AXL F UTH4 1H
8672_en_02 PHOENIX CONTACT 4
Dimensions (nominal sizes in mm)
Width 35 mm
Height 126.1 mm
Depth 54 mm
Note on dimensions The depth is valid when a TH35-7.5 DIN rail is used (according to EN60715).
4 Technical data
35
54
122,4
126,1
General data
Color traffic grey A RAL 7042
Weight 144 g (with connectors and bus base module)
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Mounting position Any (no temperature derating)
Connection data
Designation AxiolineF connector
Connection method Push-in technology
Conductor cross section solid / stranded 0.2 mm² ... 1.5 mm² / 0.2 mm² ... 1.5 mm²
Conductor cross section [AWG] 24 ... 16
Stripping length 8 mm
Interface AxiolineFlocal bus
Connection method Bus base module
Transmission speed 100 MBit/s
Communications power
Communications power U
Bus
5 V DC (via bus base module)
Current consumption from U
Bus
typ. 112 mA, max. 160 mA
Power consumption at U
Bus
typ. 0.54 W, max. 0.8 W
AXL F UTH4 1H
8672_en_02 PHOENIX CONTACT 5
I/O supply
Supply of analog modules U
A
24 V DC
Maximum permissible voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption from U
A
typ. 23 mA
max. 40 mA
Power consumption at U
A
typ. 0.55 W, max. 0.96 W
Surge protection of the supply voltage Electronic (35 V, 0.5 s)
Polarity reversal protection of the supply voltage Polarity protection diode
Transient protection Suppressor diode
Total power consumption of the module
Power consumption typ. 1.05 W (entire device), max. 1.76 W (entire device)
The typical values for current and power consumption (logic/I/O/total) are measured values, the maximum values are theoretical worst-case
values.
Analog inputs
Number of inputs 4 +1 (4 inputs for thermocouples or linear voltage, plus 1 input -5V to +5V)
Connection method Spring-cage connection with direct connector-in method
Connection method 2-wire (shielded, twisted pair)
Sensor types that can be used (TC) U, T, L, J, E, K, N, S, R, B, C, W, HK
Sensor types (RTD) that can be used Pt 100 (2 external cold junctions, can also be used as a sensor input)
Resolution A/D 24 bit
Measuring principle Sigma/Delta process
Measured value representation 16 bits (15 bits + sign bit)
Input filter time 40 ms, 60 ms, 100 ms, 120 ms (adjustable)
Relative accuracy typ. 0.01 % (Thermocouple typeK, NiCr-Ni; see tables under tolerance values)
Absolute accuracy typ. ± 0.19 K (Thermocouple type K, plus tolerance of cold junction)
Short-circuit protection, overload protection of the inputs yes
Transient protection of inputs yes
Crosstalk attenuation typ. 113 dB (Channel/channel, sensor type K)
typ. 114 dB (Channel/channel, sensor type linear voltage ±100 mV)
typ. 107 dB (Channel/channel, external Pt100 connection)
Common mode rejection (CMR): TC inputs/linear voltage min. 100 dB (Channel/FE; for DC up to 100kHz, V
cm
= -10V ... +10V)
Common mode rejection (CMR): TC inputs/linear voltage typ. 140 dB (Channel/FE; for DC up to 100kHz, V
cm
= -10V ... +10V)
Common mode rejection (CMR): TC inputs/linear voltage min. 100 dB (Channel/AGND; for DC up to 100kHz, V
cm
= -10V ... +10V)
Common mode rejection (CMR): TC inputs/linear voltage typ. 131 dB (Channel/AGND; for DC up to 100kHz, V
cm
= -10V ... +10V)
Common mode rejection (CMR): Voltage input -5V ... +5V min. 95 dB (Channel/FE; for DC up to 100kHz, V
cm
= -10V ... +10V)
Common mode rejection (CMR): Voltage input -5V ... +5V typ. 105 dB (Channel/FE; for DC up to 100kHz, V
cm
= -10V ... +10V)
Input resistance: TC inputs/linear voltage typ. 20 M (With 24 V I/O supply voltage present)
Input resistance: Voltage input -5V ... +5V typ. 5 M (With 24 V I/O supply voltage present)
Voltage at the TC input max. 40 V DC (1 min.)
Fieldbus data telegram
Fieldbus system PROFIBUS DP
Required parameter data 12 Byte
Need for configuration data 7 Byte
AXL F UTH4 1H
8672_en_02 PHOENIX CONTACT 6
Electrical isolation/isolation of the voltage areas
Test section Test voltage
5 V communications power (logic), 24 V supply (I/O) 500 V AC, 50 Hz, 1 min
5 V supply (logic)/functional earth ground 500 V AC, 50 Hz, 1 min
24 V supply (I/O) / functional earth ground 500 V AC, 50 Hz, 1 min
Mechanical tests
Vibration resistance in acc. with EN60068-2-6/IEC60068-2-6 5g
Shock in acc. with EN60068-2-27/IEC60068-2-27 30g
Continuous shock according to EN60068-2-27/IEC60068-2-27 10g
Conformance with EMC Directive 2004/108/EC
Noise immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD) EN61000-4-2/IEC61000-4-2 Criterion B; 6 kV contact discharge, 8 kV air discharge
Electromagnetic fields EN61000-4-3/IEC61000-4-3 Criterion A; Field intensity: 10 V/m
Fast transients (burst) EN61000-4-4/IEC61000-4-4 Criterion A for shielded cables; 2kV
Transient surge voltage (surge) EN61000-4-5/IEC61000-4-5 Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); ±1 kV
to shielded I/O cables
Conducted interference EN61000-4-6/IEC61000-4-6 Criterion A; Test voltage 10 V
Noise emission test according to EN 61000-6-3
Radio interference properties EN 55022 Class B
Conducted noise emission test according to EN55016-2-1 and EN55016-
1-2; 9kHz ... 30MHz
Class A
Approvals
For the latest approvals, please visit phoenixcontact.net/products.

2688598

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
I/O Modules AXL F UTH4 1H
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet