PSR-MC40
106175_en_02 PHOENIX CONTACT 13
ON ON OFF ON The sensor circuit is ac-
tive. The reset/start circuit
(S34) is/was activated.
The safety circuit (K1) is
not picking up.
External error: sensor cir-
cuit channel1 was
opened and reactivated.
Internal error: diagnostics
active.
External error: check the
sensor circuit.
Internal error: perform a
power down reset with sub-
sequent function test. If the
error occurs again after
the function test, replace
the device.
ON ON ON OFF The sensor circuit is ac-
tive. The reset/start circuit
(S34) is/was activated.
The safety circuit (K2) is
not picking up.
External error: sensor cir-
cuit channel2 was
opened and reactivated.
Internal error: diagnostics
active.
External error: check the
sensor circuit.
Internal error: perform a
power down reset with sub-
sequent function test. If the
error occurs again after
the function test, replace
the device.
OFF OFF OFF OFF The sensor circuit is ac-
tive.
1. No supply voltage at
A1/A
2. Over- or undervoltage
at A1
Check the supply voltage.
PWR
LED
IN1/2
LED
K1
LED
K2
LED
State Possible cause Remedy
PSR-MC40
106175_en_02 PHOENIX CONTACT 14
15 Application examples
Key:
Applications with the PSR-MC40
15.1 Emergency stop monitoring/automatic start
Two-channel emergency stop monitoring
Automatic start
Monitoring of external contactors
No cross-circuit detection in the sensor circuit
Suitable up to category4, PLe (ENISO13849-1),
SIL3 (EN62061), if cross-circuits in the control to the
actuator and the sensor circuit can be ruled out
Figure 12 Emergency stop monitoring/automatic start
15.2 Emergency stop monitoring/manual, monitored
start
Two-channel emergency stop monitoring
Manual, monitored start
Monitoring of external contactors
No cross-circuit detection in the sensor circuit
Suitable up to category4, PLe (ENISO13849-1),
SIL3 (EN62061), if cross-circuits in the control to the
actuator and the sensor circuit can be ruled out
Figure 13 Emergency stop monitoring/manual, moni-
tored start
S1 = Emergency stop button
S2 = Manual reset device
B1/B2 = Mechanical safety door switches
K1/K2 = Contactors
Cross-circuits in the cable installation can be
excluded if the safety relay and external con-
tactors K1 and K2 are located in the same
electrical installation space.
K1
K2
M
24V
K1
K2
N
L
S1
0V
K2
K1
A1
A2
13
14
PSR-MC40
S12
S22
( )
M1
( )
23
24
( )
34
33
S34
( )
K1
K2
M
24V
K1
K2
N
L
0V
S1
K2
K1
S2
A1
A2
13
14
PSR-MC40
S12S34
S22
( )( )
M1
( )
23
24
( )
34
33
PSR-MC40
106175_en_02 PHOENIX CONTACT 15
15.3 Safety door monitoring/automatic start
Two-channel safety door monitoring
Automatic start
Monitoring of external contactors
No cross-circuit detection in the sensor circuit
Suitable up to category4, PLe (ENISO13849-1),
SIL3 (EN62061), if cross-circuits in the control to the
actuator and the sensor circuit can be ruled out
Figure 14 Safety door monitoring/automatic start
15.4 Safety door monitoring/manual, monitored
start
Two-channel safety door monitoring
Manual, monitored start
Monitoring of external contactors
No cross-circuit detection in the sensor circuit
Suitable up to category4, PLe (ENISO13849-1),
SIL3 (EN62061), if cross-circuits in the control to the
actuator and the sensor circuit can be ruled out
Figure 15 Safety door monitoring/manual, monitored
start
K1
K2
M
24V
K1
K2
N
L
B1
open
closed
B2
0V
K2
K1
A1
A2
13
14
PSR-MC40
S12
S22
( )
M1
( )
23
24
( )
34
33
S34
( )
K1
K2
M
24V
K1
K2
N
L
0V
A1
A2
13
14
PSR-MC40
S12
S22
( )
M1
( )
23
24
( )
34
S34
( )
33
K1
K2
S2
B1
open
closed
B2

MIC2775-46YM5-TR

Mfr. #:
Manufacturer:
Microchip Technology / Micrel
Description:
Supervisory Circuits Single Voltage Supervisor with Dual Active-High and Low Push-Pull Outputs, Manua
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet