IB IL TEMP 4/8 RTD-EF-XC-PAC
8466_en_01 PHOENIX CONTACT 19
15 IN process data words
15.1 Input word IN1 (status word)
The input word IN1 serves as status word.
EB: Error bit
Mirroring of the command code:
A command code mirrored from the control word. Here, the MSB is suppressed.
15.2 Input words IN2 to IN5
The measured values, the configuration or the firmware version are transmitted to the controller board or the PC using the
process data input words IN2 to IN5 in accordance with the configuration.
For the control word 3C00
hex
, IN2 supplies the firmware version and the module ID.
Example: firmware version 1.23:
Basically two formats are available for the representation of the measured values. For more detailed information about the
formats, please refer to “Formats for representing measured values” on page 20.
IN1
Bit 1514131211109876543210
Assignment
EB Mirrored command code 00000000
EB = 0 No error has occurred.
EB = 1 An error has occurred.
IN2
Bit 1514131211109876543210
Assignment
(hex)
123E
hex
Meaning Firmware version 1.23 Module ID
MSB LSB
1514131211109876543210
SB Analog value
IB IL format,
S7-compatible format
MSB Most significant bit
LSB Least significant bit
SB Sign bit
AV Analog value
IB IL TEMP 4/8 RTD-EF-XC-PAC
8466_en_01 PHOENIX CONTACT 20
16 Formats for representing measured values
16.1 IB IL format (default setting)
The measured value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit.
This format supports extended diagnostics. Values > 8000
hex
and < 8100
hex
indicate an error.
Measured value representation in IB IL format, 15 bits
The following diagnostics codes are supported:
MSB LSB
1514131211109876543210
SB Analog value
SB Sign bit
IB input word All temperature sensors [°C/°F] R
0
up to 500 Ω R
0
up to 5 kΩ
Code (hex) Dec Resolution Resolution Resolution Resolution
0.1°C/°F 0.01°C/°F 0.1 Ω 0.01 Ω 1 Ω 0.1 Ω
8001 Overrange > Limit value > Limit value >525 >325.12 >5250 >3251.2
0FA0 1000 +100.0 +10.0 100.0 10.0 1000.0 100.0
0001 1 +0.1 +0.01 +0.1 +0.01 +1.0 +0.1
0000 0 0 0 0 0 0 0
FFFF -1 -0.1 -0.01
FC18 -1000 -100.0 -10.0
8080 Underrange < Limit value < Limit value
Code (hex) Error
8001 Overrange
8002 Open circuit
8004 Measured value invalid/no valid measured value available (e.g., because channel was not configured)
8010 Invalid configuration
8020 I/O supply voltage fault
8040 Terminal faulty
8080 Underrange
If the measured value is outside the representation area of the process data, the “Overrange” or “Underrange” error
message is displayed.
IB IL TEMP 4/8 RTD-EF-XC-PAC
8466_en_01 PHOENIX CONTACT 21
16.2 S7-compatible format
The measured value for temperature and resistance values is represented in bits 14 to 0. An additional bit (bit 15) is available
as a sign bit.
Measured value representation in S7 format, 15 bits
The following diagnostics codes are possible:
MSB LSB
1514131211109876543210
SB Analog value
SB Sign bit
IB input word All temperature sensors [°C/°F] 0 to 500 Ω 0 to 5 kΩ
Code (hex) Dec Resolution Resolution Resolution Resolution
0.1°C/°F 0.01°C/°F 0.1 Ω 0.01 Ω 1 Ω 0.1 Ω
7FFF Overrange > Limit value > Limit value >525 >325.12 >5250 >3251.2
0FA0 1000 +100.0 +10.0 100.0 10.0 1000.0 100.0
0001 1 +0.1 +0.01 +0.1 +0.01 +1.0 +0.1
0000 0 0 0 0 0 0 0
FFFF -1 -0.1 -0.01
FC18 -1000 -100.0 -10.0
8000 Underrange < Limit value < Limit value
Code (hex) Error
7FFF Overrange
8002 Open circuit
8004 Measured value invalid/no valid measured value available (e.g., because channel was not configured)
8010 Invalid configuration
8020 I/O supply voltage fault
8040 Terminal defective
8000 Underrange
If the measured value is outside the representation area of the process data, the “Overrange” or “Underrange” error
message is displayed.