Device operation M34F04
16/26 DocID11090 Rev 4
3.12 Current address read
The device has an internal address counter which is incremented each time a byte is read.
For the Current Address Read operation, following a Start condition, the bus master only
sends a Device Select Code with the RW
bit set to 1. The device acknowledges this, and
outputs the byte addressed by the internal address counter. The counter is then
incremented. The bus master terminates the transfer with a Stop condition, as shown in
Figure 7, without acknowledging the byte.
3.13 Sequential read
This operation can be used after a Current Address Read or a Random Address Read. The
bus master does acknowledge the data byte output, and sends additional clock pulses so
that the device continues to output the next byte in sequence. To terminate the stream of
bytes, the bus master must not acknowledge the last byte, and must generate a Stop
condition, as shown in Figure 7.
The output data comes from consecutive addresses, with the internal address counter
automatically incremented after each byte output. After the last memory address, the
address counter ‘rolls-over’, and the device continues to output data from memory address
00h.
3.14 Acknowledge in read mode
For all Read commands, the device waits, after each byte read, for an acknowledgment
during the 9
th
bit time. If the bus master does not drive Serial Data (SDA) Low during this
time, the device terminates the data transfer and switches to its Stand-by mode.