1Description
AxiolineF temperature module,
4inputs for connection of thermocouple sensors
AXL F UTH4 1H
© PHOENIX CONTACT
Data sheet
The module is designed for use within an AxiolineF station.
It is used to acquire signals from standard thermocouples in
industrial applications.
The module supports various types of thermocouple con-
forming to DINEN60584-1 and DIN46710 as well as linear
voltages from -100mV to +100mV.
It also offers a voltage input from -5V to +5V. Heating cur-
rents can be monitored here, forexample, using a measur-
ing transducer.
Both Pt 100 inputs (CJ1 and CJ2) can each be used as a
sensor input or as an external cold junction.
Features
4 analog input channels to connect thermocouples or
linear voltages from -100mV to +100mV
1 analog input channel to connect voltages from -5V to
+5V
Connection of sensors in 2-wire technology
Internal detection and compensation of cold junction
temperature (configurable)
External connection of Pt100 cold junction sensors
possible
Easy to use due to internal linearization of the sensor
characteristic curves
High level of accuracy (typically ±0.01%sensor typeK)
High level of accuracy, even in various mounting posi-
tions, thanks to built-in space compensation of the inter-
nal cold junction
High temperature stability (typically 8ppm/K)
High level of immunity to EMI (ClassA)
Low emitted interference
"Channel scout" function
Device type label stored
Diagnostic and status indicators
Installation monitoring with indication via diagnostic
LED for each channel
This data sheet is only valid in association with the UMENAXLFSYSINST user manual.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
8672_en_02
2014-10-27
AXL F UTH4 1H
8672_en_02 PHOENIX CONTACT 2
2Table of contents
1 Description .............................................................................................................................. 1
2 Table of contents ..................................................................................................................... 2
3 Ordering data .......................................................................................................................... 3
4 Technical data ......................................................................................................................... 4
5 Additional technical data.......................................................................................................... 7
6 Internal circuit diagram .......................................................................................................... 15
7 Terminal point assignment..................................................................................................... 16
8 Connection examples............................................................................................................16
9 Connection notes .................................................................................................................. 20
10 Configuration notes ............................................................................................................... 20
11 Local status and diagnostic indicators................................................................................... 21
12 Process data.......................................................................................................................... 23
13 Open circuit ........................................................................................................................... 23
14 Significant values in various formats...................................................................................... 24
15 Parameter, diagnostics and information (PDI) ....................................................................... 25
16 Standard objects ................................................................................................................... 26
17 Application objects ................................................................................................................ 31
18 Writing the analog values over the PDI channel..................................................................... 37
19 Device descriptions ............................................................................................................... 37
AXL F UTH4 1H
8672_en_02 PHOENIX CONTACT 3
Description Type Order No. Pcs. / Pkt.
AxiolineF temperature module, 4inputs for connection of thermocouple
sensors (including bus base module and connectors)
AXL F UTH4 1H 2688598 1
3Ordering data
Accessories Type Order No. Pcs. / Pkt.
AxiolineF bus base module for housing type H (Replacement item) AXL F BS H 2700992 5
Axioline shield connection set (contains 2 busbar holders and 2 SK 5 shield
connection clamps)
AXL SHIELD SET 2700518 1
Zack marker strip for AxiolineF (device labeling), in 2 x 20.3 mm pitch, un-
printed, 25-section, for individual labeling with B-STIFT 0.8, X-PEN, or
CMS-P1-PLOTTER (Marking)
ZB 20,3 AXL UNPRINTED 0829579 25
Zack marker strip, flat, in 10 mm pitch, unprinted, 10-section, for individual
labeling with M-PEN 0,8, X-PEN, or CMS-P1-PLOTTER (Marking)
ZBF 10/5,8 AXL UNPRINTED 0829580 50
Thermoelectric voltage terminal block, cross section: 0.2 - 2.5 mm², width:
10.4 mm, color: gray
MTKD-CU/CUNI 3100059 50
Thermoelectric voltage terminal block, cross section: 0.2 - 2.5 mm², width:
10.4 mm, color: gray
MTKD-FE/CUNI 3100046 50
Thermoelectric voltage terminal block, cross section: 0.2 - 2.5 mm², width:
10.4 mm, color: gray
MTKD-NICR/CUNI 3100075 50
Thermoelectric voltage terminal block, cross section: 0.2 - 2.5 mm², width:
10.4 mm, color: gray
MTKD-NICR/NI 3100062 50
Thermoelectric voltage terminal block, cross section: 0.2 - 2.5 mm², width:
10.4 mm, color: gray
MTKD-E-CU/A-CU 3100091 50
Thermoelectric voltage terminal block, cross section: 0.2 - 2.5 mm², width:
10.4 mm, color: gray
MTKD-S-CU/E-CU 3100101 50
Insert label, Roll, white, unlabeled, can be labeled with: THERMOMARK
ROLL, THERMOMARK X, THERMOMARK S1.1, Mounting type:
snapped into marker carrier, Lettering field: 35 x 46 mm (Marking)
EMT (35X46)R 0801604 1
Documentation Type Order No. Pcs. / Pkt.
User manual, English, AxiolineF: System and installation UM EN AXL F SYS INST - -
User manual, English, Axioline F: Diagnostic registers, and error messages UM EN AXL F SYS DIAG - -

2688598

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
I/O Modules AXL F UTH4 1H
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet