MAX16047/MAX16049
*
MAX16047 only
Table 17. Critical Fault Configuration and Enable Bits (continued)
REGISTER/ EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[0] 1 = Fault log triggered when MON9 is above/below its early warning threshold*
[1] 1 = Fault log triggered when MON10 is above/below its early warning threshold*
[2] 1 = Fault log triggered when MON11 is above/below its early warning threshold*
[3] 1 = Fault log triggered when MON12 is above/below its early warning threshold*
4Ch
[7:4] Not used
*
MAX16047 only
Table 18. Fault Log EEPROM
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[3:0]
Power-Up/Power-Down Fault Register
Slot where power-up/power-down fault is detected
[4]
Tracking Fault Bits
If ‘0,’ tracking fault occurred on MON1/EN_OUT1/INS1
[5] If ‘0,’ tracking fault occurred on MON2/EN_OUT2/INS2
[6] If ‘0,’ tracking fault occurred on MON3/EN_OUT3/INS3
00h
[7] If ‘0,’ tracking fault occurred on MON4/EN_OUT4/INS4
[0] If ‘1,’ fault occurred on MON1
[1] If ‘1,’ fault occurred on MON2
[2] If ‘1,’ fault occurred on MON3
[3] If ‘1,’ fault occurred on MON4
[4] If ‘1,’ fault occurred on MON5
[5] If ‘1,’ fault occurred on MON6
[6] If ‘1,’ fault occurred on MON7
01h
[7] If ‘1,’ fault occurred on MON8
[0] If ‘1,’ fault occurred on MON9*
[1] If ‘1,’ fault occurred on MON10*
[2] If ‘1,’ fault occurred on MON11*
[3] If ‘1,’ fault occurred on MON12*
02h
[7:4] Not used
03h [7:0]
MON_ ADC Fault Information (only the 8 MSBs of converted channels are saved following
a fault event)
MON1 conversion result at the time the fault log was triggered
04h [7:0] MON2 conversion result at the time the fault log was triggered
05h [7:0] MON3 conversion result at the time the fault log was triggered
06h [7:0] MON4 conversion result at the time the fault log was triggered
07h [7:0] MON5 conversion result at the time the fault log was triggered
08h [7:0] MON6 conversion result at the time the fault log was triggered
09h [7:0] MON7 conversion result at the time the fault log was triggered
0Ah [7:0] MON8 conversion result at the time the fault log was triggered
0Bh [7:0] MON9 conversion result at the time the fault log was triggered*
0Ch [7:0] MON10 conversion result at the time the fault log was triggered*
0Dh [7:0] MON11 conversion result at the time the fault log was triggered*
0Eh [7:0] MON12 conversion result at the time the fault log was triggered*
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 37
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
38 ______________________________________________________________________________________
Power-Up/Power-Down Faults
All EN_OUTs are deasserted if an overvoltage or under-
voltage fault is detected during power-up/power-down
(regardless of the critical fault enable bits). Under these
conditions, information of the failing slot is stored in
EEPROM r00h[3:0] unless the fault register is config-
ured not to store any information by setting r47h[1:0] to
‘11’ (see Table 17).
If there is a tracking fault on a channel configured for
closed-loop tracking, a fault log operation occurs and the
bits representing the failed tracking channels are set to
‘0’ unless the fault register is configured not to store any
information by setting r47h[1:0] to ‘11’ (see Table 17).
Autoretry/Latch Mode
For critical faults, the MAX16047/MAX16049 can be
configured for one of two fault management methods:
autoretry or latch-on-fault. Set r4Fh[3] to ‘0’ to select
autoretry mode. In this configuration, the device will
shut down after a critical fault event then restart follow-
ing a configurable delay. Use r4Fh[2:0] to select an
autoretry delay from 20µs to 1.6s. See Table 19 for
more information on setting the autoretry delay.
Set r4Fh[3] to ‘1’ to select the latch-on-fault mode. In
this configuration EN_OUT_s are deasserted after a
critical fault event. The device does not re-initiate the
power-up sequence until EN is toggled or the Software
Enable bit is reset to ‘0.’ See the
Enable
section for
more information on setting the Software Enable bit.
If fault information is stored in EEPROM (see the
Critical
Faults
section) and autoretry mode is selected, set an
autoretry delay greater than the time required for the
storing operation. If fault information is stored in EEP-
ROM and latch-on-fault mode is chosen, toggle EN or
reset the Software Enable bit only after the completion
of the storing operation. If saving information about the
failed lines only, ensure a delay of at least 60ms before
the restart procedure. Otherwise, ensure a minimum
204ms timeout. This ensures that ADC conversions are
completed and values are stored correctly in EEPROM.
See Table 20 for more information about required fault
log operation periods.
Table 19. Fault Recovery Configuration
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[2:0]
Autoretry Delay
000 = 20µs
001 = 12.5ms
010 = 25ms
011 = 50ms
100 = 100ms
101 = 200ms
110 = 400ms
111 = 1.6s
[3]
Fault Recovery Mode
0 = Autoretry procedure is performed following a fault event
1 = Latchoff on fault
[5:4]
Slew Rate
00 = 800V/s
01 = 400V/s
10 = 200V/s
11 = 100V/s
4Fh
[7:6]
Fault Deglitch
00 = 2 conversions
01 = 4 conversions
10 = 8 conversions
11 = 16 conversions
MAX16047/MAX16049
RESET
The reset output, RESET, is asserted during power-
up/power-down and deasserts following the reset time-
out period once the power-up sequence is complete.
The power-up sequence is complete when any MON_
inputs assigned to Slot 12 exceed their undervoltage
thresholds. If no MON_ inputs are assigned to Slot 12,
the power-up sequence is complete after the slot
sequence delay is expired.
RESET is a configurable output that monitors selected
MON_ voltages during normal operation. RESET also
depends on any monitoring input that has one or more
critical fault enable bits set. Use r19h[1:0] to configure
RESET to assert on an overvoltage fault, undervoltage
fault, or both. Use r19h[3:2] to configure RESET as an
active-high/active-low push-pull/open-drain output. If
desired, configure GPIO4 as a manual reset input, MR,
and pull MR low to assert RESET. RESET includes a
programmable timeout. See Table 21 for RESET depen-
dencies and configuration registers.
Table 20. EEPROM Fault Log Operation Period
FAULT CONTROL
REGISTER r47h[1:0]
DESCRIPTION
MINIMUM REQUIRED SHUTDOWN PERIOD
(ms)
00 Failed lines and ADC values saved 204
01 Failed lines saved 60
10 ADC values saved 168
11 No information saved N/A
Table 21. RESET Configuration and Dependencies
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[1:0]
RESET OUTPUT CONFIGURATION
00 = RESET is asserted if at least one of the selected inputs exceeds its undervoltage
threshold
01 = RESET is asserted if at least one of the selected inputs exceeds its early warning
threshold
10 = RESET is asserted if at least one of the selected inputs exceeds its overvoltage threshold
11 = RESET is asserted if any of the selected inputs exceeds undervoltage or overvoltage
thresholds
[2]
0 = RESET is an active-low output
1 = RESET is an active-high output
[3]
0 = RESET is a open-drain output
1 = RESET is an push-pull output
[6:4]
RESET TIMEOUT
000 = 25µs
001 = 2ms
010 = 25ms
011 = 100ms
100 = 200ms
101 = 400ms
110 = 800ms
111 = 1600ms
19h
[7] Reserved
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 39

MAX16047ETN+T

Mfr. #:
Manufacturer:
Maxim Integrated
Description:
Supervisory Circuits 12Ch EEPROM Prob System Manage
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet