PSR-MC40
106175_en_02 PHOENIX CONTACT 4
Maximum inrush current 6 A
Inrush current, minimum 3 mA
Sq. Total current 48 A
2
(see to derating)
Switching capacity min. 60 mW
Mechanical service life 10 x 10
6
cycles
Output fuse 6 A gL/gG (N/O contact)
4 A gL/gG (for low-demand applications)
Output data
Alarm outputs
Number of outputs 1 (digital, PNP)
Voltage 22 V DC (U
s
-2V)
Current max. 100 mA
Maximum inrush current 500 mA (t=1ms at U
s
)
Short-circuit protection no
General data
Relay type Electromechanical relay with forcibly guided contacts in accordance with
IEC/EN 61810-3 (EN 50205)
Nominal operating mode 100% operating factor
Degree of protection IP20
Min. degree of protection of inst. location IP54
Mounting type DIN rail mounting
Mounting position vertical or horizontal
Assembly instructions See derating curve
Type of housing PBT yellow
Clearances and creepage distances between the power circuits DIN EN 50178
Rated insulation voltage 250 V AC
Rated surge voltage/insulation Safe isolation, reinforced insulation 6 kV between input circuit and enabling cur-
rent path (13/14) and enabling current path (23/24) and enabling current path (33/
34)
Basic insulation 4 kV between all current paths and housing
Pollution degree 2
Surge voltage category III
Dimensions Screw connection Spring-cage connection
W x H x D 12.5 x 112.2 x 114.5 mm 12.5 x 116.6 x 114.5 mm
Connection data Screw connection Spring-cage connection
Conductor cross section, solid 0.2 mm² ... 2.5 mm² 0.2 mm² ... 1.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm² 0.2 mm² ... 1.5 mm²
Conductor cross section AWG/kcmil 24 ... 12 24 ... 16
Stripping length 7 mm 8 mm
Screw thread M3
Ambient conditions
Ambient temperature (operation) -40 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport) 75 % (on average, 85% infrequently, non-condensing)
PSR-MC40
106175_en_02 PHOENIX CONTACT 5
Maximum altitude max. 2000 m (Above sea level)
Shock 15g
Vibration (operation) 10 Hz ...150 Hz, 2g
Ambient conditions
Conformance / approvals
Conformance CE-compliant
Approvals $
Safety data
Stop category according to IEC 60204 0
Safety parameters for IEC 61508 - High demand
SIL 3
PFH
d
1.5 x 10
-9
(4ADC13; 5AAC15; 8760switching cycles/year)
Demand rate < 12 Months
Proof test interval 240 Months
Duration of use 240 Months
Safety parameters for IEC 61508 - Low demand
SIL 3
PFD
avg
1,46 x 10
-4
Proof test interval 60 Months
Duration of use 240 Months
Safety parameters for EN 62061
SIL CL 3
Safety characteristic data according to EN ISO 13849
Category 4
Performance level e (4ADC13; 5AAC15; 8760switching cycles/year)
Duration of use 240 Months
For applications in PLe, the required demand rate for the safety function is once per month.
PSR-MC40
106175_en_02 PHOENIX CONTACT 6
5Safety notes
WARNING: Risk of electric shock
During operation, parts of electrical switching
devices carry hazardous voltages.
Before working on the switching device, dis-
connect the power.
Please observe the safety regulations of elec-
trical engineering and industrial safety and lia-
bility associations!
Disregarding these safety regulations may re-
sult in death, serious personal injury or dam-
age to equipment.
Startup, mounting, modifications, and up-
grades should only be carried out by a skilled
electrical engineer!
WARNING: Risk of automatic machine re-
start!
For emergency stop applications, the ma-
chine must be prevented from restarting auto-
matically by a higher-level control system.
Protective covers must not be removed when
operating electrical switching devices.
WARNING: Danger due to faulty devices!
The devices may be damaged following an er-
ror and correct operation can no longer be en-
sured.
In the event of an error, replace the device im-
mediately.
Repairs to the device, especially if the hous-
ing must be opened, may only be carried out
by the manufacturer or authorized persons.
Otherwise the warranty is invalidated.
WARNING: Risk of automatic machine re-
start!
When using the manual reset function with
monitored start, the “cross-circuit between A2
(0V) and the cable from the reset button to
S34” error must be prevented by design-relat-
ed measures, especially for safety functions
with increased risk potential (see
ENISO13849-2).
WARNING: Risk due to incorrect installa-
tion
For reliable operation, the safety relay must
be installed in housing protected from dust
and humidity (IP54).
Carry out wiring according to the application.
Refer to the “Application examples” section
for this.
WARNING: Risk due to welded relay con-
tacts
A suitable and effective protective circuit is to
be provided for inductive loads. This is to be
implemented parallel to the load and not par-
allel to the switch contact.
WARNING: danger due to magnetic inter-
ference!
Do not use the device in the vicinity of strong
magnetic fields (e.g.,caused by transformers
or magnetic iron). The magnetic field strength
of the environment must not exceed 30A/m.
NOTE: Risk of damage to equipment due
to noise emissions
When operating relay modules the operator
must meet the requirements for noise emis-
sion for electrical and electronic equipment
(EN 61000-6-4) on the contact side and, if re-
quired, take appropriate measures.
NOTE: Risk of damage to equipment due
to noise emissions
This is a Class A product. In a domestic envi-
ronment it may cause radion inteference, in
which case the user may be required to take
adequate measures.
Only use power supply units with safe isola-
tion and SELV/PELV in accordance with EN
50178/VDE 0160 (SELV/PELV).

MIC2775-46YM5-TR

Mfr. #:
Manufacturer:
Microchip Technology / Micrel
Description:
Supervisory Circuits Single Voltage Supervisor with Dual Active-High and Low Push-Pull Outputs, Manua
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet