AXL F UTH4 1H
8672_en_02 PHOENIX CONTACT 31
16.6 Objects for device management
"Password" object
By entering the "Superuser" password you permit writing to the "Exclusiv right received" object. These rights are required to
transmit process data over the PDI channel.
17 Application objects
17.1 Parameter table (0080
hex
: ParaTable)
Parameterize the module using this object.
In the case of valid parameters, the parameterization is stored in the module permanently.
After resetting, the module works with the last permanently stored data. Upon delivery, the module works with the default data
(default settings).
Index
(hex)
Object name Object
type
Data type A L Rights Meaning
001D Password Simple vari-
able
Octet string 1 9 W Password
001D
hex
: password (Write)
Subindex Data type Length in
bytes
Meaning
0 Simple variable 9 Password
Index
(hex)
Object name Object
type
Data type A L Rights Assignment
0080 ParaTable Array Unsigned 16 6 6 * 2 R/W Parameter table
0082 Measured Value
Float
Array Octet string 4 4 * 6 R Measured values in the extended float
format
0083 PD Min Array Integer16 5 5 * 2 R Minimum process data value
0084 PD Max Array Integer16 5 5 * 2 R Maximum process data value
008F Local adjust value Var Octet string 1 8 R/W Local adjust values
0090 Channel Scout Var Unsigned 8 1 1 R/W Channel Scout
0080
hex
: ParaTable (read, write)
Subindex Data type Length in
bytes
Meaning Default value
0 Array of Unsigned 16 6 * 2 Read/write all elements See subindices
1 Unsigned 16 2 Parameterization of channel 1 001F
hex
:Unsigned 162 :
4 Unsigned 16 2 Parameterization of channel 4 001F
hex
5 Unsigned 16 2 Data format, mounting position 0000
hex
6 Unsigned 16 2 Reserved 0000
hex