IB IL TEMP 4/8 RTD-EF-XC-PAC
8466_en_01 PHOENIX CONTACT 22
17 PCP communication
When the terminal is delivered, it is configured according to the default settings. To adapt the configuration, the terminal can
be configured via process data or PCP.
In PCP mode, the terminal is configured with the “Config Table” object.
17.1 Object dictionary
18 Object descriptions
18.1 DiagState object (0018
hex
)
Object description:
The object is used for structured error reporting and is defined in the basic profile.
For information on PCP communication, please refer to the IBS SYS PCP G4 UM E (Order No. 2745169) and
IBS PCP COMPACT UM E (Order No. 9015349) user manuals.
The IBS CMD (for standard controller boards) and PC WORX (for Field Controllers (FC) and Remote Field Con-
trollers (RFC)) programs are available for the configuration and parameterization of your INTERBUS system.
For additional information, please refer to the IBS CMD SWT G4 UM E user manual and the documentation for the
version of PC WORX used.
Index Object name Meaning Data type N L Rights
0018
hex
DiagState Diagnostics status Record 6 rd
0080
hex
Config table Configuration table Array of Unsigned 16 12 2 rd/wr
0081
hex
Analog Values Measured value in 16-bit format Array of Unsigned 16 8 2 rd
0082
hex
Measured Value Float Measured value in extended
float format
Record 8 6 rd
0090
hex
Channel Scout Channel Scout Unsigned 8 1 1 rd/wr
N: Number of elements rd: Read access permitted
L: Length of an element in bytes wr: Write access permitted
Subindex Data type Meaning Content
1 Unsigned 16 Error Number 0 ... 65535
2 Unsigned 8 Priority ErrorCode = 0000
hex
-> Prio: 00
hex
, otherwise 02
hex
3 Unsigned 8 Channel ErrorCode = 0000
hex
-> Channel: 00
hex
, otherwise 01
hex
...
08
hex
4 Unsigned 16 Error Code 0000
hex
: OK,
8910
hex
: Overrange,
8920
hex
: Underrange,
7710
hex
: Open circuit,
5160
hex
: Power failure,
5010
hex
: Hardware fault
5 Unsigned 8 More follows 00
6 OctetString Text (10 characters) ErrorCode=0000-> Text: 'Status OK', otherwise error-specific