PSR-MC40
106175_en_02 PHOENIX CONTACT 10
11 Mounting and connection
Mount the module on a 35 mm DIN rail according to
EN60715.
Figure 8 Mounting and removing
Connect the cables to the connection terminal blocks using
a screwdriver.
Figure 9 Connecting the cables for PSR-...-SC
(screw terminal block)
Figure 10 Connecting the cables for PSR-...-SC
(spring-cage terminal block)
12 Startup
Apply the rated control supply voltage (24VDC) at terminal
blocks A1/A2. The PWR LED lights up.
Close sensor circuit 24V/S12 and 24V/S22. The IN1/2 LED
lights up.
Automatic or manual, monitored start:
Close contacts A1/S34 as follows.
Figure 11 Connection of automatic or manual, monitored
start
1 Automatic start
2 Manual, monitored start with monitored contact exten-
sion
3 Manual, monitored start
When automatic start is selected, the enabling current paths
close.
For manual, monitored start, first press the reset button. The
release of the button causes the enabling current paths to
close.
The K1 and K2 LEDs light up.
If the supply voltage drops or the sensor circuit (24V/S12 or
24V/S22) is opened, the enabling current paths of the out-
put circuits (13/14, 23/24, 33/43) open and the contacts
enter the safe state.
For compliance with UL approval, use copper
wire that is approvedupto 60°C/75°C.
0,5-0,6 Nm
5-7 lb In
7 mm
AWG 24-14
0,2-2,5 mm
2
PSR-...-SC
A
B
A
A
B
8 mm
AWG 24-16
0,2-1,5 mm
2
PSR-...-SP
0V S34
1
0V
K3
K4
A1 S34
2
24V DC
A1 S34
3
24V DC
PSR-MC40
106175_en_02 PHOENIX CONTACT 11
13 Calculating the power dissipation
Input power dissipation
P
Input
=U
B
²
/(U
S
/I
S
)
Contact power dissipation
With the same load currents:
P
Contact
=nI
L
²
50m
With different load currents:
P
Contact
=(I
L1
²
+I
L2
²
+...+I
Ln
²
)50m
Total power dissipation
P
Total
=P
Input
+P
Contact
therefore
P
Total
=U
B
²
/(U
S
/I
S
)+nI
L
²
50m
or
P
Total
=U
B
²
/(U
S
/I
S
)+(I
L1
²
+I
L2
²
+...+I
Ln
²
)50m
Key:
The total power dissipation of the safety relay
is based on the input power dissipation and
the contact power dissipation for the same
and for different load currents.
Designation Explanation
P Power dissipation in mW
U
B
Applied operating voltage
U
S
Rated control supply voltage
I
S
Rated control supply current
n Number of enabling current paths used
I
L
Contact load current
PSR-MC40
106175_en_02 PHOENIX CONTACT 12
14 Diagnostics
The following section describes the LED indicators for gen-
eral states and error messages as well as possible causes
and remedies.
Function test/proof test
14.1 General states
14.2 Error Messages
Use the function test to check the safety func-
tion. To do this, request the safety function
once by pressing the emergency stop button,
for example. Check whether the safety func-
tion is running correctly by switching the de-
vice on again via the sensor circuits.
PWR
LED
IN1/2
LED
K1
LED
K2
LED
State Notes
ON OFF OFF OFF All relays are not activated. The sensor
circuit is off.
Possible error see error messages
ON ON OFF OFF The sensor circuit is active. Relays K1
and K2 are ready to start and await reset/
start command (S34).
-
ON ON ON ON The sensor circuit is active. All relays are
picked up.
-
PWR
LED
IN1/2
LED
K1
LED
K2
LED
State Possible cause Remedy
ON OFF OFF OFF The sensor circuit is ac-
tively controlled, but no
input LEDs are lit up.
Interrupt in the sensor cir-
cuit or faulty signal gener-
ator.
Check the sensor circuit/sig-
nal generator. Then perform
a function test.
ON ON OFF OFF The sensor circuit is ac-
tive. The reset/start circuit
(S34) is/was activated.
The safety circuit (K1 and
K2) is not picking up.
External error: the read-
back contact (external ac-
tuator) is open in the reset
circuit.
Internal error:
1. The diagnostic contact
is not working correctly.
2. An N/O contact is
welded.
External error: check the ac-
tuator.
Internal error: perform a
power down reset with sub-
sequent function test. If the
error occurs again after
the function test, replace
the device.
ON ON OFF OFF The sensor circuit is ac-
tive. The reset/start circuit
(S34) is/was activated.
The safety circuit (K1 and
K2) is not picking up.
Error during manual reset
S34 (stuck-at at the in-
put).
Remove the error in the
reset/start circuit. Then per-
form a function test.

MIC2775-46YM5-TR

Mfr. #:
Manufacturer:
Microchip Technology / Micrel
Description:
Supervisory Circuits Single Voltage Supervisor with Dual Active-High and Low Push-Pull Outputs, Manua
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet