AXL F UTH4 1H
8672_en_02 PHOENIX CONTACT 10
5.7 Switch-on behavior of TC inputs with internal
cold junction compensation
Figure 1 Typical switch-on behavior of typeK TC sen-
sors with internal cold junction compensation
1. The switch-on behavior must only be taken into consid-
eration for TC measurements with internal cold junction
temperature, it does not apply for differential measure-
ments or measurements with external compensation.
2. The typical characteristic curves of the TC inputs after
power up were recorded in the preferred mounting posi-
tion (horizontal), in nominal operation (U
A
=24V,
T
A
=25°C),and with unobstructed ventilation ducts
(free air flow).
3. The measurement is performed within an AxiolineF sta-
tion in which another AXLFUTH41H module is located
to the right and left of the module in question.
4. Different installation positions or arrangements where
the module is affected by external sources of heat can
result in a different thermal switch-on behavior.
5. The measuring probes of the typeK TC sensors were
kept at a constant temperature.
In the event of sudden changes in the ambient temperature
of the temperature module (e.g.,from T
A
=+25°Cto
T
A
=+60°C),the time curve for the transient response is
comparable with that of the switch-on behavior.
5.8 Switch-on behavior of TC inputs with external
cold junction compensation
The module supports the connection of up to two external
Pt100 cold junction sensors.
Connection example: Figure 8
If you use this function, use copper cables from the isother-
mal cold junction up to the module connector.
The advantage of this is the very fast warm-up behavior of
just a few seconds.
Even in the event of extreme temperature fluctuations in the
environment where the AxiolineF station is located, the sys-
tem operates very quickly and precisely. There is also the
option of adjusting all sensor and cable tolerances in the ap-
plication via an additional path calibration function.
Figure 2 Typical switch-on behavior of typeK TC sen-
sors with external Pt100 cold junction com-
pensation and path calibration function for the
cold junction at connector1 at an ambient tem-
perature of +25°C
K1 ... K4 Channel 1 ... channel 4
Transient period Typical tolerance
5 minutes -0.7K
10 minutes -0.3 K
35 minutes ±0.2K
45 minutes ±0.2K
K 1
K 2
K 3
K 4
T [°C]
t [min]
-0,6
-0,4
-0,2
0,0
0,2
0,4
0
14 28 42
56 70
1 Maximum tolerance limit
2 Minimum tolerance limit
K1 ... K4 Channel 1 ... channel 4
-0,8
-0,6
-0,4
-0,2
0
0,2
0,4
0,6
0,8
K 1
K 2
K 3
K 4
0
2,5
5
7,5
10
12,5
15
17,5
20
T [°C]
t [min]
AXL F UTH4 1H
8672_en_02 PHOENIX CONTACT 11
5.9 Technical data for cold junctions
Internal cold junctions
Simple cold junction compensation can be implemented for
the thermocouple inputs using the internal cold junctions.
To read the temperature of each internal cold junction for TC
channels, parameterize the sensor type as "Cold Junction".
For the accuracy, please refer to the tables of the tolerance
values.
Compensation of the mounting position of the internal
cold junction
In order that maximum accuracy is also achieved when in-
stalled in various different mounting positions, it is possible
to compensate the mounting position of the internal cold
junction.
Parameterize this compensation using the ParaTable ob-
ject, data format, mounting position.
Tolerances of the internal cold junction
* Thermally steady system without external heat influence
1. The data refers to nominal operation (U
A
=24V) in the
preferred mounting position (horizontal).
2. The measurement is performed within an AxiolineF sta-
tion in which another AXLFUTH41H module is located
to the right and left of the module in question.
ExternalPt 100 cold junctions
When using external isothermal blocks or distributed termi-
nal boxes, an external cold junction is recommended. The
advantage of this is an improved switch-on behavior and the
very fast thermal transient period in the event of sudden
changes to the ambient temperature of the measuring sta-
tion.
You can connect up to two Pt 100 sensors to the
AXLFUTH41H module.
You can also use the inputs for the external cold junction
sensors as sensor inputs for any applications with Pt100
and connection with 2-wire technology. To do so, parame-
terize the sensor type as “Cold junction” and the cold junc-
tion type as “External Pt100” on the corresponding connec-
tor.
Tolerances of the external Pt100 cold junction inputs
The data contains the offset error, gain error, and linearity
error in its respective setting.
The data is valid for nominal operation (preferred mounting
position, U
A
=24V).
The documented typical tolerances were determined for ref-
erence cable type LiYCY (TP) 2 x 2 x 0.5mm² with a con-
nection length <1m.
The drift data and the tolerances specified as a percentage
refer to the measuring range final value of+400°C.
The typical data has been determined in an example Axi-
olineF station.
Typical tolerance values are measured application values
that are based on the maximum variance of all test objects.
The maximum tolerance values represent the worst-case
measurement inaccuracy. They contain the theoretical max-
imum possible tolerances in the corresponding measuring
ranges as well as the theoretical maximum possible toler-
ances of the calibration and test equipment. The data is valid
for at least 24months from delivery of the module. Thereaf-
Internal cold junction
Connection method 2-wire connection
Sensor type Pt100 DIN
R
0
(sensor resistance at T
A
=0°C) 100
Measuring range -55°C...+125°C
Resolution (process data) 0.1 K/LSB
Resolution (floating point object) < 0.001 K
Filter time 120 ms
No. Tolerance struc-
ture
Temper-
ature
Tolerances
Typ. Max.
1 Cold junction tempera-
ture drift
-25°C ...
+60°C
10 ppm/K 25 ppm/K
2 Total tolerance of the in-
ternal cold junction
+25°C ±0.15K ±1.76K
3 Total tolerance of the in-
ternal cold junction
-25°C ...
+60°C
±0.852.4K
ExternalPt 100 cold junctions
Connection method 2-wire connection
Sensor type Pt100 DIN
R
0
(sensor resistance at T
A
=0°C) 100
Measuring range -100 °C...+400 °C
Resolution (process data) 0.1 K/LSB
Resolution (floating point object) < 0.001 K
Filter time 120 ms
No. Ambient
temperature
Tolerances
Typ. Max.
1Tolerances +25°C ±0.30.8K
2 Drift -25°C ... +60°C ±10ppm/K ±25 ppm/K
AXL F UTH4 1H
8672_en_02 PHOENIX CONTACT 12
ter the modules can be recalibrated by the manufacturer at
any time.
Drift response of the TC inputs with external cold
junction compensation
Figure 3 Typical tolerance distribution of type K TC de-
tection with external cold junction compensa-
tion and path calibration function for the cold
junction
The diagram shows the typical tolerance distribution in the
entire ambient temperature range of the module with
external Pt100 compensation and path calibration of the
cold junction in the entire ambient temperature
rangeofT
U
=-25°C...+60°C.
The advantages of external cold junction compensation are,
on the one hand, immediate measuring accuracy without
thermal switch-on behavior and, on the other hand, high
temperature stability.
For maximum accuracy, path calibration is possible. This
can be carried out channel-specific using object 008F
hex
.
You can therefore calibrate the tolerances of the entire mea-
suring section including the sensor and connecting cable.
To achieve maximum accuracy (< ±0.1K, it is
possible to calibrate a measuring section.
To do so, carry out fine adjustment of the tol-
erances of the connecting cables and the ex-
ternal Pt 100 sensor with object 008F
hex
: local
adjust values.
1 Ambient temperature+25°C
2 Ambient temperature+60°C
3 Ambient temperature-25°C
K1 ... K4 Channel 1 ... channel 4
T [°C]
K 1
K 2
K 3
K 4
-0,5
-0,4
-0,3
-0,2
-0,1
0
0,1
0,2
0,3
0,4
0,5

2688598

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
I/O Modules AXL F UTH4 1H
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet