PSR-MC40
106175_en_02 PHOENIX CONTACT 19
15.11 Light grid monitoring/automatic start
Two-channel light grid monitoring
Automatic start
Monitoring of external contactors
No cross-circuit detection in the sensor circuit
Suitable up to category4, PLe (ENISO13849-1),
SIL3 (EN62061), if cross-circuits in the control to the
actuator can be ruled out
Figure 22 Light grid monitoring/automatic start
15.12 Light grid monitoring/manual, monitored start
Two-channel light grid monitoring
Manual, monitored start
Monitoring of external contactors
No cross-circuit detection in the sensor circuit
Suitable up to category4, PLe (ENISO13849-1),
SIL3 (EN62061), if cross-circuits in the control to the
actuator can be ruled out
Figure 23 Light grid monitoring/manual, monitored start
WARNING: Loss of functional safety!
Make sure that the signal generator (e.g., PLC
output card or light grid) and the safety relay
have the same ground potential.
K1
K2
M
24V DC
K1
K2
N
L
A1
13
14
PSR-MC40
S12
S22
( )
M1
( )
23
24
( )
34
S34
( )
33
Transmitter
Light grid type 4
OSSD1 OSSD2
Receiver
0V 24V
0V
A2
K2
K1
WARNING: Loss of functional safety!
Make sure that the signal generator (e.g., PLC
output card or light grid) and the safety relay
have the same ground potential.
K1
K2
M
24V DC
K1
K2
N
L
K1
K2
S2
A1
13
14
PSR-MC40
S12
S22
( )
M1
( )
23
24
( )
34
S34
( )
33
Transmitter
Light grid type 4
OSSD1 OSSD2
Receiver
0V 24V
0V
A2
PSR-MC40
106175_en_02 PHOENIX CONTACT 20
15.13 Transponder monitoring/automatic start
Two-channel transponder monitoring
Automatic start
Monitoring of external contactors
No cross-circuit detection in the sensor circuit
Suitable up to category4, PLe (ENISO13849-1),
SIL3 (EN62061), if cross-circuits in the control to the
actuator can be ruled out
Figure 24 Transponder monitoring/automatic start
15.14 Transponder monitoring/manual, monitored
start
Two-channel transponder monitoring
Manual, monitored start
Monitoring of external contactors
No cross-circuit detection in the sensor circuit
Suitable up to category4, PLe (ENISO13849-1),
SIL3 (EN62061), if cross-circuits in the control to the
actuator can be ruled out
Figure 25 Transponder monitoring/manual, monitored
start
WARNING: Loss of functional safety!
Make sure that the signal generator (e.g., PLC
output card or light grid) and the safety relay
have the same ground potential.
K1
K2
M
24V DC
K1
K2
N
L
0V
A1
A2
13
14
PSR-MC40
S12
S22
( )
M1
( )
23
24
( )
34
33
OSSD 1 OSSD 2
PLe
Cat.4
Transponder
0V 24V
K2
K1
S34
( )
WARNING: Loss of functional safety!
Make sure that the signal generator (e.g., PLC
output card or light grid) and the safety relay
have the same ground potential.
K1
K2
M
24V DC
K1
K2
N
L
0V
A1
A2
13
14
PSR-MC40
S12
S22
( )
M1
( )
23
24
( )
34
S34
( )
33
K1
K2
S2
OSSD 1 OSSD 2
PLe
Cat.4
Transponder
0V 24V
PSR-MC40
106175_en_02 21
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
15.15 Revision history
Version Date Contents
00 2014-12-03 First publication
01 2015-03-05 Reverse polarity protection extended; relay type extended; dimensions updated; load
curve extended
02 2015-08-21 Input voltage range "0"-signal added; relay type changed; application examples and
notes for the examples revised

MIC2775-46YM5-TR

Mfr. #:
Manufacturer:
Microchip Technology / Micrel
Description:
Supervisory Circuits Single Voltage Supervisor with Dual Active-High and Low Push-Pull Outputs, Manua
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet