© PHOENIX CONTACT 2012-05-08
8466_en_01
IB IL TEMP 4/8 RTD-EF-XC-PAC
Data sheet
1 Function description
The terminal is designed for use within an Inline station. This
terminal provides an 8-channel input module with three lin-
ear resistance ranges for resistance temperature detectors.
This terminal supports, for example:
Platinum and nickel sensors, e.g., Pt100, Pt1000,
Ni100, and Ni1000 according to the DIN IEC 60751
standard and to the SAMA RC 21-4-1966 guideline
KTY81 and KTY84 sensors
Cu10, Cu50, and Cu53 sensors
Communication either via
Parameter channel (PCP), all eight measuring chan-
nels, or
Four process data words; always four channels
(four 16-bit values) using the multiplex method
Thanks to special engineering measures and tests, the ter-
minal can be used under extreme ambient conditions.
Features
Connection of eight RTD temperature sensors and lin-
ear resistors in 4-wire technology
High precision and noise immunity
Temperature stability
High-resolution temperature and resistance measure-
ment
Resistance values (R
0
) can be preset separately using
configuration bits
Channels are configured independently of one another
using the bus system.
Configuration of open circuit detection sensitivity (firm-
ware 1.10 or later)
Additional representation in float format according to
IEEE 754
Diagnostic and status indicators
Channel scout functionality, e.g., for optical channel
identification during startup
Can be used under extreme ambient conditions
–Painted PCBs
Extended temperature range T2 (-40°C … +55°C)
This data sheet is only valid in association with the IL SYS INST UM E user manual.
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog
.
Inline Modular analog input terminal,
version for extreme conditions,
8 inputs, RTD
IB IL TEMP 4/8 RTD-EF-XC-PAC
8466_en_01 PHOENIX CONTACT 2
Table of contents
1 Function description ................................................................................................................... 1
2 Ordering data.............................................................................................................................. 3
3 Technical data ............................................................................................................................ 4
4 Tolerance and temperature response ........................................................................................ 7
5 Tested successfully: Use under extreme ambient conditions ..................................................... 9
6 Internal basic circuit diagram .....................................................................................................10
7 Local diagnostic and status indicators and terminal point assignment.......................................11
8 Safety note.................................................................................................................................11
9 Installation instructions ..............................................................................................................11
10 Electrical isolation................................................................................................................................................ 12
11 Connection notes.......................................................................................................................12
12 Connection examples ................................................................................................................12
13 Process data..............................................................................................................................15
14 OUT process data words ...........................................................................................................15
15 IN process data words ...............................................................................................................19
16 Formats for representing measured values................................................................................20
17 PCP communication ..................................................................................................................22
18 Object descriptions....................................................................................................................22
19 Configuration and analog values................................................................................................27
20 Temperature and resistance measuring ranges.........................................................................27
21 Measuring errors due to connection cables ...............................................................................27
22 Calculation examples ......................................................................................................................................... 29
23 Configuration example...............................................................................................................31
24 Notes on diagnostic behavior in the event of an error ................................................................33
IB IL TEMP 4/8 RTD-EF-XC-PAC
8466_en_01 PHOENIX CONTACT 3
2Ordering data
Products
Description Type Order No. Pcs. / Pkt.
Inline Modular analog input terminal, version for extreme conditions, 8 inputs,
RTD (resistance temperature detector), 4-wire connection method, complete
with individually numbered I/O connectors
IB IL TEMP 4/8 RTD-EF-XC-PAC 2701218 1
Accessories: Connectors
Description Type Order No. Pcs. / Pkt.
Inline connectors IB IL SCN-8 2726337 10
Labeling field, 12.2 mm width IB IL FIELD 2 2727501 5
Insert strip, sheet, white, unlabeled, can be labeled with: Office printing sys-
tems, plotter: laser printer, Mounting type: insertion, lettering field size: 62 x 10
mm
ESL 62X10 0809492 1
Accessories: Other
Description Type Order No. Pcs. / Pkt.
Shield connection clamp for applying the shield on busbars
8 mm diameter SK8 3025163 10
14 mm diameter SK14 3025176 10
20 mm diameter SK20 3025189 10
35 mm diameter SK35 3026463 10
Support for assembly on DIN rails
for 10 mm x 3 mm busbars
AB-SK 3025341 10
Support for direct mounting with contact to the mounting surface AB-SK 65 3026489 10
Support, made of insulation material, with fixing screws, can be used for either
10 mm x 3 mm or 6 mm x 6 mm busbars
AB-SK/E 3026476 10
N busbar, 10 mm x 3 mm, 1 m long NLS-CU 3/10 0402174 10
End terminal, 4 mm
2
, without insulating cap AK 4 0404017 50
End terminal, 4 mm
2
, with insulating cap, green-yellow for PE AK G GNYE 0421029 50
End terminal, 4 mm
2
, with insulating cap, black for L1, L2, L3 AKG 4 BK 0421032 50
Documentation
Description Type Order No. Pcs. / Pkt.
“Automation terminals of the Inline product range” user manual IL SYS INST UM E

2701218

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Controllers IB IL TEMP4/8 RTD-EF XC-PAC