Philips Semiconductors Product data
P89C660/P89C662/P89C664/
P89C668
80C51 8-bit Flash microcontroller family
16KB/32KB/64KB ISP/IAP Flash with 512B/1KB/2KB/8KB RAM
2002 Oct 28
16
Serial Clock Generator
This programmable clock pulse generator provides the SCL clock
pulses when SIO1 is in the Master Transmitter or Master Receiver
mode. It is switched off when SIO1 is in a Slave mode. The
programmable output clock frequencies are: f
OSC
/120, f
OSC
/9600
(12-clock mode) or f
OSC
/60, f
OSC
/4800 (6-clock mode) and the
Timer 1 overflow rate divided by eight. The output clock pulses have
a 50% duty cycle unless the clock generator is synchronized with
other SCL clock sources as described above.
Timing and Control
The timing and control logic generates the timing and control signals
for serial byte handling. This logic block provides the shift pulses for
S1DAT, enables the comparator, generates and detects start and
stop conditions, receives and transmits acknowledge bits, controls
the master and Slave modes, contains interrupt request logic, and
monitors the I
2
C bus status.
Control Register, S1CON
This 7-bit special function register is used by the microcontroller to
control the following SIO1 functions: start and restart of a serial
transfer, termination of a serial transfer, bit rate, address recognition,
and acknowledgment.
Status Decoder and Status Register
The status decoder takes all of the internal status bits and
compresses them into a 5-bit code. This code is unique for each I
2
C
bus status. The 5-bit code may be used to generate vector
addresses for fast processing of the various service routines. Each
service routine processes a particular bus status. There are 26
possible bus states if all four modes of SIO1 are used. The 5-bit
status code is latched into the five most significant bits of the status
register when the serial interrupt flag is set (by hardware) and
remains stable until the interrupt flag is cleared by software. The
three least significant bits of the status register are always zero. If
the status code is used as a vector to service routines, then the
routines are displaced by eight address locations. Eight bytes of
code is sufficient for most of the service routines.
The Four SIO1 Special Function Registers
The microcontroller interfaces to SIO1 via four special function
registers. These four SFRs (S1ADR, S1DAT, S1CON, and S1STA)
are described individually in the following sections.
The Address Register, S1ADR
The CPU can read from and write to this 8-bit, directly addressable
SFR. S1ADR is not affected by the SIO1 hardware. The contents of
this register are irrelevant when SIO1 is in a Master mode. In the
Slave modes, the seven most significant bits must be loaded with
the microcontroller’s own slave address, and, if the least significant
bit is set, the general call address (00H) is recognized; otherwise it
is ignored.
S1ADR (DBH) XGC
7
65 43210
own slave address
X XXXX X
The most significant bit corresponds to the first bit received from the
I
2
C bus after a start condition. A logic 1 in S1ADR corresponds to a
high level on the I
2
C bus, and a logic 0 corresponds to a low level
on the bus.
The Data Register, S1DAT
S1DAT contains a byte of serial data to be transmitted or a byte
which has just been received. The CPU can read from and write to
this 8-bit, directly addressable SFR while it is not in the process of
shifting a byte. This occurs when SIO1 is in a defined state and the
serial interrupt flag is set. Data in S1DAT remains stable as long as
SI is set. Data in S1DAT is always shifted from right to left: the first
bit to be transmitted is the MSB (bit 7), and, after a byte has been
received, the first bit of received data is located at the MSB of
S1DAT. While data is being shifted out, data on the bus is
simultaneously being shifted in; S1DAT always contains the last
data byte present on the bus. Thus, in the event of lost arbitration,
the transition from master transmitter to slave receiver is made with
the correct data in S1DAT.
S1DAT (DAH) SD7 SD6 SD5 SD4 SD3 SD2 SD1 SD0
7
65 43210
shift direction
SD7 - SD0:
Eight bits to be transmitted or just received. A logic 1 in S1DAT
corresponds to a high level on the I
2
C bus, and a logic 0
corresponds to a low level on the bus. Serial data shifts through
S1DAT from right to left. Figure 6 shows how data in S1DAT is
serially transferred to and from the SDA line.
S1DAT and the ACK flag form a 9-bit shift register which shifts in or
shifts out an 8-bit byte, followed by an acknowledge bit. The ACK
flag is controlled by the SIO1 hardware and cannot be accessed by
the CPU. Serial data is shifted through the ACK flag into S1DAT on
the rising edges of serial clock pulses on the SCL line. When a byte
has been shifted into S1DAT, the serial data is available in S1DAT,
and the acknowledge bit is returned by the control logic during the
ninth clock pulse. Serial data is shifted out from S1DAT via a buffer
(BSD7) on the falling edges of clock pulses on the SCL line.
When the CPU writes to S1DAT, BSD7 is loaded with the content of
S1DAT.7, which is the first bit to be transmitted to the SDA line (see
Figure 7). After nine serial clock pulses, the eight bits in S1DAT will
have been transmitted to the SDA line, and the acknowledge bit will
be present in ACK. Note that the eight transmitted bits are shifted
back into S1DAT.
The Control Register, S1CON
The CPU can read from and write to this 8-bit, directly addressable
SFR. Two bits are affected by the SIO1 hardware: the SI bit is set
when a serial interrupt is requested, and the STO bit is cleared when
a STOP condition is present on the I
2
C bus. The STO bit is also
cleared when ENS1 = “0”.
S1CON (D8H) ENS1 STA STO SI AA CR1 CR0
7
6543210
CR2
ENS1, the SIO1 Enable Bit: ENS1 = “0”: When ENS1 is “0”, the
SDA and SCL outputs are in a high impedance state. SDA and SCL
input signals are ignored, SIO1 is in the “not addressed” slave state,
and the STO bit in S1CON is forced to “0”. No other bits are
affected. P1.6 and P1.7 may be used as open drain I/O ports.
ENS1 = “1”: When ENS1 is “1”, SIO1 is enabled. The P1.6 and P1.7
port latches must be set to logic 1.
ENS1 should not be used to temporarily release SIO1 from the I2C
bus since, when ENS1 is reset, the I2C bus status is lost. The AA
flag should be used instead (see description of the AA flag in the
following text).
Philips Semiconductors Product data
P89C660/P89C662/P89C664/
P89C668
80C51 8-bit Flash microcontroller family
16KB/32KB/64KB ISP/IAP Flash with 512B/1KB/2KB/8KB RAM
2002 Oct 28
17
INTERNAL BUS
8
BSD7 S1DAT ACK
SCL
SDA
SHIFT PULSES
SU00969
Figure 6. Serial Input/Output Configuration
SHIFT IN
SDA
SCL
D7 D6 D5 D4 D3 D2 D1 D0 A
SHIFT ACK & S1DAT
ACK
(2) (2) (2) (2) (2) (2) (2) (2) A
(2) (2) (2) (2) (2) (2) (2) (2) (1)(1)S1DAT
SHIFT BSD7
BSD7
D7 D6 D5 D4 D3 D2 D1 D0 (3)
LOADED BY THE CPU
(1) Valid data in S1DAT
(2) Shifting data in S1DAT and ACK
(3) High level on SDA
SHIFT OUT
SU00970
Figure 7. Shift-in and Shift-out Timing
In the following text, it is assumed that ENS1 = “1”.
The “START” Flag, STA: STA = “1”: When the STA bit is set to
enter a Master mode, the SIO1 hardware checks the status of the
I2C bus and generates a START condition if the bus is free. If the
bus is not free, then SIO1 waits for a STOP condition (which will free
the bus) and generates a START condition after a delay of half a
clock period of the internal serial clock generator.
If STA is set while SIO1 is already in a Master mode and one or
more bytes are transmitted or received, SIO1 transmits a repeated
START condition. STA may be set at any time. STA may also be set
when SIO1 is an addressed slave.
STA = “0”: When the STA bit is reset, no START condition or
repeated START condition will be generated.
The STOP Flag, STO: STO = “1”: When the STO bit is set while
SIO1 is in a Master mode, a STOP condition is transmitted to the
I
2
C bus. When the STOP condition is detected on the bus, the SIO1
hardware clears the STO flag. In a Slave mode, the STO flag may
be set to recover from an error condition. In this case, no STOP
condition is transmitted to the I
2
C bus. However, the SIO1 hardware
behaves as if a STOP condition has been received and switches to
the defined “not addressed” Slave Receiver mode. The STO flag is
automatically cleared by hardware.
Philips Semiconductors Product data
P89C660/P89C662/P89C664/
P89C668
80C51 8-bit Flash microcontroller family
16KB/32KB/64KB ISP/IAP Flash with 512B/1KB/2KB/8KB RAM
2002 Oct 28
18
If the STA and STO bits are both set, the a STOP condition is
transmitted to the I
2
C bus if SIO1 is in a Master mode (in a Slave
mode, SIO1 generates an internal STOP condition which is not
transmitted). SIO1 then transmits a START condition.
STO = “0”: When the STO bit is reset, no STOP condition will be
generated.
The Serial Interrupt Flag, SI: SI = “1”: When the SI flag is set, then,
if the EA and ES1 (interrupt enable register) bits are also set, a
serial interrupt is requested. SI is set by hardware when one of 25 of
the 26 possible SIO1 states is entered. The only state that does not
cause SI to be set is state F8H, which indicates that no relevant
state information is available.
While SI is set, the low period of the serial clock on the SCL line is
stretched, and the serial transfer is suspended. A high level on the
SCL line is unaffected by the serial interrupt flag. SI must be reset
by software.
SI = “0”: When the SI flag is reset, no serial interrupt is requested,
and there is no stretching of the serial clock on the SCL line.
The Assert Acknowledge Flag, AA: AA = “1”: If the AA flag is set,
an acknowledge (low level to SDA) will be returned during the
acknowledge clock pulse on the SCL line when:
The “own slave address” has been received
The general call address has been received while the general call
bit (GC) in S1ADR is set
A data byte has been received while SIO1 is in the Master
Receiver mode
A data byte has been received while SIO1 is in the addressed
Slave Receiver mode
AA = “0”: if the AA flag is reset, a not acknowledge (high level to
SDA) will be returned during the acknowledge clock pulse on SCL
when:
A data has been received while SIO1 is in the Master Receiver
mode
A data byte has been received while SIO1 is in the addressed
Slave Receiver mode
When SIO1 is in the addressed Slave Transmitter mode, state C8H
will be entered after the last serial is transmitted (see Figure 11).
When SI is cleared, SIO1 leaves state C8H, enters the not
addressed Slave Receiver mode, and the SDA line remains at a
high level. In state C8H, the AA flag can be set again for future
address recognition.
When SIO1 is in the not addressed Slave mode, its own slave
address and the general call address are ignored. Consequently, no
acknowledge is returned, and a serial interrupt is not requested.
Thus, SIO1 can be temporarily released from the I
2
C bus while the
bus status is monitored. While SIO1 is released from the bus,
START and STOP conditions are detected, and serial data is shifted
in. Address recognition can be resumed at any time by setting the
AA flag. If the AA flag is set when the part’s own Slave address or
the general call address has been partly received, the address will
be recognized at the end of the byte transmission.
The Clock Rate Bits CR0, CR1, and CR2: These three bits
determine the serial clock frequency when SIO1 is in a Master
mode. The various serial rates are shown in Table 3.
A 12.5 kHz bit rate may be used by devices that interface to the I
2
C
bus via standard I/O port lines which are software driven and slow.
100 kHz is usually the maximum bit rate and can be derived from a
16 MHz, 12 MHz, or a 6 MHz oscillator. A variable bit rate (0.5 kHz
to 62.5 kHz) may also be used if Timer 1 is not required for any
other purpose while SIO1 is in a Master mode.
The frequencies shown in Table 3 are unimportant when SIO1 is in a
Slave mode. In the Slave modes, SIO1 will automatically
synchronize with any clock frequency up to 100 kHz.
The Status Register, S1STA
S1STA is an 8-bit read-only special function register. The three least
significant bits are always zero. The five most significant bits contain
the status code. There are 26 possible status codes. When S1STA
contains F8H, no relevant state information is available and no serial
interrupt is requested. All other S1STA values correspond to defined
SIO1 states. When each of these states is entered, a serial interrupt
is requested (SI = “1”). A valid status code is present in S1STA one
machine cycle after SI is set by hardware and is still present one
machine cycle after SI has been reset by software.

P89C662HBA/00,512

Mfr. #:
Manufacturer:
NXP Semiconductors
Description:
IC MCU 8BIT 32KB FLASH 44PLCC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union