IB IL TEMP 4/8 RTD-EF-XC-PAC
8466_en_01 PHOENIX CONTACT 25
18.4 Measured Value Float object (0082
hex
)
Object description:
The extended float format is a specific format from Phoenix Contact and consists of the measured value, the status and the
unit code. The status is required as there are no patterns informing about the status of the value defined in the float format.
The status corresponds to the lower bytes of the Inline error code.
For example, if status = 01 with overrange, the Inline error code is 8001
hex
. The measured value is valid if status=0.
Measured value record:
Structure of the float format according to IEEE 754
S = 1 sign bit, 0: positive, 1: negative
E = 8 bits, exponent with offset 7Fh
hex
M = 23 bits, mantissa
Example values for the float format
This format provides the highest internal module accuracy and is independent of the configured resolution.
Object Measured Value Float
Access Read
Data type Array of Record 8 x 6 bytes
Index 0082
hex
Subindex 01
hex
02
hex
03
hex
04
hex
05
hex
06
hex
07
hex
08
hex
Analog value of channel 1
Analog value of channel 2
Analog value of channel 3
Analog value of channel 4
Analog value of channel 5
Analog value of channel 6
Analog value of channel 7
Analog value of channel 8
Length (bytes) 30
hex
06
hex
Subindex 00
hex
Subindex 01
hex
to 08
hex
Data Analog values of the channels
Element Data type Length in bytes Meaning
.1 Float 4 Measured value in float format according to
IEEE 754
.2 Unsigned 8 1 Status
.3 Unsigned 8 1 Unit code: 32: °C, 33: °F, 37: Ω
Bit 25 17 9 1
Assignment VEEE EEEE EMMM MMMM MMMM MMMM MMMM MMMM
1.0 3F 80 00 00
hex
-1.0 BF 80 00 00
hex
10 41 20 00 00
hex
1.03965528 3F 85 13 6D
hex
IB IL TEMP 4/8 RTD-EF-XC-PAC
8466_en_01 PHOENIX CONTACT 26
18.5 Channel Scout object (0090
hex
)
The channel scout function supports the fast discovery of a measuring channel on the Inline terminal (e.g., during startup).
Object description:
Value range:
The channel scout functionality is superior to all diagnostics messages of the selected LED and must be disabled
separately by the user. In comparison, the configuration of a channel automatically causes this functionality to be
aborted.
Object Channel Scout
Access Read/ Write
Data type Unsigned 1 byte
Index 0090
hex
Length (bytes) 01
hex
Subindex 00
hex
Data Control of the channel LED
0 Disable all channel scout processes
1 ... 8 Orange LED of the channel is flashing at
0.5 Hz (1 second ON, 1 second OFF)
IB IL TEMP 4/8 RTD-EF-XC-PAC
8466_en_01 PHOENIX CONTACT 27
19 Configuration and analog values
The terminal only needs to be configured if the channels are
not to be operated with the default values (see “Parameters
for configuration” on page 17).
You can either configure the terminal via process data or
via PCP and transmit analog values accordingly.
If you have configured the terminal via PCP, the configura-
tion can no longer be modified via the process data.
Examples for terminal configuration via process data
20 Temperature and resistance mea-
suring ranges
20.1 Measuring ranges depending on the resolution
(IB IL format)
Where:
21 Measuring errors due to connec-
tion cables
21.1 4-wire technology
The terminal provides 4-wire technology for all eight chan-
nels and supports the maximum connection length of
250 meters for each sensor. Additional measuring toler-
ances caused by the cable length do not occur.
21.2 Systematic errors during temperature mea-
surement using 2-wire technology
Figure 10 Systematic temperature measuring error ΔT
depending on the cable length l
Curves depending on cable cross section A
(Measuring error valid for: copper cable χ = 57 m/Ωmm
2
,
T
A=
25°C and Pt 100 sensor)
Figure 11 Systematic temperature measuring error ΔT
depending on the cable cross section A
(Measuring error valid for: copper cable χ = 57 m/Ωmm
2
,
T
A
=
25°C, l = 5 m, and Pt100 sensor)
For easy terminal configuration a function block
can be downloaded at
www.phoenixcontact.net/catalog
.
Resolution Temperature sensors
00 -273°C to +3276.8°C;
Resolution: 0.1°C
01 -273°C to +327.68°C;
Resolution: 0.01°C
10 -459°F to +3276.8°F
Resolution: 0.1°F
11 -459°F to +327.68°F
Resolution: 0.01°F
Temperature values can be converted from °C to
°F with this formula:
T [°F] Temperature in °F
T [°C] Temperature in °C
T [ ° F ] = T [ ° C ] x + 3 2
9
5
(1) Temperature measuring error for A = 0.14 mm
2
(2) Temperature measuring error for A = 0.25 mm
2
(3) Temperature measuring error for A = 0.50 mm
2
0.0
3.0
6.0
9.0
12.0
15.0
0.0 2.5 5.0 7.5
10.0 12.5 15.0 17.5 20.0
K
l
m
57551014
(1)
(2)
(3)
D
T
0.0
1.0
2.0
3.0
4.0
5.0
6.0
0
0.1
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
K
A
mm²
7567A012
D
T

2701218

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Controllers IB IL TEMP4/8 RTD-EF XC-PAC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union