15.11 Light grid monitoring/automatic start
– Two-channel light grid monitoring
– Automatic start
– Monitoring of external contactors
– No cross-circuit detection in the sensor circuit
– Suitable up to category4, PLe (ENISO13849-1),
SIL3 (EN62061), if cross-circuits in the control to the
actuator can be ruled out
Figure 22 Light grid monitoring/automatic start
15.12 Light grid monitoring/manual, monitored start
– Two-channel light grid monitoring
– Manual, monitored start
– Monitoring of external contactors
– No cross-circuit detection in the sensor circuit
– Suitable up to category4, PLe (ENISO13849-1),
SIL3 (EN62061), if cross-circuits in the control to the
actuator can be ruled out
Figure 23 Light grid monitoring/manual, monitored start
WARNING: Loss of functional safety!
Make sure that the signal generator (e.g., PLC
output card or light grid) and the safety relay
have the same ground potential.