IB IL TEMP 4/8 RTD-EF-XC-PAC
8466_en_01 PHOENIX CONTACT 10
6 Internal basic circuit diagram
Figure 2 Internal wiring of the terminal points
Key:
Local bus
U
L+
U
ANA
U
L-
+24V(U )
M
+24V(U)
S
Input protection and signal filtering / open circuit detection / multiplexer
Supervisor
µC
SRE 1
OPC
IB protocol chip
24 V
DC
IN
+5 V
UL
+3,3 V
+5 V
+7,5 V
I
K1
I
K3
I
K5
I
K7
I
K2
I
K4
I
K6
I
K8
Voltage
monitoring
7567B002
Protocol chip
Register expansion
Hardware monitoring
Hardware monitoring
Microcontroller
Optocoupler
Analog/digital converter
OPC
S R E 1
S u p e r v i s o r
IB protocol chip
µ C
Amplifier
Voltage monitoring
DC/DC converter with electrical
isolation
Input protection and signal filter,
open circuit detection,
multiplexer
Constant current source
Other symbols used are explained in the
IL SYS INST UM E user manual.
Voltage
monitoring
x x x
X X X
Input protection and signal filtering
open circuit detection
multiplexer
IB IL TEMP 4/8 RTD-EF-XC-PAC
8466_en_01 PHOENIX CONTACT 11
7 Local diagnostic and status indica-
tors and terminal point assignment
Figure 3 terminal with an appropriate connector
7.1 Local diagnostics and status LEDs
7.2 Function identification
Green
2 Mbps: white stripe in the vicinity of the D LED
7.3 Terminal point assignment with 4-wire connec-
tion
8Safety note
9 Installation instructions
High current flowing through potential jumpers U
M
and U
S
leads to a temperature rise in the potential jumpers and in-
side the terminal. To keep the current flowing through the
potential jumpers of the analog terminals as low as possible,
always place the analog terminals after all the other termi-
nals at the end of the main circuit (for the sequence of the
Inline terminals: see also IL SYS INST UM E user manual).
Des. Color Meaning
D Green Diagnostics
TR Green PCP
LED
1 ... 8
Green
ON
Measuring channel in operation
Red ON Open circuit, over-/underrange
Orange Channel Scout
Flashing
at 0.5 Hz
Channel “n” is selected for startup pur-
poses with the PCP object (see Section
“Channel Scout object (0090
hex
)” on
page 26).
TR
D
TEMP 4/8
RTD E F
1
2
3
4
5
6
7
8
12
1
2
3
4
1
2
3
4
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
7567B003
D
TR
TEMP 4/8
RTD EF
1
2
3
4
5
6
7
8
Terminal
points
Signal Assignment
1.1 U
1
+ RTD sensor 1
1.2 I
1+
Constant current supply
1.3 I
1
-
1.4 U
1
- RTD sensor 1
2.1 U
2
+ RTD sensor 2
2.2 I
2
+
Constant current supply
2.3 I
2
-
2.4 U
2
- RTD sensor 2
WARNING: Electric shock
During configuration, ensure that no isolating volt-
age for safe isolation is specified between the an-
alog inputs and the bus. During thermistor
detection, for example, this means that the user
has to provide signals with safe isolation, if ap-
plicable.
IB IL TEMP 4/8 RTD-EF-XC-PAC
8466_en_01 PHOENIX CONTACT 12
10 Electrical isolation
Figure 4 Electrical isolation of the individual function
areas
11 Connection notes
Always connect temperature shunts using shielded,
twisted-pair cables.
The connection examples show how to connect the shield
(Figure 5).
Insulate the shield at the sensor.
Short-circuit unused channels (see Figure 5 on page 12,
channel 4).
12 Connection examples
12.1 4-wire connection
Figure 5 4-wire connection example
Example assignment:
7567A004
Analog inputs
FE potential
A
B
Electrical isolation
between area
A and B
U (24 V DC)
ANA
Local bus (IN)
I/O interface
Bus interface
OPC
and microcontroller
Local bus (OUT)
U (7.5 V DC)
L
U (24 V DC)
ANA
U (7.5 V DC)
L
24 V
5V
5V
Connect the braided shield of the sensor cable at
one end only.
For the assignments illustrated below, it is abso-
lutely necessary to connect the cable shield at a
central point in the control cabinet. The braided
shield can be connected to a shield busbar using,
for example, a shield connection clamp of SK8
type, Order No. 3025163.
Chan-
nel
Connection
method
Remark
1 4-wire connection
2 ... 8 Not used Insert the short-circuit
jumper.
12
1
2
3
4
1
2
3
4
34
1
2
3
4
1
2
3
4
56
1
2
3
4
1
2
3
4
78
1
2
3
4
1
2
3
4
D
TR
1
2
3
4
Slot
Channel
12345678
RL
RL
RL
RTD
RL
7567B009
U+
I-
I+