Operation M41T00AUD
10/42 Doc ID 13480 Rev 5
4 Operation
The M41T00AUD clock operates as a slave device on the serial bus. Access is obtained by
implementing a start condition followed by the correct slave address (D0h). The 10 bytes
contained in the device can then be accessed sequentially in the following order:
The M41T00AUD continually monitors V
CC
for an out of tolerance condition. Should V
CC
fall
below V
PFD
, the device terminates an access in progress and resets the device address
counter. Inputs to the device will not be recognized at this time to prevent erroneous data
from being written to the device from an out of tolerance system. When V
CC
falls below V
SO
,
the device automatically switches over to the backup battery or capacitor and powers down
into an ultra low current mode of operation to conserve battery life. Upon power-up, the
device switches from battery to V
CC
at V
SO
and recognizes inputs.
Table 2. List of registers
Byte address Contents
00h Seconds register
01h Minutes register
02h Century/hours register
03h Day register
04h Date register
05h Month register
06h Years register
07h Calibration/control register
08h Audio register
09h Control2 register
M41T00AUD Operation
Doc ID 13480 Rev 5 11/42
4.1 2-wire bus characteristics
This bus is intended for communication between different ICs. It consists of two lines: one
bi-directional for data signals (SDA) and one for clock signals (SCL). Both the SDA and the
SCL lines must be connected to a positive supply voltage via a pull-up resistor.
The following protocol has been defined:
Data transfer may be initiated only when the bus is not busy.
During data transfer, the data line must remain stable whenever the clock line is high.
Changes in the data line while the clock line is high will be interpreted as control
signals.
Accordingly, the following bus conditions have been defined:
Bus not busy. Both data and clock lines remain high.
Start data transfer. A change in the state of the data line, from high to low, while the
clock is high, defines the START condition.
Stop data transfer. A change in the state of the data line, from low to high, while the
clock is high, defines the STOP condition.
Data valid. The state of the data line represents valid data when after a start condition,
the data line is stable for the duration of the high period of the clock signal. The data on
the line may be changed during the low period of the clock signal. There is one clock
pulse per bit of data.
Each data transfer is initiated with a start condition and terminated with a stop condition.
The number of data bytes transferred between the start and stop conditions is not limited.
The information is transmitted byte-wide and each receiver acknowledges with a ninth bit.
By definition, a device that gives out a message is called "transmitter", the receiving device
that gets the message is called "receiver". The device that controls the message is called
"master". The devices that are controlled by the master are called "slaves".
Acknowledge. Each byte of eight bits is followed by one acknowledge bit. This
acknowledge bit is a low level put on the bus by the receiver, whereas the master
generates an extra acknowledge related clock pulse.
A slave receiver which is addressed is obliged to generate an acknowledge after the
reception of each byte. Also, a master receiver must generate an acknowledge after the
reception of each byte that has been clocked out of the slave transmitter.
The device that acknowledges has to pull down the SDA line during the acknowledge clock
pulse in such a way that the SDA line is a stable Low during the high period of the
acknowledge related clock pulse. Of course, setup and hold times must be taken into
account. A master receiver must signal an end-of-data to the slave transmitter by not
generating an acknowledge on the last byte that has been clocked out of the slave. In this
case, the transmitter must leave the data line high to enable the master to generate the
STOP condition.
Operation M41T00AUD
12/42 Doc ID 13480 Rev 5
Figure 5. Serial bus data transfer sequence
Figure 6. Acknowledgement sequence
Figure 7. Bus timing requirements sequence
Note: P = STOP and S = START
AI00587
DATA
CLOCK
DATA LINE
STABLE
DATA VALID
START
CONDITION
CHANGE OF
DATA ALLOWED
STOP
CONDITION
AI00601
DATA OUTPUT
BY RECEIVER
DATA OUTPUT
BY TRANSMITTER
SCLK FROM
MASTER
START
CLOCK PULSE FOR
ACKNOWLEDGEMENT
12 89
MSB LSB
AI00589
SDA
P
t
SU:STO
t
SU:STA
t
HD:STA
SR
SCL
t
SU:DAT
t
F
t
HD:DAT
t
R
t
HIGH
t
LOW
t
HD:STA
t
BUF
SP

M41T00AUDD1F

Mfr. #:
Manufacturer:
STMicroelectronics
Description:
Real Time Clock SERIAL RTC W/AUDIO
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet