Mounting and connection ...................................................................................................... 10
12 Startup................................................................................................................................... 10
13 Calculating the power dissipation .......................................................................................... 11
14 Diagnostics............................................................................................................................ 12
14.1 General states .................................................................................................................. 12
14.2 Error Messages................................................................................................................. 12
15 Application examples ............................................................................................................ 14
15.1 Emergency stop monitoring/automatic start.............................................................................. 14
15.2 Emergency stop monitoring/manual, monitored start .................................................................. 14
15.3 Safety door monitoring/automatic start .................................................................................... 15
15.4 Safety door monitoring/manual, monitored start......................................................................... 15
15.5 Single-channel safety door monitoring/automatic start ................................................................ 16
15.6 Single-channel safety door monitoring/manual, monitored start ..................................................... 16
15.7 Connection to failsafe controller/automatic start ........................................................................ 17
15.8 Connection to failsafe controller/manual, monitored start ............................................................. 17
15.9 Single-channel connection to failsafe controller/automatic start ..................................................... 18
15.10 Single-channel connection to failsafe controller/manual, monitored start.......................................... 18
15.11 Light grid monitoring/automatic start....................................................................................... 19
15.12 Light grid monitoring/manual, monitored start ........................................................................... 19
15.13 Transponder monitoring/automatic start .................................................................................. 20
15.14 Transponder monitoring/manual, monitored start....................................................................... 20
16 Revision history .................................................................................................................... 21
PSR-MC40
106175_en_02 PHOENIX CONTACT 3
Description Type Order No. Pcs. / Pkt.
Safety relay for emergency stop, safety doors, and light grids up to SIL3,
SILCL3, Cat.4, PLe, 2-channel operation, automatic or manual, moni-
tored start, 3 enabling current paths, U
S
=24VDC, plug-in screw terminal
block
PSR-MC40-3NO-1DO-24DC-SC 2700569 1
Safety relay for emergency stop, safety doors, and light grids up to SIL3,
SILCL3, Cat.4, PLe, 2-channel operation, automatic or manual, moni-
tored start, 3 enabling current paths, U
S
=24VDC, plug-in spring-cage
terminal block
PSR-MC40-3NO-1DO-24DC-SP 2700570 1
3Ordering data
4 Technical data
Hardware/firmware version
HW/FW 00/-- (The technical data and safety characteristics are valid as of the specified
HW/FW version.)
Input data
Rated control supply voltage U
S
24 V DC -15 % / +10 %
Rated control supply current I
S
typ. 80 mA
Input voltage range "0"-signal 0 V DC ... 5 V DC (for safe off)
Typical inrush current 5 A (t=200s at U
s
)
< 20 mA (with U
s
/I
x
to S12)
< 200 mA (with U
s
/I
x
to S34)
< 5 mA (with U
s
/I
x
to S22)
Current consumption < 5 mA (with U
s
/I
x
to S12)
< 5 mA (with U
s
/I
x
to S22)
> -5 mA (with U
s
/I
x
to S34)
< 10 mA (with U
s
/I
x
to S34)
Power consumption at U
S
typ. 1.92 W
Voltage at input/start and feedback circuit 24 V DC -15 % / +10 %
Filter time 1 ms (at A1 in the event of voltage dips at U
s
)
max. 1.5 ms (at S12, S22; test pulse width)
min. 7.5 ms (at S12, S22; test pulse rate)
Test pulse rate=5xTest pulse width
Max. permissible overall conductor resistance
(Input and reset circuit at U
S
)
150
Typical response time at U
s
< 175 ms (automatic start)
< 175 ms (manual, monitored start)
Typical starting time with U
s
< 250 ms (when controlled via A1)
Typical release time with U
s
< 20 ms (when controlled via A1 or S12 and S22.)
Recovery time < 500 ms
Maximum switching frequency 0.5 Hz
Operating voltage display 1 x green LED
Status display 3 x green LED
Protective circuit Surge protection Suppressor diode
Reverse polarity protection for rated control supply voltage
Output data
Contact type 3 enabling current paths
Contact material AgSnO
2
Minimum switching voltage 20 V AC/DC
Maximum switching voltage 250 V AC/DC
Limiting continuous current 6 A (N/O contact)

MIC2775-46YM5-TR

Mfr. #:
Manufacturer:
Microchip Technology / Micrel
Description:
Supervisory Circuits Single Voltage Supervisor with Dual Active-High and Low Push-Pull Outputs, Manua
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet