8.8 Universal AC and DC current acquisition in
combination with a current transducer
Any AC or DC currents with 300VAC safe isolation accord-
ing to EN50178, EN61010, suchas heating currents, can
be acquired via the ±5 V voltage input (terminal points 02
and 12) using a current transducer.
For signal conditioning, use the MCR-S-1-5-UI(-SW)-DCI
current transducer from Phoenix Contact, forexample.
Figure 13 Measurement of an AC or DC current signal at
the -5V voltage input ... +5VDC in combina-
tion with a current transducer (heating current
acquisition)
9 Connection notes
Use encapsulated thermocouples.
Always connect the thermocouples using twisted pair equal-
izing conductors.
Use shielded twisted pair equalizing conductors for a cable
length from 10m.
For mV sensors in environments prone to interference as
well as for sensor cables which are longer than 10m. use
shielded twisted connecting cables (e.g.,LiYCY (TP) 2 x 2 x
0.5 mm
2
).
For TC sensors, use the corresponding shielded TC con-
necting cable according to DINEN60584-3/ISO60584-3.
For optimum shield connection directly before the module,
use the AXLSHIELDSET Axioline shield connection set
(see ordering data).
Please refer to the UMENAXLSYSINST user manual for
information on how to install the set and connect the shield.
For installation in a control cabinet: connect the cable shield
to functional earth ground immediately after the cables enter
the control cabinet. Route the shield as far as the AxiolineF
temperature module without interruption.
10 Configuration notes
Always position temperature modules at the end of the sta-
tion. For modules that must be positioned next to a bus cou-
pler, the typical measuring tolerance can be increased by up
to 0.9K.
I
In
AC/DC input current, 0mA ... 200mA up
to 0A ... 11A, 15Hz ... 400Hz
U
Out
-5VDC ... +5VDC output voltage
MCR-S-1-5-UI(-
SW)-DCI
Current transducer
Make sure that the shielded twisted sensor
cable is no more than 5m in length from the
current transducer to the temperature mod-
ule.
If longer cable lengths are required, connect
appropriate converters or signal conditioners
upstream.
The MCR range from PhoenixContact offers
a comprehensive range of products for this.